HomeMy WebLinkAbout792-792-15058 Norfolk Ave, Easton, MA 02375 • Tel 508 822 6934 • www.swcole.com Report of Concrete Compressive Strength ASTM C31, ASTM C39, ASTM C1231 Project Name:Yarmouth MA - Town of Yarmouth Water Resource Recovery Facility - Concrete Testing Services Client:Wright-Pierce Project #:25-0468 Report Date:6/15/2026 Concrete Supplier:Cape Cod Ready Mix PLACEMENT INFORMATION Date Cast: 6/8/2026 Time Cast: 7:00 AM Date Received: Placement Location:N PROCESS BUILDING ELV 4.50 SLAB Placement Method:PUMP Cylinders Made By:Alexander Charnitsky Material Type:Concrete Cylinders Placement Vol. (yd ):40 Aggregate Size (in):3/4 Cylinder Size:6 x 12 INITIAL CURING CONDITION DELIVERY INFORMATION Temperatures Minimum (°F):Maximum (°F): Admixtures:SIKA 75 TEST RESULTS Slump (in) (C-143):7 Air Content (%) (C-231):4 Air Temp (°F):65 Conc. Temp (°F) (C-1064):72 Load Number:1 Mixer Num.:75 Ticket Num.:52270 Cubic Yards:10 Design (psi):4500 Batch 6:27 AM Arrive 6:45 AM Depart 7:00 AM Cylinder Designation Defect (Y/N) Cylinder Weight (lbs) Cylinder Diameter (in) Cross Sectional Area (in ) Date Of Test Cure Type Cap Type Age (Days) Fracture Type Load (kips) Strength (psi) 792-150A N 29.15 6 28.27 6/15/2026 Lab Unbonded 7 5 150.05 5310 792-150B 6/22/2026 Lab 14 792-150C 7/6/2026 Lab 28 792-150D 7/6/2026 Lab 28 792-150E 7/6/2026 Lab 28 3 2 Remarks:Kaylie O'Sullivan Reviewed By