HomeMy WebLinkAboutFIRE ALARM INSPECTION BUILDING REPORT 20262026
Sea Dog Brew Pub
23 White's Path
South Yarmouth, MA 02664
(508)694-6020
Building Contact:Peter Lucido
Title:Contact
Company:Cape Cod Alarm
Contact:Marty Crowell
Title:Installer
Fire Alarm Systems
INSPECTIONCERTIFICATE
Aug 13, 2026Inspection Date:
Tested to NFPA 72 Standards
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed
ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Page of 2 11
Executive Summary
Cape Cod Alarm Download Date: 08/14/2026
EXECUTIVE SUMMARY
Generated by: BuildingReports.com
Building Information
Sea Dog Brew Pub
23 White's Path
South Yarmouth, MA 02664
United States of America
Contact: Peter Lucido
Phone: (508)728-1960
Fax:
Mobile:
Email:
Inspection Performed By
Cape Cod Alarm204 Old Townhouse RoadWest Yarmouth, MA 02673United States of America
Inspector: Marty Crowell
Phone: (508) 398-6316
Fax:
Mobile:
Email: service@capecodalarm.com
System Control Unit
Manufacturer: Fire-Lite Inspection Date: 08/13/2026 IDC Style: E
Model Number: MS-5024UD Install Date: 08/13/2026 SLC Style: N/A
Software Version:Version Date: 08/13/2026 NAC Style: E
Location: Entry Foyer Disconnect Location:Disconnect Type:
Current Protection: Breaker
Monitoring
Company: Cape Cod Alarm Phone:Account #: S24072
Central Station Signal Verification
Type: Mesh Radio Network Mfg: AES Model #: 7788F
Test Time/Date: 8/13/26 10:19:19 AM Restore Time: 10:56 AM Note:
Type of Signal Signal Confirmed Time Notes
Alarm Signal 10:35 AM
Trouble Signal 10:37 AM
Page of 3 11
Executive Summary
Cape Cod Alarm Download Date: 08/14/2026
Building: Sea Dog Brew Pub
Contact: Peter Lucido
Company: Cape Cod Alarm
Inspector: Marty Crowell
Inspection Summary
Category
Total Items Serviced Passed Failed/Other
Qty %Qty %Qty %Qty %
Alarm 1 3.45%1 100.00%1 100.00%0 0.00%
Auxiliary 1 3.45%1 100.00%1 100.00%0 0.00%
Control 5 17.24%5 100.00%5 100.00%0 0.00%
Indicating 10 34.48%10 100.00%10 100.00%0 0.00%
Initiating 8 27.59%8 100.00%8 100.00%0 0.00%
Monitor 2 6.90%2 100.00%2 100.00%0 0.00%
Supervisory 2 6.90%2 100.00%2 100.00%0 0.00%
Totals 29 100%29 100.00%29 100.00%0 0.00%
Certification
Page of 4 11
Inspection & Testing
Cape Cod Alarm Download Date: 08/14/2026
Control Panel: 1 - Fire-Lite MS-5024UDBuilding: Sea Dog Brew Pub
INSPECTION & TESTING
Generated by: BuildingReports.com
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other .
Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.
Device Type Location Service Time Date
PASSED
Alarm
Kitchen Hood Kitchen Tested 9:41:13 AM 08/13/2026
Auxiliary
Sound Shutdown By Back Hall to Basement Tested 10:14:59 AM 08/13/2026
Control
Battery In AES Transmitter Tested 9:39:55 AM 08/13/2026
Battery In Fire Alarm Control Panel Tested 10:20:57 AM 08/13/2026
Battery In Fire Alarm Control Panel Tested 10:50:37 AM 08/13/2026
Communicator Entry Foyer (in ceiling above first tile)Tested 10:19:19 AM 08/13/2026
Control Panel Entry Foyer Tested 9:38:54 AM 08/13/2026
Indicating
Bell Sprinkler Room (outside Back Door)Tested 10:34:02 AM 08/13/2026
Horn/Strobe By Back Entry Tested 9:53:58 AM 08/13/2026
Horn/Strobe By Front Entry Tested 9:45:07 AM 08/13/2026
Horn/Strobe By Side Deck Tested 10:17:41 AM 08/13/2026
Horn/Strobe Kitchen Back Door Tested 10:00:10 AM 08/13/2026
Horn/Strobe Kitchen Restroom Tested 9:59:47 AM 08/13/2026
Horn/Strobe Left Dining Room Tested 9:46:20 AM 08/13/2026
Horn/Strobe Men's Restroom Tested 9:47:20 AM 08/13/2026
Horn/Strobe Women's Restroom Tested 9:48:12 AM 08/13/2026
Page of 5 11
Inspection & Testing
Cape Cod Alarm Download Date: 08/14/2026
Device Type Location Service Time Date
PASSED (continued)
Indicating (continued)
Horn/Strobe Basement by Stairs Tested 9:57:41 AM 08/13/2026
Initiating
Duct Detector Kitchen Tested 9:42:35 AM 08/13/2026
Duct Detector Kitchen Tested 9:42:41 AM 08/13/2026
Pull Station By Back Entry Tested 9:53:19 AM 08/13/2026
Pull Station By Front Entry Tested 9:43:32 AM 08/13/2026
Pull Station By Kitchen Back Door Tested 10:00:33 AM 08/13/2026
Pull Station By Side Deck Tested 10:17:17 AM 08/13/2026
Pull Station Basement by Stairs Tested 9:57:13 AM 08/13/2026
Waterflow Switch Sprinkler Room (outside Back Door)Tested 10:31:05 AM 08/13/2026
Monitor
Monitoring Alarm Signal Tested 10:20:37 AM 08/13/2026
Monitoring Trouble Signal Tested 10:20:46 AM 08/13/2026
Supervisory
Tamper Switch Sprinkler Room (outside Back Door)Tested 10:32:12 AM 08/13/2026
Tamper Switch Sprinkler Room (outside Back Door)Tested 10:33:12 AM 08/13/2026
Page of 6 11
Service Summary
Cape Cod Alarm Download Date: 08/14/2026
SERVICE SUMMARY
Generated by: BuildingReports.com
The Service Summary section provides an overview of the services performed in this report.
Building: Sea Dog Brew Pub
Device Type Service Quantity
PASSED
Battery, Sealed Lead Acid Tested 3
Bell Tested 1
Communicator, Mesh Radio Network Tested 1
Control Panel, Conventional Tested 1
Duct Detector Tested 2
Horn/Strobe Tested 9
Kitchen Hood Tested 1
Monitoring, Alarm Signal Tested 1
Monitoring, Trouble Signal Tested 1
Pull Station, Dual Action Tested 5
Sound Shutdown Tested 1
Tamper Switch Tested 2
Waterflow Switch Tested 1
Total 29
Grand Total 29
Page of 7 11
Auxiliary Functions Testing
Cape Cod Alarm Download Date: 08/14/2026
Control Panel: 1 - Fire-Lite MS-5024UDBuilding: Sea Dog Brew Pub
AUXILIARY FUNCTIONS TESTING
Generated by: BuildingReports.com
The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled
by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is
provided to indicate if the test conducted was simulated.
Type Location Comment ScanID Simulated
PASSED
Sound Shutdown
By Back Hall to Basement Passed A9018867 ☐
Page of 8 11
Sound and Visual Testing
Cape Cod Alarm Download Date: 08/14/2026
SOUND AND VISUAL TESTING
Generated by: BuildingReports.com
The Sound and Visual Testing section lists various points throughout your building where audible and visual alarm notification
devices were tested. Any bar-coded audible and visual devices will appear in the Inspection and Testing section of this report.
Items in this section are grouped by Passed or Failed/Other. Where specific decibel readings were recorded, they will appear
under the ambient and alarm columns. The Voice column indicates whether the Sound Test Point passed the Voice Intelligibility
requirements. The STI or Sound Transmission Index is shown if recorded.
Building: Sea Dog Brew Pub
Audible/Visual Appliances
Location Comment Ambient Alarm Synched ScanID
PASSED
Horn/Strobe
By Front Entry Passed ☐A9018855
Left Dining Room Passed ☐A9018856
Men's Restroom Passed ☐A9018857
Women's Restroom Passed ☐A9018858
By Back Entry Passed ☐A9018860
Basement by Stairs Passed ☐A9018863
Kitchen Back Door Passed ☐A9018865
Kitchen Restroom Passed ☐A9018866
By Side Deck Passed ☐A9018868
Page of 9 11
Battery & Power Supply Testing
Cape Cod Alarm Download Date: 08/14/2026
Control Panel: 1 - Fire-Lite MS-5024UDBuilding: Sea Dog Brew Pub
BATTERY & POWER SUPPLY TESTING
Generated by: BuildingReports.com
The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to
provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Battery
Type Location
Rated
Ah
Rated
Volts
Pre
Test
Post
Test
Min
Ah
Teste
d Ah
MFG
Date
PASSED
Sealed Lead Acid In AES Transmitter 7AH 12V 100 100 05/13
/2026
Sealed Lead Acid In Fire Alarm Control Panel 7AH 12V 100 100 05/13
/2026
Sealed Lead Acid In Fire Alarm Control Panel 7AH 12V 100 100 05/13/2026
Page of 10 11
Inventory & Warranty Report
Cape Cod Alarm Download Date: 08/14/2026
Control Panel: 1 - Fire-Lite MS-5024UDBuilding: Sea Dog Brew Pub
INVENTORY & WARRANTY REPORT
Generated by: BuildingReports.com
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete
inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices
installed for two years or more are grouped together for easy reference.
Building: Sea Dog Brew Pub
Device or Type Category % of Inventory Quantity
Battery Control 10.34%3
Bell Indicating 3.45%1
Communicator Control 3.45%1
Control Panel Control 3.45%1
Duct Detector Initiating 6.90%2
Horn/Strobe Indicating 31.03%9
Kitchen Hood Alarm 3.45%1
Monitoring Monitor 6.90%2
Pull Station Initiating 17.24%5
Sound Shutdown Auxiliary 3.45%1
Tamper Switch Supervisory 6.90%2
Waterflow Switch Initiating 3.45%1
Type Qty Model #Description Install Date
NEW (UNDER 90 DAYS)
Fire-Lite
Control Panel 1 MS-5024UD Conventional 08/13/2026
IN SERVICE - 90 DAYS - 1 YEAR
Ansul
Page of 11 11
Inventory & Warranty Report
Cape Cod Alarm Download Date: 08/14/2026
Type Qty Model #Description Install Date
IN SERVICE - 90 DAYS - 1 YEAR (continued)
Ansul (continued)
Kitchen Hood 1 Ansul 05/13/2026
Fire-Lite
Battery 2 FAS-1075 Sealed Lead Acid 05/13/2026
Pull Station 5 BG-12 Dual Action 05/13/2026
Power Patrol
Battery 1 SEC-1075 Sealed Lead Acid 05/13/2026
System Sensor
Duct Detector 1 Duct 1 05/13/2026
Duct Detector 1 Duct 2 05/13/2026
IN SERVICE - 10 YEARS TO 15 YEARS
AES
Communicator 1 7788F Mesh Radio Network 05/13/2015
System Sensor
Bell 1 Water Gong 05/13/2015
Sound Shutdown 1 R20 05/13/2015
Tamper Switch 2 OSY2 05/13/2015
Waterflow Switch 1 WFD 05/13/2015
Wheelock
Horn/Strobe 9 P2R (replacement)05/13/2015
(manufacturer not specified)
Monitoring 1 Alarm Signal 05/13/2015
Monitoring 1 Trouble Signal 05/13/2015