HomeMy WebLinkAbout2026 FIRE ALARM INSPECTION BUILDING REPORT2026
Town of Yarmouth Water Department
99 Buck Island Road
West Yarmouth, MA 02673
(508)776-1892
Building Contact:Luke White
Title:Contact
Company:Cape Cod Alarm
Contact:Chad Benaka
Title:Service Tech
Fire Alarm Systems
INSPECTIONCERTIFICATE
Aug 12, 2026Inspection Date:
Tested to NFPA 72 Standards
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed
ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Page of 2 15
Executive Summary
Cape Cod Alarm Download Date: 08/13/2026
EXECUTIVE SUMMARY
Generated by: BuildingReports.com
Building Information
Town of Yarmouth Water Department
99 Buck Island Road
West Yarmouth, MA 02673
United States of America
Contact: Luke White
Phone: (508)776-1892
Fax:
Mobile:
Email:
Inspection Performed By
Cape Cod Alarm204 Old Townhouse RoadWest Yarmouth, MA 02673United States of America
Inspector: Chad Benaka
Phone: (508) 398-6316
Fax:
Mobile:
Email: service@capecodalarm.com
System Control Unit
Manufacturer: Notifier Inspection Date: 08/07/2026 IDC Style: E
Model Number: System 500 Install Date: 08/07/2026 SLC Style: N/A
Software Version:Version Date: 12/31/1969 NAC Style: E
Location: 2nd Floor Electrical Room Disconnect Location:Disconnect Type:
Current Protection: Breaker
Monitoring
Company: Cape Cod Alarm Phone:Account #: S29583
Central Station Signal Verification
Type: Mesh Radio Network Mfg: AES Model #: 7788F
Test Time/Date: 8/7/26 2:44:18 PM Restore Time: 3:44 PM Note:
Type of Signal Signal Confirmed Time Notes
Alarm Signal 3:25 PM
Trouble Signal 3:26 PM
Page of 3 15
Executive Summary
Cape Cod Alarm Download Date: 08/13/2026
Building: Town of Yarmouth Water
Department
Contact: Luke White
Company: Cape Cod Alarm
Inspector: Chad Benaka
Inspection Summary
Category
Total Items Serviced Passed Failed/Other
Qty %Qty %Qty %Qty %
Control 6 13.95%6 100.00%6 100.00%0 0.00%
Indicating 15 34.88%15 100.00%13 86.67%2 13.33%
Initiating 11 25.58%11 100.00%10 90.91%1 9.09%
Monitor 2 4.65%2 100.00%2 100.00%0 0.00%
Supervisory 9 20.93%9 100.00%9 100.00%0 0.00%
Totals 43 100%43 100.00%40 93.02%3 6.98%
Certification
Page of 4 15
Discrepancy Report
Cape Cod Alarm Download Date: 08/13/2026
Control Panel: 1 - Notifier System 500Building: Town of Yarmouth Water Department
DISCREPANCY REPORT
Deficiency, Impairment, and Observation
Generated by: BuildingReports.com
The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where
appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a
manufacturer's replacement/upgrade program is included.
This section is now enhanced by BuildingReports AI, which helps refine applicable manufacturer recalls and replacement notices, enabling service providers and facilities to address potential issues more quickly.
Building: Town of Yarmouth Water Department
Items listed for Recall or Replacement/Upgrade
Device Type Manufacturer Model Number Date Qty
No recalled items found during this inspection.
Discrepancies
ScanID Location Problem Address Reference
INDICATING
Remote Indicator
B9519871 2nd Floor above Boiler Room Door Failed Operation 1 NFPA72
14.2.2.2.2
B9519869 2nd Floor above Electrical Room Door Failed Operation 1 NFPA72 14.2.2.2.2
INITIATING
Pull Station
B9519901 1st Floor Rear Garage Right Side Exit Door Damaged/Worn 1 NFPA72
14.2.2.2.2
Code References
NFPA72 14.2.2.2.2 System deficiencies shall be corrected.
Page of 5 15
Proposed Solutions Report
Cape Cod Alarm Download Date: 08/13/2026
Control Panel: 1 - Notifier System 500Building: Town of Yarmouth Water Department
PROPOSED SOLUTIONS REPORT
Generated by: BuildingReports.com
The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark
where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials
basis.
ScanID Location Solution Model #Cost Fixed Date
INDICATING
Remote Indicator
B9519871 2nd Floor above Boiler Room Door Investigate/Replace RA400Z T/M
B9519869 2nd Floor above Electrical Room
Door
Investigate/Replace RA400Z T/M
INITIATING
Pull Station
B9519901 1st Floor Rear Garage Right Side
Exit Door
Replace NBG-10 T/M
Customer WO/PO #:
(none)
Internal WO/PO #:
(none)
Total: T/M
Page of 6 15
Inspection & Testing
Cape Cod Alarm Download Date: 08/13/2026
Control Panel: 1 - Notifier System 500Building: Town of Yarmouth Water Department
INSPECTION & TESTING
Generated by: BuildingReports.com
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other .
Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.
Device Type Location Service Time Date
PASSED
Control
Annunciator 1st Floor Office Area Side Exit Door Tested 3:08:23 PM 08/07/2026
Battery In AES Transmitter Tested 2:42:10 PM 08/07/2026
Battery In Fire Alarm Control Panel Tested 2:46:26 PM 08/07/2026
Battery In Fire Alarm Control Panel Tested 2:46:48 PM 08/07/2026
Communicator 2nd Floor Electrical Room Tested 2:44:18 PM 08/07/2026
Control Panel 2nd Floor Electrical Room Tested 2:36:49 PM 08/07/2026
Indicating
Horn/Strobe 1st Floor Garage Front Wall Middle Tested 2:51:16 PM 08/07/2026
Horn/Strobe 1st Floor Garage Left Side Exit Door Tested 2:49:09 PM 08/07/2026
Horn/Strobe 1st Floor Garage Rear Wall Middle Tested 2:52:01 PM 08/07/2026
Horn/Strobe 1st Floor Garage Right Side Exit Door Tested 2:58:54 PM 08/07/2026
Horn/Strobe 1st Floor Office Area Main Entry Tested 3:07:19 PM 08/07/2026
Horn/Strobe 1st Floor Office Area Main Hallway Tested 3:04:35 PM 08/07/2026
Horn/Strobe 1st Floor Office Area Side Exit Door Tested 3:03:35 PM 08/07/2026
Horn/Strobe 1st Floor Rear Garage Left Side Door Tested 2:53:20 PM 08/07/2026
Horn/Strobe 2nd Floor Garage Front Tested 2:38:06 PM 08/07/2026
Horn/Strobe 2nd Floor Garage Rear Tested 2:38:32 PM 08/07/2026
Strobe 1st Floor Men’s Restroom Tested 3:00:42 PM 08/07/2026
Strobe 1st Floor Women’s Restroom Tested 3:02:17 PM 08/07/2026
Page of 7 15
Inspection & Testing
Cape Cod Alarm Download Date: 08/13/2026
Device Type Location Service Time Date
PASSED (continued)
Indicating (continued)
Strobe 1st Floor Office Area Conference Room Tested 3:05:36 PM 08/07/2026
Initiating
Pull Station 1st Floor Garage Left Side Exit Door Tested 2:49:54 PM 08/07/2026
Pull Station 1st Floor Garage Right Side Exit Door Tested 2:59:11 PM 08/07/2026
Pull Station 1st Floor Office Area Main Entry Tested 3:06:58 PM 08/07/2026
Pull Station 1st Floor Office Area Side Exit Door Tested 3:03:07 PM 08/07/2026
Pull Station 1st Floor Rear Garage Left Side Exit Door Tested 2:54:58 PM 08/07/2026
Smoke Detector 2nd Floor Boiler Room Tested 2:40:11 PM 08/07/2026
Smoke Detector 2nd Floor Electrical Room Tested 2:39:13 PM 08/07/2026
Waterflow Switch 1st Floor Garage Sprinkler Area Tested 3:14:41 PM 08/07/2026
Waterflow Switch 1st Floor Garage Sprinkler Area Tested 3:14:44 PM 08/07/2026
Waterflow Switch 1st Floor Garage Sprinkler Area Tested 3:14:50 PM 08/07/2026
Monitor
Monitoring Alarm Signal Tested 2:44:51 PM 08/07/2026
Monitoring Trouble Signal Tested 2:45:26 PM 08/07/2026
Supervisory
Air Pressure Switch 1st Floor Garage Sprinkler Area Tested 3:12:14 PM 08/07/2026
Air Pressure Switch 1st Floor Garage Sprinkler Area Tested 3:13:34 PM 08/07/2026
Air Pressure Switch 1st Floor Garage Sprinkler Area Tested 3:13:48 PM 08/07/2026
Air Pressure Switch 1st Floor Garage Sprinkler Area Tested 3:13:57 PM 08/07/2026
Tamper Switch 1st Floor Garage Sprinkler Area Tested 3:15:00 PM 08/07/2026
Tamper Switch 1st Floor Garage Sprinkler Area Tested 3:15:58 PM 08/07/2026
Tamper Switch 1st Floor Garage Sprinkler Area Tested 3:16:20 PM 08/07/2026
Tamper Switch 1st Floor Garage Sprinkler Area Tested 3:16:23 PM 08/07/2026
Tamper Switch 1st Floor Garage Sprinkler Area Tested 3:16:27 PM 08/07/2026
FAILED/OTHER
Page of 8 15
Inspection & Testing
Cape Cod Alarm Download Date: 08/13/2026
Device Type Location Service Time Date
FAILED/OTHER (continued)
Indicating
Remote Indicator 2nd Floor above Boiler Room Door Tested 3:37:45 PM 08/12/2026
Remote Indicator 2nd Floor above Electrical Room Door Tested 3:43:06 PM 08/12/2026
Initiating
Pull Station 1st Floor Rear Garage Right Side Exit Door Tested 3:26:58 PM 08/12/2026
Page of 9 15
Service Summary
Cape Cod Alarm Download Date: 08/13/2026
SERVICE SUMMARY
Generated by: BuildingReports.com
The Service Summary section provides an overview of the services performed in this report.
Building: Town of Yarmouth Water Department
Device Type Service Quantity
PASSED
Air Pressure Switch Tested 4
Annunciator, LED List Tested 1
Battery, Sealed Lead Acid Tested 3
Communicator, Mesh Radio Network Tested 1
Control Panel, Conventional Tested 1
Horn/Strobe Tested 10
Monitoring, Alarm Signal Tested 1
Monitoring, Trouble Signal Tested 1
Pull Station, Dual Action Tested 5
Smoke Detector Tested 2
Strobe Tested 3
Tamper Switch Tested 5
Waterflow Switch Tested 3
Total 40
FAILED/OTHER
Pull Station, Dual Action Tested 1
Remote Indicator Tested 2
Total 3
Grand Total 43
Page of 10 15
Sound and Visual Testing
Cape Cod Alarm Download Date: 08/13/2026
SOUND AND VISUAL TESTING
Generated by: BuildingReports.com
The Sound and Visual Testing section lists various points throughout your building where audible and visual alarm notification
devices were tested. Any bar-coded audible and visual devices will appear in the Inspection and Testing section of this report.
Items in this section are grouped by Passed or Failed/Other. Where specific decibel readings were recorded, they will appear
under the ambient and alarm columns. The Voice column indicates whether the Sound Test Point passed the Voice Intelligibility
requirements. The STI or Sound Transmission Index is shown if recorded.
Building: Town of Yarmouth Water Department
Audible/Visual Appliances
Location Comment Ambient Alarm Synched ScanID
PASSED
Horn/Strobe
2nd Floor Garage Rear Passed ☐A9021805
2nd Floor Garage Front Passed ☐A9021806
1st Floor Garage Left Side Exit
Door
Passed ☐B9519899
1st Floor Garage Rear Wall Middle Passed ☐B9519900
1st Floor Office Area Side Exit
Door
Passed ☐B9519902
1st Floor Garage Right Side Exit Door Passed ☐B9519906
1st Floor Rear Garage Left Side
Door
Passed ☐B9519908
1st Floor Garage Front Wall
Middle
Passed ☐B9519909
1st Floor Office Area Main Entry Passed ☐B9519910
1st Floor Office Area Main
Hallway
Passed ☐B9519919
Strobe
1st Floor Women’s Restroom Passed ☐B9519903
Page of 11 15
Sound and Visual Testing
Cape Cod Alarm Download Date: 08/13/2026
Location Comment Ambient Alarm Synched ScanID
PASSED (continued)
Strobe (continued)
1st Floor Men’s Restroom Passed ☐B9519904
1st Floor Office Area Conference
Room
Passed ☐B9519918
Page of 12 15
Battery & Power Supply Testing
Cape Cod Alarm Download Date: 08/13/2026
Control Panel: 1 - Notifier System 500Building: Town of Yarmouth Water Department
BATTERY & POWER SUPPLY TESTING
Generated by: BuildingReports.com
The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to
provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Battery
Type Location
Rated
Ah
Rated
Volts
Pre
Test
Post
Test
Min
Ah
Teste
d Ah
MFG
Date
PASSED
Sealed Lead Acid In AES Transmitter 7 12 100%100%08/29
/2025
Sealed Lead Acid In Fire Alarm Control Panel 7 12 100%100%08/07
/2026
Sealed Lead Acid In Fire Alarm Control Panel 7 12 100%100%08/07/2026
Page of 13 15
Inventory & Warranty Report
Cape Cod Alarm Download Date: 08/13/2026
Control Panel: 1 - Notifier System 500Building: Town of Yarmouth Water Department
INVENTORY & WARRANTY REPORT
Generated by: BuildingReports.com
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete
inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices
installed for two years or more are grouped together for easy reference.
Building: Town of Yarmouth Water Department
Device or Type Category % of Inventory Quantity
Air Pressure Switch Supervisory 9.30%4
Annunciator Control 2.33%1
Battery Control 6.98%3
Communicator Control 2.33%1
Control Panel Control 2.33%1
Horn/Strobe Indicating 23.26%10
Monitoring Monitor 4.65%2
Pull Station Initiating 13.95%6
Remote Indicator Indicating 4.65%2
Smoke Detector Initiating 4.65%2
Strobe Indicating 6.98%3
Tamper Switch Supervisory 11.63%5
Waterflow Switch Initiating 6.98%3
Type Qty Model #Description Install Date
NEW (UNDER 90 DAYS)
AES
Communicator 1 7788F Mesh Radio Network 08/07/2026
Central
Page of 14 15
Inventory & Warranty Report
Cape Cod Alarm Download Date: 08/13/2026
Type Qty Model #Description Install Date
NEW (UNDER 90 DAYS)(continued)
Central (continued)
Tamper Switch 1 BFV 08/07/2026
Tamper Switch 4 OSYSU-2 08/07/2026
Gentex
Horn/Strobe 1 SHG-24-15/75WR 08/07/2026
Strobe 2 08/07/2026
Notifier
Control Panel 1 System 500 Conventional 08/07/2026
Pull Station 6 NBG-10 Dual Action 08/07/2026
Potter
Air Pressure Switch 3 PS10-2A 08/07/2026
Air Pressure Switch 1 PS40-2A 08/07/2026
Waterflow Switch 3 VSR-F 08/07/2026
Power Patrol
Battery 2 FAS1075 Sealed Lead Acid 08/07/2026
Space Age
Annunciator 1 LED List 08/07/2026
System Sensor
Remote Indicator 2 RA400Z 08/07/2026
Smoke Detector 2 2100T 08/07/2026
Strobe 1 PS24-LO 08/07/2026
Wheelock
Horn/Strobe 9 08/07/2026
(manufacturer not specified)
Monitoring 1 Alarm Signal 08/07/2026
Monitoring 1 Trouble Signal 08/07/2026
IN SERVICE - 90 DAYS - 1 YEAR
Page of 15 15
Inventory & Warranty Report
Cape Cod Alarm Download Date: 08/13/2026
Type Qty Model #Description Install Date
IN SERVICE - 90 DAYS - 1 YEAR (continued)
Power Patrol
Battery 1 FAS1075 Sealed Lead Acid 08/29/2025