HomeMy WebLinkAbout5197 20 Old Hyannis Rd Decision Recordedw RE
f;telC;9Ti NOV 1$'25� qQ
TOWN OF YARMOUTH
BOARD OF APPEALS
DECISION
FILED WITH TOWN CLERK: November 18, 2025
PETITION NO: 5197
HEARING DATE: October 9, 2025
Bk 37364 Pg159 #52121
12-16-2025 @ 12:42p
PETITIONER: Cellco Partnership d/b/a Verizon Wireless
PROPERTY OWNER: Town of Yarmouth
PROPERTY: 20 Old Hyannis Road, Yarmouth, MA
Map 104, Parcel 10
Zoning District: R40, Aquifer Protection Overlay
District
Title: Book 1795, Page 99
MEMBERS PRESENT AND VOTING: Chairman Sean Igoe, Dick Martin, John Mantoni,
Barbara Murphy, and Tim Scanlan
Notice of the hearing.has been given by sending notice thereof to the Petitioner and all those
owners of property as required by law, and to the public by posting notice of the hearing and
publishing in The Cape Cod Times, the hearing opened and held on the date stated above.
The subject property is located at 20 Old Hyannis Road, Yarmouth, MA 02575 (the "Property"),
which is located in the R-40 zoning district and the Aquifer Protection Overlay District
("APOD"). The Property is owned by the Town of Yarmouth and currently improved with a
Town -owned water tank and a wireless communications facility owned and operated by a
different wireless service provider. The Property is shown on Plan Book No. 266, Page No. 20
and contains approximately 9.89 acres.
The Petitioner, Cellco Partnership d/b/a Verizon Wireless, seeks to install an emergency power
generator to provide backup power for a permitted wireless communications facility to be
installed on the Town -owned water tank at the Property. The wireless communications facility,
minus the emergency power generator, was approved by the Building Department on November
14, 2024 in accordance with Section 6409(a) of Title VI of the Middle Class Tax Relief and Job
Creation Act of 2012, commonly known as the "Spectrum Act," and the Federal
Communications Commission (FCC) regulations implementing that section.
An APOD Special Permit is required because the emergency power generator will contain "toxic
or hazardous materials," as that term is defined in Section 406.6.1 of the Town of Yarmouth
TRUE QWY AT'EST:
Psi
DEC — 9 / chit I Towns CLERK
Bk 37364 Pg160 #52121
Zoning Bylaw ("Zoning Bylaw"), in quantities greater than those commonly associated with
normal household use, pursuant to Sections 406.5 and 103.2 of the Zoning Bylaw. The generator
will run on diesel fuel contained in a double -walled steel fuel tank with a maximum capacity of
300 gallons. The generator will also hold 14.4 quarts of engine oil, 4.5 gallons of engine
antifreeze and a generator starter battery containing approximately 27.7 pounds of lead and 8.14
pounds (0.5 gallons) of sulfuric acid. Complete secondary containment for the diesel fuel tank is
provided at 120% of the fuel tank's capacity. Secondary containment for the antifreeze, engine
oil and small fuel spills from the engine are provided by a top -of -fuel -tank containment pan that
is designed to capture any fluid released from the generator above and has an approximately 29-
gallon containment capacity. The top -of -fuel -tank containment pan consists of the top steel
surface of the fuel tank and the four steel sides of the fuel tank, which extend 2.5 inches above
the top. The containment area measures 2.5 inches high by 76.91 inches long by 35.67 inches
wide.
At the hearing, no members of the public spoke in favor or in opposition to the petition.
The Petitioner is seeking the following relief:
1. Petitioner is seeking a Special Permit pursuant to Sections 406 and 103.2 of the Zoning
Bylaw for the installation of an emergency power generator to provide backup power for
a permitted wireless communications facility to be installed on and adjacent to the Town -
owned water tank on the Property.
The Petitioner, through its representative, presented evidence establishing how the proposed
emergency power generator complies with the Special Permit requirements set forth in Sections
103.2 and 406 of the Zoning Bylaw. Specifically, the Petitioner established that the proposed
emergency power generator will not result in impacts to the public drinking water supply in the
Town of Yarmouth. Secondary containment for the fuel tank is provided by the fuel tank's
double -walled design, which provides containment at 120% of the fuel tank's capacity.
Secondary containment for the antifreeze, engine oil, and small fuel spills from the engine is
provided by a top -of -fuel -tank containment pan that is designed to capture any fluid released
from the generator above and has an approximately 29-gallon containment capacity. If a leak
were to occur, the Petitioner has measures in place in accordance with the Emergency Spill
Response Plan filed with the Board, as part of this application, and revised on October 20, 2025
to correct a typographical error.
The Petitioner also established that the proposed emergency power generator has been well -
vetted by the Yarmouth Board of Health. On July 7, 2025, the Petitioner appeared before the
Board of Health, which unanimously voted to recommend the proposal to the Zoning Board of
Appeals for relief, based on the ability of the proposal to comply with the Town of Yarmouth
Board of Health Regulation: "Handling and Storage of Toxic or Hazardous Materials." The
Petitioner, through its representative, testified to reviewing the Memorandum drafted by Carl E.
Lawson, Jr., the Hazardous Materials Inspector for the Yarmouth Health Department, dated
August 6, 2025 (the "Memorandum") and that the petition before the Board addresses the
concerns in the Memorandum.
A TRUE COPY ATTEST:
&q,a. Aq&X44h4
CMM ; CMG 1 TOWN CLERK
DEC — 9 Sus
Bk 37364 Pg161 #52121
The Board reviewed the Memorandum and was satisfied that the proposed emergency power
generator would meet the requirements under the Zoning Bylaw for the issuance of a Special
Permit with the imposition of the requirements and recommendations recited in the
Memorandum. As such, the Memorandum is hereby incorporated in its entirety and attached
hereto.
Regarding the request for Special Permit, the Board found that the Petitioner demonstrated that it
has met the criteria for a Special Permit, that no undue nuisance, hazard, or congestion will be
created and that there will be no substantial harm to the established or future character of the
neighborhood or town. The Board also found that the Petitioner demonstrated that it has met the
criteria under Section 406 of the Zoning Bylaw, that there will be no danger to the public
drinking water supply and that it has made adequate safeguards to ensure that.
Accordingly, a motion was made by Mr. Scanlan, and seconded by Mr. Martin, to approve the
Special Permit, as requested, incorporating the Memorandum of the Hazardous Materials
Inspector, dated August 6, 2025, in its entirety. A roll call vote was taken on this Motion with the
following results: Mr. Igoe - AYE; Mr. Martin - AYE; Mr. Mantoni - AYE; Ms. Murphy - AYE;
and Mr. Scanlan - AYE.
Accordingly, the Special Permit was approved on a 5-0 vote in favor, with the following
conditions:
I. The Memorandum drafted by Carl E. Lawson, Jr., the Hazardous Materials Inspector for
the Yarmouth Health Department, dated August 6, 2025, is incorporated into the
Decision in its entirety, and the requirements and recommendations set forth therein are
conditions of this Special Permit; and
2. The Petitioner furnish the Board with the name of a local contractor that will respond to
an emergency in the event there is one.
No permit shall issue until 20 days from the filing of this decision with the Town Clerk. Appeals
from this decision shall be made pursuant to MGL c40A section 17 and must be filed within 20
days after filing of this notice/decision with the Town Clerk. Unless otherwise provided herein,
the Special Permit shall lapse if a substantial use thereof has not begun within 24 months. (See
bylaw § 103.2.5, MGL c40A §9)
Sean Igoe, Chairman
A TRUE COPY ATTEST.
CMMD I CMG I TOWN CLEFK
Bk 37364 Pg162 #52121
CERTIFICATION OF TOWN CLERK
1, Mary A. Maslowski, Town Clerk, Town of Yarmouth, do hereby certify that 20 days have
elapsed since the filing with me of the above Board of Appeals Decision #5197 that no notice of
appeal of said decision has been filed with me, or, if such appeal has been filed it has been
dismissed or denied. All appeals have been exhausted.
%1&WU*VJ4
Mary A. Maslowski, MMC, CMMC
UZI - 9 2025
Bk 37364 Pg163 #52121
g Yq� COMMONWEALTH OF MASSACHUSETTS
TOWN OF YARMOUTH
4.�..rs Or! t BOARD OF APPEALS
F,�C�RApRASED �%
Petition #: 5197 Date: December 9, 2025
Certificate of Granting of a Special Permit
(General Laws Chapter 40A, Section 11)
The Board of Appeals of the Town of Yarmouth Massachusetts hereby certifies that a Special Permit has been
granted to:
PETITIONER: Cellco Partnership d/b/a Verizon Wireless
PROPERTY OWNER: Town of Yarmouth
Affecting the rights of the owner with respect to land or buildings at: 20 Old Hyannis Road, Yarmouth, MA;
Map 104, Parcel 10; Zoning District: R40, Aquifer Protection Overlay District; Title: Book 1795, Page
99 and the said Board of Appeals further certifies that the decision attached hereto is a true and correct copy of
its decision granting said Special Permit, and copies of said decision, and of all plans referred to in the decision,
have been fled.
The Board of Appeals also calls to the attention of the owner or applicant that General Laws, Chapter 40A,
Section 11 (last paragraph) and Section 13, provides that no Special Permit, or any extension, modification or
renewal thereof, shall take effect until a copy of the decision bearing the certification of the Town Clerk that
twenty (20) days have elapsed after the decision has been filed in the office of the Town Clerk and no appeal
has been filed or that, if such appeal has been filed, that it has been dismissed or denied, is recorded in the
Registry of Deeds for the county and district in which the land is located and indexed in the grantor index under
the name of the owner of record or is recorded and noted on the owner's certificate of title. The fee for such
recording or registering shall be paid by the owner or applicant.
k�
Sean Igoe, Chairman
A TRUE COPY ATTEST
&q'a- A40VIM4
CM / CMC / TOWN GLEFK
DEC - 9 2025
Bk 37364 Pg164 #52121
TO:
FROM:
TOWN OF YARMOUTH OARDOF
HE
1146 ROUTE 28, SOUTH YARMOUTH, MASSACHUSETTS 02664-24451 HEALTH
Tcicphone (508) 398-2231. ext. 1241 DIVISION
Fax (548)760.3472
RECEIVED
SEP 2 9 2025
MEMORANDUM YAAMOUTH
Zoning Board of Appeals
Carl E. Lawson, Jr., Hazardous Materials Inspector C L
SUBJECT: Zoning Board of Appeals Petition Number 5197
New Verizon Wireless Facility
20 Old Hyannis Rd., Yarmouth Port
and
Request to store toxic or hazardous materials in amounts greater
than those commonly associated with normal household use as
referenced in Yarmouth Zoning Bylaw Section 406.5.1.1(3).
DATE: August 6, 2025
ATTACHMENT: Board of Health, Handing and Storage of Toxic or Hazardous
Materials Registration Form Completed by Verizon Wireless and
Received by the Health Dept. on June 26, 2025
Vedzon is an intemational telecommunications company providing a variety of
communication and information services, including. but not limited to, wireless
communications service.
Verizon has a lease agreement with the Town of Yarmouth, signed in June of 2024, to
Install wireless communications equipment, inducing, but not limited to, antennas,
structural supports, cabling, equipment cabinets, a diesel generator including a double -
walled fuel tank, auxiliary power batteries. and a concrete pad. at the site of a Town
water supply tank site located at 20 Old Hyannis Rd. in Yarmouth Port. The location is
within the Aquifer Protection District (APO) for the Town's public drinking water supply.
Verizon proposes ins ding auxiliary power sources to maintain area wireless
communication service in the event of an electric uldtiy power failure. The Initial auxiliary
power source that will activate is a battery array, which will power wireless
communications in the short term. In the event of a longw4erm power failure, the
second auxiliary power source, a diesel generator, will provide po �r.
A TRUE COPY ATTEqT:
w t Ae4
L`MhS / CMC DEC N CLERK OP5
Bk 37364 Pg165 #52121
Both auxiliary power sources contain toxic or hazardous materials. The battery array
contains a liquid electrolyte solution. The diesel generator has a fuel tank containing
diesel fuel and an engine containing oil and antifreeze with a starter battery containing
liquid electrolyte.
Since October of 2024, the Building Commissioner and I have acquired knowledge of
the details of the Verizon proposal through extensive communication with the
representatives of the following agencies.
1) Ve6zon legal counsel, Robinson + Cole, Boston MA
2) Structure Consulting Group, Canton MA
3) Energy Systems, Marlborough, MA (the generator dealer)
4) United Alloy, Janesville, WI (the generator fuel tank manufacturer)
Reaulatory Items
Permit Issued by the Building Dept.
A permit has been issued by the Building Dept. for the following work as described
within the Brief Descriptlon of Proposed Work field on the building permit
application: "Install Verizon Wireless equipment and antennas at existing water tank /
wireless communication facility as per attached plans Generator shown on plans not
part of this permit.'
Zgnina
Verizon has applied for zoning relief with the Zoning Board of Appeals (ZBA) for toxic
and hazardous materials storage of more than normal household quantities, within the
APO as outlined in Yarmouth Zoning Bylaw Section 406.5.1.1 (3).
Board of Health:
The Board of Health Regulation `Handling and Storage of Toxic or Hazardous
Materials," effective May 2, 1990, applies to the proposal from Verizon, as the planned
quantity of materials is greater than the licensing threshold of 10 gallons.
Board of Health Realstration
Verizon Wireless registered with the Board of Health when their Board of Health,
Handling and Storage of Toxic or Hazardous Materials Registration Form was received
In print form by the Health Dept. on June 26, 2026. The registration form is complete
and attached for your referenoe.
Other information
The site will not be continuously occupied although it will receive regular visits from
technical service personnel and a diesel fuel delivery service. The most frequent site
visit interval is monthly visual inspections by a service technician.
2
Bk 37364 Pg166 #52121
Toxic and Hazardous Materials Dslive
Toxic and hazardous materials consisting of diesel fuel for the generator, engine fluids
for the generator and batteries will be delivered to the site during or following
construction of the wireless communications facility.
Following construction and activation of the facility, diesel fuel will be delivered an
estimated once per year, but potentially more often if the generator is operated beyond
regular weekly exercise to provide power during outages.
Replacement generator engine oil, antifreeze, starter batteries, and auxfliary power
batteries will be brought onske by service technicians as they are needed to replace
spent fluids or components.
Tong Hazardous Materials Storage
Toxic and Hazardous Materials present onsite will only be those in use and within the
generator, diesel fuel tank and battery cabinet. There will be no toxic or hazardous
materials present onsite within any other storage containers except for those brought
onsite by service technicians and remaining onsite only during servicing of the onsite
stationary equipment.
The generator will be mounted (botted) on top of a double -walled, steel fuel tank with a
300-gallon capacity that will hold diesei fuel. The steel fuel tank will be mounted on a
10-inch-thick concrete pad. Secondary containment of the diesel fuel is provided by the
double walls of the tank.
The generator will contain 14.4 quarts of engine oil, 4.6 gallons of engine antifreeze and
use a starter battery that contains approximately 0.5 gallons of liquid electrolyte in the
form of sulfuric acid. The generator will also contain some small amount of diesel fuel.
Secondary containment of these fluids will be provided by the design of the fuel tank on
which the generator is mounted. The top of the fuel tank has a continuous, raised, steel
edge which forms a containment area for the fluids within the generator mounted above.
The fluids listed above collectively total 34.4 quarts or approximately 8.6 gallons. The
secondary containment area on the top of the fuel tank has a capacity of approximately
29 gallons, which far exceeds the BOH Regulation secondary containment volume
requirement of 150%.
The auxiliary power batteries that will power the wireless communications equipment
(as opposed to the generator stater battery mentioned previously) will collectively
contain 17.80 gallons of liquid electrolyte in the form of potassium hydroxide. The
battery cabinet in which the auxiliary power batteries will be placed provides 26.7
gallons of secondary containment.
26.7 gallons of secondary containment / 17.80 gallons of electroly.% TI#tE COPY ATTEST:
F'; ix,, of
CMI<4 s I GtI tTQVMRK
Bk 37364 Pg167 #52121
1.5 X 100 = 150% volume secondary containment which in is compliance with BOH
Regulation.
The proposed generator model does not have a gear box.
Diesel Exhaust Fluid (DEF) will not be used.
The total liquid volume of toxic or hazardous materials proposed to be onshe is
calculated as follows:
Diesel fuel 300 gallons
Generator engine oil 3.6 gallons (14.4 quarts)
Generator Engine antifreeze 4.6 gallons
Generator starter battery electrolyte 0.5 gallons
Auxiliary battery electrolyte 17.8 gallons
Total 326.4 gallons
T is anj Hazardous Matedgk Use
The use of materials is only for the operation of the generator and auxiliary battery
array.
Toxic and Haurdigge Materials DIsDosgi
All toxic or hazardous waste material resulting from onsite equipment repair and
maintenance will be immediately removed by the service technician(s) upon the
completion of work and not left unattended. These materials will be properly disposed of
in accordance with applicable regulations.
Generator engine oil in the amount of 14.4 quarts will be changed with the waste oil
removed and new oil added. The predicted frequency of this service is every 250 hours
of generator run time or annually, whichever comes first.
Generator engine oil filters will be replaced with each engine oil change.
Generator engine antifreeze in the amount of 4.5 gallons will be replaced every two
years.
Engine fuel filters will be replaced annually.
The generator starter battery will be replaced once every three years.
The auxiliary power batteries are expected to be replaced about every ten years.
Other Oeerativns Involvl g Toxic or N rdo+r&_llila „ rlals
Fuel polishing is a method by which water, sediment and microbial contamination is
removed from fuel. The need for fuel polishing is determined by fuel sample testing.
4
Bk 37364 Pg168 #52121
Fuel polishing is accomplished with the use of specialized equipment. The process
involves pumping the diesel fuel from the lowest point of the tank, where contaminants
tend to rest, circulating the diesel though a series of filters and separators that remove
contaminants, and returning the diesel to the fuel surface inside the tank. The removal
of untreated fuel from the tank, and the return of treated fuel to the tank, occur
simultaneously so the entire volume of diesel in the tank is not completely removed at
once and reinserted. Instead, only a fraction of the diesel fuel is removed from the tank
at any one time. Fuel polishing is used to maintain fuel quality for applications in which
the fuel Is seldom used and replenished, as If often the case with auxiliary generators.
Verizon plans to have the diesel fuel for the generator polished when fuel testing
indicates such is needed.
Environmental Safeway
1) All toxic or hazardous materials proposed to be onsite will have secondary
containment, as described previously.
2) The accidental release of diesel fuel from the generator fuel tank inner wall to the
space between the inner and outer walls, known as the interstitial space, will
activate an immediate notification to the Verizon Wireless network alarm center
for emergency response, which is continuously available. The released fuel will
be recovered from the interstitial tank space by attaching reclamation equipment
to a port, built into the outer wall of the tank.
3) The accidental release of generator engine oil, generator engine antifreeze
and/or generator starter battery electrolyte from the generator to the containment
area immediately beneath the generator and on top of the fuel tank will also
activate an Immediate notification to the Verizon Wireless network alarm center
for emergency response, which is continuously available. These released
substances will be recovered by attaching reclamation equipment to a separate
port from the one referenced above, that is built into the upper portion of the tank.
4) The monitoring systems that are mentioned above will transmit hazardous
material release notifications to the Verizon Wireless network alarm center by a
fiber optic communication line to be installed onsite.
5) According to the generator and tank dealer, the fuel fill has a "cam and groove
system that requires the refueler to have a positive attachment from the lilt hose
to fuel fill --this is not a standard fuel station pump handle that is easily overfilled."
6) The fuel fill port on the fuel tank has an overfill valve that stops fuel flow when the
tank reaches 95% of its capacity.
7) The fuel fill port on the fuel tank is surrounded by a fuel fill containment bucket,
that will catch an overfill of fuel in the event of a failure of the overfill valve
mentioned above. The fuel fill containment bucket allows any captured fuel to
drain back into the tank.
A TRUE COPY ATTEST
lei
S
CMA,1C / OMC 1 TOWN CLERK
DEC - 12025
Bk 37364 Pg169 #52121
8) Diesel fuel delivery, generator maintenance and repair, and diesel fuel polishing
will all occur under the continuous supervision of the trained personnel providing
the services.
9) Toxic or hazardous waste generated by or removed from equipment will be
removed from the site immediately after servicing and will not be left unattended.
10) Service personnel will carry personal protective equipment (PPE) and spill
response materials for use if needed.
11) An Emergency Spill Response Plan has been developed and will be provided to
all service technicians. The plan includes notification numbers for local and State
authorities and the licensed hazardous waste hauler chosen by Verizon.
12) Bollards, vertical structures designed to protect infrastructure from vehicle
strikes, will be placed to protect the generator fuel tank.
Health Dent. Reaulrements
Yarmouth Health Regulation requires the following regarding toxic or hazardous
materials handling and storage, which applies to the proposal by Verizon.
1) The business must register annually for a Yarmouth Board of Health Handling
and Storage of Toxic or Hazardous Materials License.
2) No materials may be discharged to the environment.
3) No outdoor storage of materials is allowed.
All toxic and hazardous materials will be within the fuel tank, generator or
auxiliary battery cabinet, all of which are designed for outdoor use.
4) All materials must be protected from vandalism.
All telecommunications equipment containing toxic or hazardous will be
surrounded by a 6-foot-tall, locked, stockade fence. Additionally, traffic bollards
will protect the generator from intentional vandalism in the form of vehicle strikes.
5) All materials must be stored inside secondary containment of 150% volume of
the total amount of materials stored.
6) Containers of materials must be stored in such a manner to facilitate visual
inspection of each container.
The Verizon plan with Sheet Title: Construction Details and Sheet Number A-4,
shows spatial arrangement of (1) the generator with the fuel tank (2) the battery
cabinet, and other equipment indicating clear sight lines should be available to
view the exterior of the generator, generator fuel tank, and battery cabinet.
M,
Bk 37364 Pg170 #52121
7) Any waste material must be properly disposed of by a licensed hazardous waste
hauler.
8) Absorbent material must be kept onsite for use in the event of spills.
Spill response kits containing absorbent materials will not be stoned onsite
because the facility is not staffed. However, spill response kits containing
absorbent materials will be brought onsite in the vehicles of service technicians
and the fuel delivery service.
9) Safety Data Sheets (SDS) for each toxic or hazardous material must be
maintained onsite and be readily available.
Safety Data Sheets (SDS) for each toxic or hazardous material wiN not be stored onsite
because the facility is not staffed and will not have an office or any building in which to
store SDS. SDS will, however, be available to service and fuel delivery personnel when
they are working onsite.
BOH Hearing and Recommendations
Mr. Timothy Twardowski, Attorney for Verizon Wireless, presented the proposal to the
BOH at the regular board meeting on July 7, 2025. After discussion, the BOH approved
recommending the proposal of Verizon Wireless to the ZBA by a unanimous vote with
four members present and voting. This recommendation is based on the ability of the
business to comply with the Town of Yarmouth Board of Health Regulation: "Handling
and Storage of Toxic or Hazardous Materials" and based on the following six (6)
conditions listed below. These conditions are in addition to the strict scope of the
regulation and are intended to provide additional protection for the APD.
9 ) The maximum allowed total combined storage volume of toxic and hazardous
materials is 400 gallons.
2) The Emergency Spill Response Plan submitted by Verizon Wireless to the Board
of Health must be immediately available, in either electronic or print form, to all
service and fuel delivery personnel while they are onsite and they must be
familiar with the plan.
3) Safety Data Sheets (SDS) for applicable materials must be immediately
available, in either print or electronic form, to all service and fuel delivery
personnel while they are onsite.
4) Spill response materials must be immediately available to all service and fuel
delivery personnel while they are onsite.
5) Toxic or hazardous waste generated or removed from equipment must be
removed from the site for proper disposal immediately after servicing and never
left unattended.
A TRUE COPY ATTEST
7
C%.IW I CMG / TOWN CLERK
DEC - 9 20
Bk 37364 Pg171 #52121
6) Bollards, vertical structures designed to protect infrastructure from vehicle
strikes, must be installed and maintained in such a manner to protect the
generator fuel tank.
The Board of Health and Health Department respectfully request that if this proposal is
approved by the ZBA, the preceding six (6) conditions please be included in any ZBA
Decision. Furthermore, if the proposal is allowed by the ZBA, these Items will be
included as conditions of the annual Board of Health license.
Bk 37364 Pg172 #52121
TOWN OF YARMOUTH
1146 RoUrf. ZC 90Ur" YARMOUTH. MASSACHUSETTS 03""SI
Tekphw(S06)39 .zLltl ext. Its Fox (SM WO-347
sum
BOARD OF HEALTH
HANDLING AND STORAGE OF TOXIC OR HAZARDOUS MATERU LS 'UN' 2 B 2025
REGISTRATION FORM HEALTH DEPT.
I Written description of business to Include.
a) Business ownees name, address, phone number
Cellco perm mNp WWI Venison Wireless with legal address and principal place
of business at One Verhwn Way, Mail Stop 4AW100, BasMV Ridge• Now Jersey
07=0 f 244mur "Mom 000. M0039 or NO-2644M
b) Name of business - cenco Partnership dlbla/ Verizon tlYh+eless
c) Business operation (indudkV statement on vehicle repair. vehicle washing, vahide
fuelling, stud storage of any other bulk materials w HOw or not they are toxic or
hazardous such as omVost or ferliltzer) - Maim w tenna kwta9ation on the
existing murgeipai water tank. Induding sesodated cabling and ground
equipment cabinets with battery backup.
d) Hours of operation • 24IT.
s) Number of employees - No empk "n on site, sa-opewting. The location Is
visaed by servk:e technicians approximately once a month In a regular pickup
truck.
7) List of all toxic and hazardous materials proposed to be used or stored in the business.
Include material guar ties, aonlawi M sizes and tank sides if apple. These materials
Include any material 6ha1 may be considered harmful to public health and the environment
such as gasoline. oils. motor vehicle Bids, paints, adhesives, chemicals and other products.
Two battery strings each containing 8.90 gaMum of IlquM potassium hydroxalde
electrolyte for s total of 17.#0 gallons of battery acid. Housings are sbngle walled, and
Ow battery cabinet provkles 24.7 genons of secoadwy conU*w enL
Diesel fuel: 3Q0-gallon capacity - Integral. double- NWW steel tank
DEF: MIA
Engine ON:14A quarts
Rovised 1-16 2013
A TRUE COPY A7Tl;ST
de
CMM J CIWC 1 TOWN CLERK
DEC - 9 2625
Bk 37364 Pg173 #52121
Gearbox Oil: NIA - oeaW bearing
Erghw ArrtNneae: 43 gallons
Generator Starer Battery: Approximately 27.7 On of lead and approxknatefy 8.14
On f0-S gallon) of" uric add.
Complete secondary eonialnomm fbr 1"I Is provided at 120% of the kwl tank's
eWft. Secondary eonafrunent for the anWreere, engine od, and small fuel
spi0s faom the engine is provided by a tiop•of fuel.lank contaimment pan that is
designed to capture any fhdd messed from the gerwator above and has an
appraxlaatsty �-gsllor� cmtd�nnnent capacity. The topofhrel�k eonlNmnent
Pan onrusJ AS of the top steal surface of tiN fuel tank and the tour anal sides of the
fusel tank. mf" extatd 2.5 Inches above the top. The containment area messur"
2.Jt" high x 76.91" Jong x 35AT" wide.
3) H flammables storage terft am proposed plans are required. Pease see the separate
document: Board of Heath Plan Requirements for Underground Stamps Tanks.
See subnmed fuel to* spec sheets. The fuel tank Is a belly-rnomt tank to be
mounted below the generator and wtfhln dw generator footprint. The fuel tank will
sit below and be boNod to the generator.
4) Material Safety Data Sheets (MSDS) for each proposed product dw dd be av WWe for
review. but not sulxnitted to the Board of Heath unless requested.
Subodded
5) Butding floor Plan
No building or GW%r onsite - only waatlterpnaaf equipmeM battwy cabinet
located on the concrete pad. Generac doudivest generator is located out
fire concrete slab. Fuel tank is within the generator's footprint.
8) kr kmft rooms clearly labeled.
b) Toxic and hazardous materials storage Gres 050% volume capacity required). Wcate
the height, kro and width.
c) Mark floor drain locations
6) Floor Drain Detail NIA
a) location(*)
b) N wrdW
c) Structure drains are emnected to (Iewhkq. hum lank)
d) Pump records (if holding tarNt)
e) Mong WW hVAevel alarm rest dales and results (for holding tank)
1I _ 9 permg it lbor drains have been cioved
Town or wet water s
7) Wd W(CONTINUED
9 %%t@#eries property. NfA
8) krdicste WoOmd(s) of soled waaM disposal WA
a) Durnpsar service
Revised 146-2013
Bk 37364 Pg174 #52121
b) R" Semioe
9) Include onorgerM so conlalnment pleWprocedure with names and phone Aurnbers of
appropriate Stale and Town Depatma" Such as. bul not limited to:
s) Muse is Department of EmWonmental Protection (OEP) 386,304-1133
b) Fire Dept. 911 for wnee+gencios 1 Yarmouth Fir* Department 503.398-2213
C) Health Dept. tl0I1.398.2231 X 1?40
d) Hazardous Waste Disposal Company Clean Harbors M.64U260
e) Owner of property If property Is rented or leased Yarmouth (hater Department NO-
n17921
toy Hazardous waste Removal
a) Licensed Hazardous Waste
Clean Harbors
42 Longwater drive
Norwell, MA 02081
761-792.5000
How - company name an d address
b) Frequency of removals (number of time$ per month or year that waste is (*moved)
The generator WM be exercised once pw week for 35 m Inutes. Therefore, over the
course, of a year k wM run for 30 hours provided there are na electrfoat power
outages.
piesei: Used onolM and replaced as required. Fuel polishing and fuel
runt of generator fuel will be determined via lust testing. In either case,
proper technician PPE (safety glasses, gloves, absorbent rmata) and spNI
00ntainment kits wlp be on hand and knplenOnted. All meteriats required to
perform the work will be removed trap the site and disposed of in an EHS
approved mathor. AN technicloes required for (fie c*rnpletion of the work will
remain one to for the duration, of the process until final cleanup and Imspeclloms
are completed. Because the eke Is located within the AquVw Protection Oftd*Y
District, roe( Ing. fuel poIWW4I. andlor fuel repiae"mo activltlr will be dome in
accor mw with final work processes to be reviewed with the Yarmouth Water
Depsrtme t to "we that the activities sheet apgiCable rexphiremeMs. In the
event et a spill, the WON tochleldan(s) will &OW the local regulatory agency's
n—ficatlon procedure and notWy the office of such an instant whlb ensue and
,on In onsks until released unim a safely issue arises then dw WAnk*m will
shove to a skure area.
Fuel fitters: Annually whh each fuel check. Metal cannlster fll OL
Gearbox of: WA
Engine ale: Annually or 250 hours of no time, Whichever occurs first.
ErWm a* fitters: Annually or 250 hours of run time whichever occurs first.
Engine antifreeze: every two years.
Starter battery: every three years.
Revised 1-16-2013
A TRUE Copy ATTEST:
CMl'r I CMC I TOWN CLERK
DEC - 9 825
Bk 37364 Pg175 #52121
See below table for Owmator items:
11atr�aeaaa psnr - - -
Of end 01 FOW
r�ewbo��f�prsWrwedl _.
ICWIPM Ouft
� f'JsxfB� Ffaep
� Aaoe:soryQd►w bolts
pielwp(it naurNid on
�d Ipwsi+0
ergs ha�aon. sn R�i1 d
me Sm fs he do dp and Okay aperadm or � to bat *No months of
d SM"Mhours(mygowdrere h r.KsnoAsr,**
PrW= is wed ISMUSI A Me SONV b e0 dWV MW Cm be erdwWod to 500 Own
a every *0 years, bread on do emb of fhs wwWs
f sO emY ego fem a ddo trams of oo.r-an n p�qc oa�6ex of wvN
Ron" a evwy t00 burs of opwaft
C"l+seu coolsro smrsey for proper OWAW prerruon Irw4. Oraia. &M& gad real Igo Cleoairp
sYr wb fied►eooasrN every tyro yews rsON's er ool marshowl
Cbwge eodanto: kd cf &wo
* s%A* es *" tow" to mixer), off, ara: a'r
and W04 homes Mess, ftX%b 00%, :to. Z owa Mo 0" m pra" of O"fs rp hogs
f saeswrt►drbe behs every Wm yore wpNdess of operatrrl0 hoes. H neo,," I
Chet~ and #a*= NaWN& tarwionw (tuad). J
AMlOMe. Bean. MPect. aWMW 01 W $90 pdwps b #* cared eperal W sutprrl robepe
dew* sYslern f�rawuo rpr Y rn -0 (oult O for dmmwm" sad dgldeess
C) Quantifies generetedlremoved -
Oack-up Power Bowles- Two strings - r+eplaced every 10+ yean, or as needed
6ngbw all:14.4 quarts
Engine antifreeze: 4.5 gallons
Starwr batterfl: One battery. Group 31-automotive We
Fuel lister: One Mter
On filter one filter
The sasvlce technician w01 remove ail toxic and hazardous waste Immediately
after servkhV the generator. No toxic and hazardous waste will be left omoke
overnight, nor unatwnded.
f I indicate whether or not the site is vwuwn llte Aquifer Protection District (APD). Maps are
avallable in the Health Dept. g within the APO a Building 000. Zoning Determination will be
required and possible Board of Health and Board of Appeals HearvW. Yes, the sue is
within APO.
12)StWa whether or not arty of the f0ilowing operations are proposed:
a) Vehicle washhV -NIA.
b) Velf+iale hm*q - A Vwlzon-approved roof eoagmV w01 laver diesel to the
generator approximately once per year In the absence of electrical power outages.
k is anticipated that approximately 120 gallons of diesel wtll be included In each
debvery. In the went of an sieetrkal power outage, the deNveNes may become
mow frgque d. depending on the durstion of the outage.
c) Vehicle repair -NIA
Revised 1-16-2013
Bk 37364 Pg176 #52121
d) storage of mad sand or road salt -NIA
e) Storage of compost -NIA
1) Please contact the Health Department at NS-398 2231 x1240 if there are any questions or
# assistance Is needed to complete Iles information request.
2) The keowhV meetings or hearings may apply to You proposal:
a)
She Plan Review
b)
Board of Health
c)
Board of Appeals
d)
Board of Selectmen
3) N a Board d Selectrim or Board of Appeals Dearing applies to your proposal the Health
Dept. Handling and Storage of Toxic or Hazardous MaterWs t ioense is to be paid for once
all applicable boards grant their approvals. The licensing threshold is ten gallons for liquids
and fire powde for solids. The license fee Is $1 SO- per fiscal year: Orly 1— June 30.
4) the applicant must also contact the Building and Fire Depts, for their requirements.
6) There shall be no occupancy of the property until all dept. approvals are complete.
Revised 1-16.2013
A TRUE COPY ATTEST:
7- - .
1I
Mr O / CMC 1 TOWN CLERK
S.-
JOHN F. MADE, REGISTER
BARNSTABLE COUNTY REGISTRY OF DEED: