The S.W.COLE field representative is on-site at the request of our client to provide construction materials testing and to observe and document construction activities. The Contractor has soleresponsibility for schedule, site safety, methods, completeness and quality control.
58 Norfolk Ave, Easton, MA 02375 • Tel 508 822 6934 • www.swcole.com
Project Name:Town of Yarmouth Water Resource Recovery Facility Project NO.:25-0468Location:Yarmouth MA Date:8/6/2026
Client:Wright-Pierce Client Rep:Rayssa FonteWeather:Mostly Cloudy 67 - 73°F S.W.COLE Rep:Alexander
Charnitsky
General Contractor:Nickerson Time Onsite:09:30 - 14:00Placement Type: Footing Wall Slab Other
Placement Location:SBR Exterior Walls on Slabs 22 & 23
Concrete Placement Observations Observed Comments
Required mix used Yes 4,500 Psi, 1 1/2, Sika 75
Concrete properly conveyed to all areas of placement Yes Pump Truck
Internal vibration / consolidation of concrete Yes Handheld vibrator
Even layering around openings and embedments Yes Concrete evenly layered and vibrated around
openings and embedments
Post placement observations (finishing, curing, etc.)Yes Concrete Manually Finished
Field Testing of Concrete performed:Yes
*CYLINDER SET NO:792-185 *Refer to associated concrete test report
Notes:
As requested by Wright-Pierce, S.W. COLE rep was onsite to perform concrete sampling and
concrete testing at the locations referenced above.
S.W. COLE rep Alex Charnitsky arrived onsite at approximately 9:30 AM to perform the
requested services.
S.W. COLE rep observed concrete placement during the sampling and testing activities.
Concrete Delivery Truck 24, Load 1, arrived onsite carrying approximately 11 cubic yards of
4,500-psi concrete containing 1½-inch aggregate. Project personnel added Sika 75 admixture
to the concrete prior to placement. The contractor placed the concrete via pump truck.
Approximately 92 cubic yards of concrete were placed during this visit. One set of field tests
was performed on sampled concrete and yielded the following results:
Truck 24 – Load 1
Slump: 6.5 inches
Air Content: 3.1%
Concrete Temperature: 80°F
Laboratory compressive strength test results will be reported separately upon completion of
testing.
One set of 6×12-inch compression test cylinders was fabricated for laboratory testing at 7, 14,
and 28 days (two cylinders), along with two additional hold cylinders.
Test results and observations were verbally reported to the onsite client representative, Rayssa
Fonte, while onsite.
Concrete Construction Observation Report
The S.W.COLE field representative is on-site at the request of our client to provide construction materials testing and to observe and document construction activities. The Contractor has soleresponsibility for schedule, site safety, methods, completeness and quality control.
58 Norfolk Ave, Easton, MA 02375 • Tel 508 822 6934 • www.swcole.com
S.W. COLE rep departed the site at approximately 2:00 PM after completing the requested
services.