Loading...
HomeMy WebLinkAbout792-792-152 (1)58 Norfolk Ave, Easton, MA 02375 • Tel 508 822 6934 • www.swcole.com Report of Concrete Compressive Strength ASTM C31, ASTM C39, ASTM C1231 Project Name:Yarmouth MA - Town of Yarmouth Water Resource Recovery Facility - Concrete Testing Services Client:Wright-Pierce Project #:25-0468 Report Date:6/26/2026 Concrete Supplier:Cape Cod Ready Mix PLACEMENT INFORMATION Date Cast: 6/12/2026 Time Cast: 7:05 AM Date Received: 6/13/2026 Placement Location:SBR Slabs 56 and 64 Placement Method:PUMP Cylinders Made By:Alexander Charnitsky Material Type:Concrete Cylinders Placement Vol. (yd ):178 Aggregate Size (in):1 1/2 Cylinder Size:6 x 12 INITIAL CURING CONDITION DELIVERY INFORMATION Temperatures Minimum (°F):Maximum (°F): Admixtures:SIKA 25 TEST RESULTS Slump (in) (C-143):6 Air Content (%) (C-231):3.5 Air Temp (°F):65 Conc. Temp (°F) (C-1064):73 Load Number:1 Mixer Num.:52 Ticket Num.:36045 Cubic Yards:11 Design (psi):4500 Batch 6:36 AM Arrive 6:50 AM Depart 7:10 AM Cylinder Designation Defect (Y/N) Cylinder Weight (lbs) Cylinder Diameter (in) Cross Sectional Area (in ) Date Of Test Cure Type Cap Type Age (Days) Fracture Type Load (kips) Strength (psi) 792-152A N 29.15 6.02 28.46 6/19/2026 Lab Unbonded 7 3 111.92 3930 792-152B N 29.15 6.01 28.37 6/26/2026 Lab Unbonded 14 3 130.04 4580 792-152C 29.15 7/10/2026 Lab 28 792-152D 29.15 7/10/2026 Lab 28 792-152E 29.30 HOLD Lab 3 2 Remarks:Kaylie OSullivan Reviewed By