Loading...
HomeMy WebLinkAbout792-792-118 (4)58 Norfolk Ave, Easton, MA 02375 • Tel 508 822 6934 • www.swcole.com Report of Concrete Compressive Strength ASTM C31, ASTM C39, ASTM C1231 Project Name:Yarmouth MA - Town of Yarmouth Water Resource Recovery Facility - Concrete Testing Services Client:Wright-Pierce Project #:25-0468 Report Date:5/7/2026 Concrete Supplier:Cape Cod Ready Mix PLACEMENT INFORMATION Date Cast: 4/9/2026 Time Cast:Date Received: 4/10/2026 Placement Location:SPR SLABS 7, 12, 13 SOLIDS HANDLING COLUMNS Placement Method:PUMP Cylinders Made By:Mohammed Rifaz Material Type:Concrete Cylinders Placement Vol. (yd ):226 Aggregate Size (in):1 1/2 Cylinder Size:6 x 12 INITIAL CURING CONDITION DELIVERY INFORMATION Temperatures Minimum (°F):Maximum (°F): Admixtures:SIKA 75 TEST RESULTS Slump (in) (C-143):3 Air Content (%) (C-231):3.8 Air Temp (°F):48 Conc. Temp (°F) (C-1064):60 Load Number:11 Mixer Num.:56 Ticket Num.:35140 Cubic Yards:11 Design (psi):4500 Batch 7:24 AM Arrive Depart Cylinder Designation Defect (Y/N) Cylinder Weight (lbs) Cylinder Diameter (in) Cross Sectional Area (in ) Date Of Test Cure Type Cap Type Age (Days) Fracture Type Load (kips) Strength (psi) 792-118A N 29.10 6 28.27 4/13/2026 Lab Unbonded 4 5 106.97 3780 792-118B N 29.10 6 28.27 4/16/2026 Lab Unbonded 7 5 141.22 5000 792-118C N 29.15 6.01 28.37 4/23/2026 Lab Unbonded 14 5 142.99 5040 792-118D N 29.30 6 28.32 5/7/2026 Lab Unbonded 28 5 145.8 5160 792-118E N 29.35 6 28.27 5/7/2026 Lab Unbonded 28 5 147.35 5210 3 2 Remarks:Kaylie OSullivan Reviewed By