HomeMy WebLinkAboutsprinkler and backflow test 2014CETECI Fire Sprinklers & Backflow Protection Service - lnsnection - lnslallation - Teslino - Maintenancc 352 Main Street, West Yarmouth, Ma. 02673 Tel: 508-775-2082 - Fax: 508-775-2880 - info@cancofiresprinkler com - www.cancofirespnnkler.com cErx>oFIEIE s}EEINKLEEI Date: 512212014 Horace & Jeanne Svlvester 810 Main Street Hingham , MA 02403 System is equipped with a backflow preventer: Make: Wilkins Model: 975XL @coPY Re: 2014 Fire Sprinkler lnspection & Test Enclosed please find the annual fire sprinkler report. The system consists of: ( ) Dry Sprinkler System ( )Wet Sprinkler System ( )Deluge System ( )Combination WeUDry System (X)Antifreeze Protected System Your fire alarm company is ADT (X)Yes ( )No Type: RPZ Size:2" The following items need attention 1. Our technician noted that the main drain piping needs an auxiliary drain installed in order to remove trapped water and to ensure that the drain line does not freeze in the winter. lt is recommended that this auxiliary drain be installed prior to cold weather. A quote is attached for your review. Your next inspection and test is scheduted for May 20'15. We will contact you approximalely 30 days in advance in order to schedule. Respectfully submitted, Paul L. Cuddv PLC/slo serving Cap6 Cod sinco 1930 Canco Fire Sprinkler Services recently completed the annual inspection and test of the residential antifreeze sprinkler system at 13 Bay Rd., West Yarmouth, MA. Antifreeze freeze point: -2"F, PH reading: 7 (PH reading of 7 is normal. Lower is acidic and higher is alkaline.) Property lnformation & lnspection for: Sylvester Residence cEncctFIFIE BPFIINKLEF Aqle_e4rot ir thqfite? ri ttrelntire OuirOingrcccupiea at tG-time? Sinole Riser: Anli-Freeze Svstem AntiFrz Propertv: Street: 13 Citv: West lnterview Questions Does Canco have an updated copy of the "lnspection System Type Svlvaslar Residence Bav Rd. Yarmouth State: MA. Zil: Riser Type 02673 All "NO" answers require an explaination Owner / Desiqnated Representative lnterview Y/N Yes Reference Canco Fir Yes NFPA.25 NFPA-25ls the occupancy and the hazard of contents unchanged?Yes Are all fire protection systems in service, including fire Yes alat[srend olhqt suooression svstems?- Has lhe sprinkier system remained in service without changes? Yes ! A,!L!J NFPA-z5 A.4.3.1 NFPA.25 NFPA25Was the sprinkler system free of activation of devices or alarms? Yes _ A.4.3.1 The building has been unchanged with regards to construction Yes sioce-the last insoection. ls the building free of any hazardous materials? Are you aware that the fire alarms will sound during our testino todav ? Occupancy of the building is: R-3: 1&2 Familv housino Fire department connection is located Yes Property / Building lnspection Special hazards noticed in the building NA Post indicator valve is located NA The outside alarm equipment consists of: Water Motor Gonq; No Horn / Stobe Liqht: trto Electric Bell: ft Main entrance is located ln front of the buildino Closest hydrant is located Across the street lnspector's test outlet is located in the basement lnspector's test outlet is approximately t feet above grade. Yes NFPA.25: 4.1.5 NFPA.25: " 4.8.5.2 i Canco Fire ln fron! of the buildino The sprinkler room is located The fire alarm control panel is located Kevoad bv front door Propertv / Buildinq Questions Has the owner provided ready access to all parts of the sprinkler All "NO' answers require an explainationY/N Yes sYstem?- Reference NfPe-ZS,_at2_ NFPA-25: 4.1 .2 NFPA.25: 4.1.1.1 Has the owner provided lighting and ready access to the sorinkler svstem -- Are all areas of the building with water filled piping at a temDerature of 40 deorees F or hioher. Yes Yes 5t9120',t 4 Testing Date Test Annual Contact Type ln the basement Property lnformation & lnspection for: Sylvester Residence Sprinkler System lnspection: Sprinklers Y/N All "NO'answers require an explaination The sprinkler heads show no sign of leakage. Yes The sprinklers are free of corrosion, paint, damage & loading Loadinq is when heads are coated wrth dust. qrease etc. Reference t'rf Pe-ZS, 5.2.1.'t.1 NFPA.25: NFPA-25; 5.2.1 .1.1 NFPA-25: NFPA-25: NFPA-25: 5.2.1.4 NFPA-25; 5.2.1.4 The sprinklers are installed in the correct orientation. Meaning the uorioht heads are Lroriohl and oendants heads face down Glass bulb sprinkler heads have liquid in them. Yes Yes Stock, furnishings and equipment are not too close to sprinklers Nale:.Sprlnller heads n€cd alcalanec Sl !a sperate properlv The spare head box contains proper number and type of heads. Yes Yes Sprinkler System lnspection: Pipe, Fittings, Hangers and Seismic Bracing Piping and fittings are free from mechanical damage, leakage & Yes corrosion. There is nothing resting against or hanging from the pipang Yes Piping, fittings & bracing in concealed spaces such as above Yes suspended ceilinqs shall not require insgection. Areas inaccessible due to safety considerations were not NA insDected. A schedulcd shut down needs to be scheduled. Hangers and seismic bracing are not damaged or loose. Yes Loose hanqers and bracinq shall be tiqhtened or refastened. Sprinkler System lnspection: Wet pipe sprinkler system gauges are in good condition and yei normal water suoDlv oressure is beino maintained. Gauges NFPA.25 ].2,?1 NFPA.25 5.2.?.2 NFPA.25 5.2.2.3 NFPA-25 3.224 NFPA-25 5.2.3.1 NA Reserved Sprinkler System lnspection: Waterflow & Supervisory Devices Waterflow and supervisory oevicei are free of physical damage. Yes This includes water motoloono. electric bells. tamoers &Iow air. Sprinkler System lnspection: Hydraulic Design lnformation Signs The hydraulic design information sign(s) on hydraulically NA desiqned svstems are attached securelv and leqible. Sprinkler System lnspection: Heat Tape The heat tape if any was inspected pemanrfaCtrrer's NA requirements. Sprinkler System lnspection: lnformation Sign The information iign is securely attached to the system and is NA lesible-ln metal or rcidplastie stalinslhe riser tvpe. NFPA-25: 5.2.4.1 NFPA.25: 5.2.4.2 NFPA-25; 5.2.4.4 NFPA-25: 5.2.4.4.1 NFPA-25: 5.2.4.4.2 NFPA.25 NFPA-25 NFPA-25 5.2.7 NFPA-25 s.2.8 Yes The spare head box contains proper type of sprinkler wrench. Yes Dry, preaction & deluge system gauges show normal air and water pressures. Reserved cErrcc,Wet System Testing Worksheet for: Svlvester Residence Test Date 519114 Back Flow Prevention EENCC' Backflow Type Reduced Pressure Last Tesl 5/5/2012 By Pressure Type 'l st static residual Mak€ Wilkins [/ode 975 XL Siz€ 2" Serial 1369431 YWD Pass Fail Pass Flow Testp.s.i. p.s.i. p.s.i. p.s.i. Year Year Year YBar Do14 ,013 --=l83 87_ I oz os - -r-'_-l - (WET) Alarm Check ValveMak€ Size Year Model Serial # SHOTGUN 2.1h- Riser Tvpe Wet System Trip Test Performed From Mam Riser Test & Drain lnspectors Test, Low Point & Auxilary Drains # Type Location Valve Tvpe H2O Alarm Time -es. 7 oflarm Test Device Equipq Opq!4les Electric Bell No NA W.M.Gong Nq FACP Alarm \GS Horn/ Strobe Nq NA Yes NA2nd static 85 87 Compares to previous tests Vga Control Valves CV # CV Location Size Type Turns Secured By Time I Isrreet sioe I z lieqlaarr pervlsory 32 System Side 2 But-Ball 7 Supery1qqry 2 {$ 7 Antifreeze SamplesTeEB- oh pH.-2 39.5 7+H is Neutral. Test Poinl Basement AntifreezeTvDet@il_