HomeMy WebLinkAbout792-792-15358 Norfolk Ave, Easton, MA 02375 • Tel 508 822 6934 • www.swcole.com Report of Concrete Compressive Strength ASTM C31, ASTM C39, ASTM C1231 Project Name:Yarmouth MA - Town of Yarmouth Water Resource Recovery Facility - Concrete Testing Services Client:Wright-Pierce Project #:25-0468 Report Date:6/19/2026 Concrete Supplier:Cape Cod Ready Mix PLACEMENT INFORMATION Date Cast: 6/12/2026 Time Cast: 7:40 AM Date Received: 6/13/2026 Placement Location:MIDDLE PROCESS BUILDING ELV 19.50 Placement Method:PUMP Cylinders Made By:Alexander Charnitsky Material Type:Concrete Cylinders Placement Vol. (yd ):187 Aggregate Size (in):1 1/2 Cylinder Size:6 x 12 INITIAL CURING CONDITION DELIVERY INFORMATION Temperatures Minimum (°F):Maximum (°F): Admixtures:SIKA 25 TEST RESULTS Slump (in) (C-143):7 Air Content (%) (C-231):4.2 Air Temp (°F):68 Conc. Temp (°F) (C-1064):77 Load Number:10 Mixer Num.:51 Ticket Num.:36049 Cubic Yards:44 Design (psi):4500 Batch 7:09 AM Arrive 7:30 AM Depart 7:50 AM Cylinder Designation Defect (Y/N) Cylinder Weight (lbs) Cylinder Diameter (in) Cross Sectional Area (in ) Date Of Test Cure Type Cap Type Age (Days) Fracture Type Load (kips) Strength (psi) 792-153A N 29.05 6 28.27 6/19/2026 Lab Unbonded 7 3 100.09 3540 792-153B 29.05 6/26/2026 Lab 14 792-153C 29.05 7/10/2026 Lab 28 792-153D 29.05 7/10/2026 Lab 28 792-153E 29.05 HOLD Lab 3 2 Remarks:Kaylie O'Sullivan Reviewed By