HomeMy WebLinkAboutletter regarding removal of sprinkler system 2023YARMOUTH FIRE AND RESCUE 96 OLD MAIN STREET SOUTH YARMOUTT{, MASSACHUSETTS 02664 Fire Prevention Telephone: (508) 7604859 Ex3216 Fax: (508) 760-4858 John Callahan I Buttercup Lane South Yarmouth, MA 02664 Mr. Callahan, Per our conversation dated 3/30/23, the following requirements must be met for issuance of a permit to remove the sprinkler system at 9El Rt. 28. Based on the change of use for the building and letter from Engineer Philbrook stating that a sprinkler system is not required for the new use, and that replacement or repair of said system. Yarmouth Fire Department will grant a permit for removal, provided the following conditions are met: l. Letter from owners' insurance company stating they are aware the system is being removed.2. Yarmouth Water Department requires that the system is cut and capped at the street. Please provide documentation that this will be done.3. AII Sprinkler piping, heads, connections, and risers are removed.4. A final inspection by YFD inspectors will be done prior to Use & Occupancy being signed off. Thank You, Kevin Huck Captain /Inspector Yarmouth Fire Departrnent 508-39E-2212 ext 3214 March 30, 2023 PHILBROOK ENGINEERING & CONSTRUCTION 1O7 BEACH STREET oENNls. MA 02638 1-508-385-86a2 ENGINEERING DESIGN . CONSTRTJCTION INSPECTIONS . BUILOING' ALTERAT ONS E RENOVATIONS 16 March 2023 To: Yarmouth Building Department Attn: Mr. Mark Grylss, Building Commissioner Town Hall, I 146 Route 28 South Yarmoulh, MA 02664 Reference: 981 Route 28 (Main St.), South Yarmouth Port, MA 0266 Fon Adrotive Conversion of Existing Resteurant to Office (Business) Use Dear Mr. Grylss: I am writing to provide a code review for the requirements tbr this buitding to have its' fire suppression system removed. Presently the system is in default and in extreme disrepair. The past current occupancy is A.2 [all-others] Restaurant. Adaptive plans call for a change of use 1o B Business use through alterations & renovations- As proposed there will be no substantial change to the buildings aspect ratios; floor area or story height. I have reviewed the IEBC 2015 code Work Area Compliance method Gotal building) Chp. 5 Sec. 504 Alterations (Level II) & Chp. l0 Change of Occupancy. Both ofthese chapters have Fire Protection Sections. Fire Protection: Paru.804.2.2 & Para. 1012.2.1 - Essentially both of these paragraphs refer the need for sprinklers to the IBC 2015 Code for nerv construction. Pan.8M.2.2.l states that sprinkler protection shall be IAW IBC 2015 for new construction (requirenrents). Pata- 1012.2.1 states that for change of occupancy sprinkler protection shall be based upon the new occupancy IAW IBC 2015 for new construction. These referrals take usto Chp.9lBC2015 and more specifically to Tbl. 903.2 (MA Amend) Occupancy Automatic Sprinkler Requirements. New Use - B; based upon Tlb. 903.2 a sprilkler system is not required - No Ambulatory use. Totsl area = 3,930 sf < 12,000 sf AND < 7,5fi) sq IAW M.G.L. c. 148,9 26G. There are more construction requirements based on the IEBC 2015 for Change of Use. This information is intended to specifically address the right to remove the fire suppression system. Frs,slRespectfully submitted, T\L-.,R,-..-.- T. VARNUM PHILBROOK, P Existing Use - A2r; based upon Tbl. 90J.2 the current sprinkler system should not be required. Total area = 3,930 sf < 5,000 sf; Occupancy = 78 < 100; All on the level of exit discharge. I I ] VARNUII,PHILBROOl( I!,I E CHA I,TICAL F Fwd: Abandonment permit/change of use acknowledgement Begin forwarded message: From: Jessica McLaughlin <.lessica.McLaughlin@rogersgray.com > Date: April 7 , 2023 at 1 1:57:35 AM EDT To: Shauna Daly < shau na@ peregrinesclu b.com > Subject RE: Abandonment permit/change of use acknowledgement Carrier has confirmed as there is no specific warranty on the policy noting the sprinkler system we are ok to keep the policy as is ( no issue with having the sprinkler system removed and no changes needed at this time). Thanks ! Jessica Jessica McLaughlin Client ManaSer Rogerscray, a Saldwin Risk Partner rel: 50&a09:€q1! Fax: 877-8162155 tmailr &llr4!49trsa[lgelgseEslaydgla web: !gseEEy,!g! R(]GERSIGRAY IIUE From: Shauna Daly <shauna@peregrinesclub.com> Sent: Friday, April 7 ,2023 LO:22 AM To: Jessica McLaughlin <Jessica.McLaughlin@rogersgray.com> Subject: Re: Abandonment permit/change of use acknowledgement Any sense of when we can get some resolution on this? On Apr 6, 2023, at 10:30 AM, Shauna Daly <sha una @p3gggrinesclub.com> wrote: Any word from them yet? On Tue, Apr 4, 2023 at 4:05 PM Jessica McLaughlin <Jessica.McLaughlin@ rogCIsgfAy.ggE> wrote: ff Delete fi Archive Q Report - er Reply <6r Reply all 2 Forward ' I O ?SI RT Z\ Hl Shauna, t (r ,..l A aN ^, Just heard backl Please see below and let me know if you need an6hing else: E-