HomeMy WebLinkAboutCCOR 05-18-2026 792-140Concrete Construction Observation Report
The S.W.COLE field representative is on-site at the request of our client to provide construction materials testing and to observe and document construction activities. The Contractor has soleresponsibility for schedule, site safety, methods, completeness and quality control.
58 Norfolk Ave, Easton, MA 02375 • Tel 508 822 6934 • www.swcole.com
Project Name:Town of Yarmouth Water Resource Recovery Facility Project NO.:25-0468Location:Yarmouth MA Date:5/18/2026
Client:Wright-Pierce Client Rep:Reyssa FonteCDM
Weather:Clear 62 - 71°F S.W.COLE Rep:Alexander
CharnitskyGeneral Contractor:Nickerson Time Onsite:06:30 - 09:15
Placement Type: Footing Wall Slab OtherPlacement Location:SBR Wall 2
Concrete Placement Observations Observed Comments
Required mix used Yes 4500psi, 1 1/2", Sika 75
Concrete properly conveyed to all areas of placement Yes Pump Truck
Internal vibration / consolidation of concrete Yes Handheld vibrator
Even layering around openings and embedments Yes Concrete evenly layered and vibrated around
openings and embedments
Post placement observations (finishing, curing, etc.)Yes Concrete Manually Finished
Field Testing of Concrete performed:Yes
*CYLINDER SET NO:792-140 *Refer to associated concrete test report
Notes:
As requested by Rayssa (CDM Smith), S.W.COLE rep was onsite to observe concrete placement
and perform concrete sampling and testing at the locations referenced above.
The S.W.COLE rep arrived onsite at approximately 6:30 AM. Concrete placement activities were
observed during the time of sampling and testing. Observations were limited to conditions
present and activities occurring at the time of the site visit.
One concrete delivery was observed during the site visit. Concrete Delivery No. 1 arrived
onsite consisting of approximately 10.5 cubic yards of 4,500‑psi concrete with 1‑1/2‑inch
nominal aggregate. The concrete reportedly included Sika® 75, which was added prior to
arrival. The concrete was placed via pump truck.
One set of field tests was performed on the sampled concrete with the following results:
Truck 53 – Load 1Slump: 8.5 inches
Air Content: 4 percent
Concrete Temperature: 70°F
One set of compression test cylinders was cast for laboratory testing at 7, 14, and 28 days (two
cylinders per test age), along with one hold cylinder. Test results will be reported separately
upon completion of laboratory testing.
Test results and field observations were verbally reported to the onsite Justin while onsite.
The S.W.COLE rep departed the site at approximately 9:15 AM after completing the requested
services.Attachments: 2 Photos Reviewed by:5/18/2026 Kaylie OSu iv Kaylie OSullivan