Loading...
HomeMy WebLinkAbout792-792-12358 Norfolk Ave, Easton, MA 02375 • Tel 508 822 6934 • www.swcole.com Report of Concrete Compressive Strength ASTM C31, ASTM C39, ASTM C1231 Project Name:Yarmouth MA - Town of Yarmouth Water Resource Recovery Facility - Concrete Testing Services Client:Wright-Pierce Project #:25-0468 Report Date:4/29/2026 Concrete Supplier:Cape Cod Ready Mix PLACEMENT INFORMATION Date Cast: 4/22/2026 Time Cast: 7:30 AM Date Received: 4/24/2026 Placement Location:SBR SLABS 13, 14, 16 Placement Method:PUMP Cylinders Made By:Alexander Charnitsky Material Type:Concrete Cylinders Placement Vol. (yd ):175 Aggregate Size (in):1 1/2 Cylinder Size:6 x 12 INITIAL CURING CONDITION DELIVERY INFORMATION Temperatures Minimum (°F):Maximum (°F): Admixtures: TEST RESULTS Slump (in) (C-143):7 Air Content (%) (C-231):5.1 Air Temp (°F):46 Conc. Temp (°F) (C-1064):65 Load Number:7 Mixer Num.:76 Ticket Num.:35297 Cubic Yards:11 Design (psi):4500 Batch 6:34 AM Arrive 7:16 AM Depart 7:30 AM Cylinder Designation Defect (Y/N) Cylinder Weight (lbs) Cylinder Diameter (in) Cross Sectional Area (in ) Date Of Test Cure Type Cap Type Age (Days) Fracture Type Load (kips) Strength (psi) 792-123A N 29.45 5.99 28.13 4/29/2026 Lab Unbonded 7 5 120.14 4260 792-123B 29.20 5/6/2026 Lab 14 792-123C 29.20 5/20/2026 Lab 28 792-123D 29.20 5/20/2026 Lab 28 792-123E 29.15 5/20/2026 Lab 28 792-123F 29.20 HOLD Lab 3 2 Remarks:Kaylie OSullivan Reviewed By