792-792-140 (1)
58 Norfolk Ave, Easton, MA 02375 • Tel 508 822 6934 • www.swcole.com Report of Concrete Compressive Strength ASTM C31, ASTM C39, ASTM C1231 Project Name:Yarmouth MA - Town of Yarmouth Water Resource Recovery Facility - Concrete Testing Services Client:Wright-Pierce Project #:25-0468 Report Date:5/26/2026 Concrete Supplier:Cape Cod Ready Mix PLACEMENT INFORMATION Date Cast: 5/18/2026 Time Cast: 7:12 AM Date Received: 5/19/2026 Placement Location:SBR WALL 2 Placement Method:PUMP Cylinders Made By:Alexander Charnitsky Material Type:Concrete Cylinders Placement Vol. (yd ):85 Aggregate Size (in):1 1/2 Cylinder Size:6 x 12 INITIAL CURING CONDITION DELIVERY INFORMATION Temperatures Minimum (°F):Maximum (°F): Admixtures:SIKA 75 TEST RESULTS Slump (in) (C-143):8 1/2 Air Content (%) (C-231):4 Air Temp (°F):56 Conc. Temp (°F) (C-1064):70 Load Number:1 Mixer Num.:53 Ticket Num.:51954 Cubic Yards:10.5 Design (psi):4500 Batch 6:37 AM Arrive 7:03 AM Depart 7:15 AM Cylinder Designation Defect (Y/N) Cylinder Weight (lbs) Cylinder Diameter (in) Cross Sectional Area (in ) Date Of Test Cure Type Cap Type Age (Days) Fracture Type Load (kips) Strength (psi) 792-140E N 28.95 6.02 28.42 5/21/2026 Lab Unbonded 3 5 109.49 3850 792-140A N 28.95 6 28.27 5/26/2026 Lab Unbonded 8 3 137.24 4850 792-140B 28.95 6/1/2026 Lab 14 792-140C 28.95 6/15/2026 Lab 28 792-140D 28.95 6/15/2026 Lab 28 3 2 Remarks:Kaylie OSullivan Reviewed By