The S.W.COLE field representative is on-site at the request of our client to provide construction materials testing and to observe and document construction activities. The Contractor has soleresponsibility for schedule, site safety, methods, completeness and quality control.
58 Norfolk Ave, Easton, MA 02375 • Tel 508 822 6934 • www.swcole.com
Project Name:Town of Yarmouth Water Resource Recovery Facility Project NO.:25-0468Location:Yarmouth MA Date:6/26/2026
Client:Wright-Pierce Client Rep:Rayssa FonteWeather:Rain 65 - 68°F S.W.COLE Rep:Alexander
Charnitsky
General Contractor:Nickerson Time Onsite:05:30 - 12:00Placement Type: Footing Wall Slab Other
Placement Location:SBR Slab 22 & SBR Gallery Slab 35
Concrete Placement Observations Observed Comments
Required mix used Yes 4500psi, 1 1/2", 3/4, Sika 75
Concrete properly conveyed to all areas of placement Yes Pump Truck
Internal vibration / consolidation of concrete Yes Handheld vibrator
Even layering around openings and embedments Yes Concrete evenly layered and vibrated around
openings and embedments
Post placement observations (finishing, curing, etc.)Yes Concrete Manually Finished
Field Testing of Concrete performed:Yes
*CYLINDER SET NO:789-163 to 789-165 *Refer to associated concrete test report
Notes:
As requested by Rayssa (CDM Smith), an S.W.COLE rep was onsite to perform concrete
sampling, and concrete testing at the locations referenced above.
The S.W.COLE Construction Services representative arrived onsite at approximately 5:30 AM.
Concrete placement was observed during the time of sampling and testing.
Concrete Delivery of Load 1 arrived onsite with approximately 11 cubic yards of 4,500‑psi
concrete with 1‑1/2‑inch aggregate. Sika 75 admixture was added prior to placement. The
concrete was placed via pump truck.
Two sets of field tests total were performed on sampled concrete with the following results:
Truck 59 – Load 1
Slump: 6 inches
Air Content: 4.5 percent
Concrete Temperature: 77°F
Truck 75 – Load 10
Slump: 7.5 inches
Air Content: 3.8 percent
Concrete Temperature: 73°F
Two sets of compression test cylinders were cast for laboratory testing at 6, 14, and 28 days
(2), along with one hold cylinder.
Following completion of the initial placement, the pump truck relocated and utilized a
4,500‑psi concrete mix with 3/4‑inch aggregate. Sika 75 admixture had been added prior to
arrival.
Concrete Construction Observation Report
The S.W.COLE field representative is on-site at the request of our client to provide construction materials testing and to observe and document construction activities. The Contractor has soleresponsibility for schedule, site safety, methods, completeness and quality control.
58 Norfolk Ave, Easton, MA 02375 • Tel 508 822 6934 • www.swcole.com
Truck 65 – Load 1
Slump: 8 inches
Air Content: 3.5 percent
Concrete Temperature: 79°F
One set of compression test cylinders were cast for laboratory testing at 6, 14, and 28 days
(3), along with one hold cylinder.
Laboratory compressive strength test results will be reported separately upon completion of
testing.
Test results and observations were verbally reported to the onsite client representative while
onsite.
The S.W.COLE rep departed the site at approximately 12:00 PM after completing the requested
services.
Attachments: 4 Photos Reviewed by:6/30/2026 Kaylie O'Su iv Kaylie O'Sullivan
Concrete Construction Observation Report
The S.W.COLE field representative is on-site at the request of our client to provide construction materials testing and to observe and document construction activities. The Contractor has soleresponsibility for schedule, site safety, methods, completeness and quality control.
58 Norfolk Ave, Easton, MA 02375 • Tel 508 822 6934 • www.swcole.com
Concrete Construction Observation Report
The S.W.COLE field representative is on-site at the request of our client to provide construction materials testing and to observe and document construction activities. The Contractor has soleresponsibility for schedule, site safety, methods, completeness and quality control.
58 Norfolk Ave, Easton, MA 02375 • Tel 508 822 6934 • www.swcole.com