Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
792-792-147 (1)
58 Norfolk Ave, Easton, MA 02375 • Tel 508 822 6934 • www.swcole.com Report of Concrete Compressive Strength ASTM C31, ASTM C39, ASTM C1231 Project Name:Yarmouth MA - Town of Yarmouth Water Resource Recovery Facility - Concrete Testing Services Client:Wright-Pierce Project #:25-0468 Report Date:6/17/2026 Concrete Supplier:Cape Cod Ready Mix PLACEMENT INFORMATION Date Cast: 6/3/2026 Time Cast: 10:40 AM Date Received: 6/4/2026 Placement Location:SBR WALLS 19 AND 12 Placement Method:PUMP Cylinders Made By:Mohammed Rifaz Material Type:Concrete Cylinders Placement Vol. (yd ):120 Aggregate Size (in):1 1/2 Cylinder Size:6 x 12 INITIAL CURING CONDITION DELIVERY INFORMATION Temperatures Minimum (°F):Maximum (°F): Admixtures:SIKA CONTROL 75, ENERGY SURCHARGE TEST RESULTS Slump (in) (C-143):7 1/2 Air Content (%) (C-231):4 Air Temp (°F):72 Conc. Temp (°F) (C-1064):74 Load Number:10 Mixer Num.:64 Ticket Num.:35921 Cubic Yards:11 Design (psi):4500 Batch 9:13 AM Arrive 10:06 AM Depart 11:00 AM Cylinder Designation Defect (Y/N) Cylinder Weight (lbs) Cylinder Diameter (in) Cross Sectional Area (in ) Date Of Test Cure Type Cap Type Age (Days) Fracture Type Load (kips) Strength (psi) 792-147A N 28.70 6 28.32 6/5/2026 Lab Unbonded 2 5 84.37 2980 792-147B N 28.65 6 28.23 6/17/2026 Lab Unbonded 14 5 119.36 4220 792-147C 28.80 7/1/2026 Lab 28 792-147D 28.80 7/1/2026 Lab 28 792-147E 28.80 HOLD Lab 3 2 Remarks:Kaylie O'Sullivan Reviewed By