HomeMy WebLinkAboutsprinkler and backflow test 2015.-€rlcElFIFIE SPFIINKLEEI
Date: 6/10/20'15
Horace & Jeanne Sylvester
810 Main Street
Hingham , MA 02403
Fire Sprinklers & Backflow Protection
Service - lnspection - lnstallation - Testing - Maintenance
352 Main Street. West Yarmouth, Ma. 02673
Tel: 50&775-2082 - Fax: 508-77+2860 - info@cancofiresprinkler.com - \./y r/.cancolirespnnkler.com
Fire Department's Copy
eiErEoFIPE =IPFIN<LEEI
C2
Y
Re: 2015 Fire Sprinkler lnspection & Test
Canco Sprinkler Services recenlly completed the lnspection and Testing of your fire sprinkler system(s) on 6/10/2015 at the
Sylvester Residence, 13 8ay Rd. West Yarmouth, MA.. Please find the atlached lnspection and Test Report.
Your sprinkler system does contain antifreeze Cfest resulls vrould be shown on the test worksheet)
The information about the system's backflow preventer valve is also shown on the test worksheet.
lf your lire sprinkler system is tied into a fire alarm system, the llre alarm mmpany that you use is
ADT
180G2384653
Your next annual inspection has been tentatively scheduled. We will be contacting you regarding the inspection approximately 30 days
prior to the inspection and set up a date and time.
Respectf ully submitted,
Eric F. Hubler
EFH/slp
Our lnspector Decastro has dascovered no issues that need(s) attention.
<
(
serving Cape Cod since 1930
a-ae,
FIEIE SPFIINXLEF!
Property lnformation & Inspection for: Sylvester Residence
6t10t20't5 Sinole Riser: Anti-Freeze Svstem A ntiFrz
Testing Date
Propertv:
Street: 13 Bav Rd.
City: Wesl Yarmouth
System Type
Sylvester Residence
Riser Type Contact Type
State:UA. zp ozatz
Owner / Designated Representative lnterview
lnterview Questions
Does Canco have an updated copy of the 'lnspection
Aoreement" in the file?
Y/N
Yes
All 'NO" answers require an exolaination
ls the entire building occupied at this time?Yes
ls the occupancy and the hazard of contents unchanged?
Are all fire protection syslems in service, including fire
Yes
Yes
Reference
Canco
Fie
NFPA.25:
. A43.1
NFPA-25:
A.4.3.1
NFPA.25:
A.4.3.'1
NFPA-25:
A.4.3.1
NFPA.25:
A..t.J. I
NFPA-25:
4.1.5
NFPA.25:
4.8.5.2
alarms. and other suooression svstems?
Has the sprinkler system remained in service without changes? Yes
Was the sprinkler system free of activation of devices or alarms? Yes
The building has been unchanged with regards to construction
since the last insoection.
Yes
ls the building free of any hazardous materials?Yes
Are you aware that the fire alarms will sound during our
testino todav ?
Yes
Property / Building lnspection
Special hazards noticed in the building
NA
Canco
Fire
Occupancy of the building is
R-3: 1&2 Familv housino
Fire department connection is located Post indicator valve is located
ln front of the Urildino
The sprinkler room is located
ln th
The fire alarm control panel is loc€ted
Electric Bell:No
ln fronl of the buil.ii
Closest hydrant is located
Aarosq lhe qtrppi
The outsids alarm equipment consists of lnspecto/s test outlet is located
Water l\,lotor Gonq: No h-thebasement
Horn / Stobe Lioht No
Propenv / Burldinq Questions
Has the owner provided ready access to all parts of the sprinkler
svstelo?
Has the owner provided lighting and ready access to the
All "NO" answers require an explaination Reference
NFPA.25:
4.1 .2
sprinkler svstem
Are all areas of the building with water filled piping at a
temgerature of 40 deqrees F or hiaher.
Yes
NFPA-25:
4.1.2
NFPA.25.
4.1 .1.1
Test Annual
Main entrance is located:
NA
Kevoad bv front door I
Y/N
Yes
lnspector's test outlet is approximately:
5- feet above grade.
Yes
Property !nformation & !nspection for: Sylvester Residence
Sprinkler System lnspection: Sprinklers
Y/N All 'NO" answers require an explaination
The sprinkler heads show no sign of leakage. Yes
Reference
NFPA.25
5.2.1 11
The sprinklers are ftee of corrosion, paint, damage & loading
Loadino is when heads are coated with dust. orease etc.
Yes
The sprinklers are installed in the correct orientation. Meaning
tie uqrioht heads are urrrioht and Dend?nts head-s faqe dewn.
Glass bulb sprinkler heads have liquid in them.
Yes
Yes
NFPA.25
5.2.1.1.1
NFPA.25
5.2.1.1.1
NFPA-25
Stock, fumishings and equipment are not too close to sprinklers
llaleisorinklerlheads need clearance of 18" to ooerate orooerlv.
The spare head box contains proper number and type of heads.
Yes
Yes
The spare head box contains proper type of sprinkler wrench. Yes
Sprinkler System lnspection: Pipe, Fittings, Hangers and Seismic Bracing
Piping and fittings are free from mechanical damage, leakage &
corrosion.
There is nothing resting against or hanging from the piping.
Piping, fittings & bracing in concealed spaces such as above
susgended ceilinqs shall not require anspection.
Ar€as inaccessible due to safety considerations were not
i0soeeted. A seheduled shut down oeLds tobe seheduled.
Hangers and seismic bracing are not damaged or loose.
Loose hanqers and bracinq shall be tiohtened or refastened.
Dry, preaction & deluge system gauges show normal air and
water pressures.
Raserved
Yes NFPA,25
5.221
N FPA-25
5-22?
NFPA.25
5.223
NFPA-25
5.224
NFPA.25
Yes
Yes
NA
Yes
Sprinkler System lnspection: Gauges
Wet pipe sprankler system gauges are in good mndition and Yes
normal water suoolv oressure is heino maintaine.l
NFPA-25
.124,2-
NFPA-25
5.2.4A.
NFPA-25
5.2.4.4.1
NFPA.25
52442
NFPA.25
NFPA-25
5.2.6
Reserved
Sprinkler System lnspection: Waterflow & Supervisory Devices
Waterflow and supervisory devices are free of physical damagi. yes
This includes watermotor aono. electnc bells. tamDers & low air.
Sprinkler System lnspection: Hydraulic Design lnformation Signs
The hydraulic design information sign(s) on hydraulically NA
desiqned svstems are attached securelv and leaible.
Sprinkler System lnspection: Heat Tape
The heat tape if any was inspected per manufacture/s NA
reouiremgnts.
Sprinkler System Antif reeze
Your sprinkler svstem does contain antifreeze
NFPA-25
5.2.7
5.2.1 .1 .5
NFPA.25:
5.2.1.3 _
NFPA.25:
5.2.1.4
NFPA-25:
5.2.1 .4
NFPA-25
5.241
NA
c€rtcctrIH€ EiPEIINI<I-EEI
Backflow Type
Reduced Pressure
Back Flow Prevention
Make N4odel Serial
Rebuild
Order #
Rebuild
Kit Onsite
Wet System Testing Worksheet for:
Sylvester Residence
Test Date 6/10/15
Size
2"
Your sp nkler system does
Antifreeze Pipe Size
Basement
(WED Alarm Check ValveMake Size Year Model
SHOTGUN 2-112"
Wilkins 975 XL 1369431
containantifreeze Antifreeze SampleS
Expansion Tank Size Antifreeze Loop Volume Expansion Tank psi
7-nH is Ncrrtral
pressure Year
Type | 2015 zuq- ,013]----]Electric Bell
Ojgteles
NA
'!$ sralic f 9s 83 87 l w.M.Gong N"- !!A-
Wet System Trip Test
Performed From
Main Riser Tpst .q nrain
lnspectors Test, Low Point & Auxilary Drains
# Type Location Valve Tvpe H2O
Alarm
Time
Secs.E
Flow Testp.s.i. p.s.i. p.s.i. p.s.i Alarm TestAlarm
7l
Supervisory 3
Supervisory 2
Year Year Year Device
l
L-l
2
Dtreet Side
System Side 2
1 2 7
Riser Tvpe
#i)
E
residuat f6s ' 62 65 l - l FACP Al'drm tres- n'es-
2nd llatic f90 8s 8? l-___l noa strobq tN. hA-
S"ry'laIgilqIlqylQlq@qlq , Y*-
Control Valves
CV # CV Location Size TVpe Tums Secured By Time
ButBall
But-Ball
4