HomeMy WebLinkAbout2026 FIRE ALARM INSPECTION BUILDING REPORT2026
Cape Cod Mechanical Systems
8 Fruean Avenue
South Yarmouth, MA X
(508)394-7501
Building Contact:Shane Wintringham
Title:Contact
Company:Cape Cod Alarm
Contact:Chad Benaka
Title:Service Tech
Fire Alarm Systems
INSPECTIONCERTIFICATE
Aug 18, 2026Inspection Date:
Tested to NFPA 72 Standards
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed
ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Page of 2 14
Executive Summary
Cape Cod Alarm Download Date: 08/20/2026
EXECUTIVE SUMMARY
Generated by: BuildingReports.com
Building Information
Cape Cod Mechanical Systems
8 Fruean Avenue
South Yarmouth, MA X
United States of America
Contact: Shane Wintringham
Phone: (508)394-7501
Fax:
Mobile:
Email:
Inspection Performed By
Cape Cod Alarm204 Old Townhouse RoadWest Yarmouth, MA 02673United States of America
Inspector: Chad Benaka
Phone: (508) 398-6316
Fax:
Mobile:
Email: service@capecodalarm.com
System Control Unit
Manufacturer: ESL Inspection Date: 08/18/2026 IDC Style: E
Model Number: 1503 Install Date: 08/18/2000 SLC Style: N/A
Software Version:Version Date: 12/31/1969 NAC Style: E
Location: 1st Floor Storage Closet Disconnect Location:Disconnect Type:
Current Protection: Breaker
Monitoring
Company: Cape Cod Alarm Phone:Account #: S52189
Central Station Signal Verification
Type: Mesh Radio Network Mfg: AES Model #: 7058E
Test Time/Date: 8/18/26 2:11:08 PM Restore Time: 3:22 PM Note:
Type of Signal Signal Confirmed Time Notes
Alarm Signal 2:38 PM
Page of 3 14
Executive Summary
Cape Cod Alarm Download Date: 08/20/2026
Building: Cape Cod Mechanical Systems
Contact: Shane Wintringham
Company: Cape Cod Alarm
Inspector: Chad Benaka
Inspection Summary
Category
Total Items Serviced Passed Failed/Other
Qty %Qty %Qty %Qty %
Control 5 20.00%5 100.00%5 100.00%0 0.00%
Indicating 3 12.00%3 100.00%3 100.00%0 0.00%
Initiating 16 64.00%16 100.00%10 62.50%6 37.50%
Monitor 1 4.00%1 100.00%1 100.00%0 0.00%
Totals 25 100%25 100.00%19 76.00%6 24.00%
Certification
Page of 4 14
Discrepancy Report
Cape Cod Alarm Download Date: 08/20/2026
Control Panel: 1 - ESL 1503Building: Cape Cod Mechanical Systems
DISCREPANCY REPORT
Deficiency, Impairment, and Observation
Generated by: BuildingReports.com
The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where
appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a
manufacturer's replacement/upgrade program is included.
This section is now enhanced by BuildingReports AI, which helps refine applicable manufacturer recalls and replacement notices, enabling service providers and facilities to address potential issues more quickly.
Building: Cape Cod Mechanical Systems
Items listed for Recall or Replacement/Upgrade
Device Type Manufacturer Model Number Date Qty
No recalled items found during this inspection.
Discrepancies
ScanID Location Problem Address Reference
INITIATING
Heat Detector
B9520014 1st Floor Front Left Office Restroom Date Expired 1 NFPA72 Table
14.4.3.2 (17)(4)(c)
B9520039 1st Floor Garage (1st from Office)Date Expired 1 NFPA72 Table 14.4.3.2 (17)(4)(c)
B9520032 1st Floor Garage (2nd from Office)Date Expired 1 NFPA72 Table
14.4.3.2 (17)(4)(c)
B9520033 1st Floor Garage (far end)Date Expired 1 NFPA72 Table
14.4.3.2 (17)(4)(c)
B9520040 1st Floor Garage above Office Date Expired 1 NFPA72 Table 14.4.3.2 (17)(4)(c)
Page of 5 14
Discrepancy Report
Cape Cod Alarm Download Date: 08/20/2026
ScanID Location Problem Address Reference
INITIATING (continued)
Heat Detector (continued)
B9520034 1st Floor Hallway Restroom Date Expired 1 NFPA72 Table 14.4.3.2 (17)(4)(c)
Code References
NFPA72 Table 14.4.3.2 (17)
(4)(c)
After 15 years from initial installation, replace all devices or have 2 detectors per 100
laboratory tested.
Page of 6 14
Proposed Solutions Report
Cape Cod Alarm Download Date: 08/20/2026
Control Panel: 1 - ESL 1503Building: Cape Cod Mechanical Systems
PROPOSED SOLUTIONS REPORT
Generated by: BuildingReports.com
The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark
where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials
basis.
ScanID Location Solution Model #Cost Fixed Date
INITIATING
Heat Detector
B9520014 1st Floor Front Left Office
Restroom
Replace 281BPL T/M
B9520039 1st Floor Garage (1st from Office)Replace 284BPL T/M
B9520032 1st Floor Garage (2nd from Office)Replace 284BPL T/M
B9520033 1st Floor Garage (far end)Replace 284BPL T/M
B9520040 1st Floor Garage above Office Replace 284BPL T/M
B9520034 1st Floor Hallway Restroom Replace 281BPL T/M
Customer WO/PO #:(none)Internal WO/PO #:(none)Total: T/M
Page of 7 14
Notes & Recommendations
Cape Cod Alarm Download Date: 08/20/2026
NOTES & RECOMMENDATIONS
Generated by: BuildingReports.com
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the
building inspection. Notes are grouped by Category.
General Note
Three of the garage heats are 16-20 feet high
Page of 8 14
Inspection & Testing
Cape Cod Alarm Download Date: 08/20/2026
Control Panel: 1 - ESL 1503Building: Cape Cod Mechanical Systems
INSPECTION & TESTING
Generated by: BuildingReports.com
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other .
Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.
Device Type Location Service Time Date
PASSED
Control
Battery In AES Transmitter Tested 2:11:51 PM 08/18/2026
Battery In Fire Alarm Control Panel Tested 2:36:38 PM 08/18/2026
Battery In Fire Alarm Control Panel Tested 2:36:57 PM 08/18/2026
Communicator 1st Floor Storage Closet Tested 2:11:08 PM 08/18/2026
Control Panel 1st Floor Storage Closet Tested 2:14:08 PM 08/18/2026
Indicating
Horn/Strobe 1st Floor Garage Restroom Tested 2:28:56 PM 08/18/2026
Horn/Strobe 1st Floor Garage Side Door Tested 2:31:22 PM 08/18/2026
Horn/Strobe 1st Floor Office Entry Tested 2:18:04 PM 08/18/2026
Initiating
Heat Detector 1st Floor Garage Restroom Tested 2:28:04 PM 08/18/2026
Pull Station 1st Floor Garage Side Door Tested 2:31:02 PM 08/18/2026
Pull Station 1st Floor Office Entry Tested 2:19:52 PM 08/18/2026
Smoke Detector 1st Floor Back Office Tested 2:25:58 PM 08/18/2026
Smoke Detector 1st Floor Front Left Office Tested 2:22:09 PM 08/18/2026
Smoke Detector 1st Floor Garage Contractor’s Office Tested 2:30:06 PM 08/18/2026
Smoke Detector 1st Floor Hallway to Garage Tested 3:12:39 PM 08/18/2026
Smoke Detector 1st Floor Office Entry Tested 2:21:37 PM 08/18/2026
Smoke Detector 1st Floor Small Office by Garage Tested 3:09:28 PM 08/18/2026
Page of 9 14
Inspection & Testing
Cape Cod Alarm Download Date: 08/20/2026
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
Smoke Detector 1st Floor Storage Closet Tested 2:20:23 PM 08/18/2026
Monitor
Monitoring Alarm Signal Tested 2:13:07 PM 08/18/2026
FAILED/OTHER
Initiating
Heat Detector 1st Floor Front Left Office Restroom Tested 2:24:56 PM 08/18/2026
Heat Detector 1st Floor Garage (1st from Office)Tested 2:35:04 PM 08/18/2026
Heat Detector 1st Floor Garage (2nd from Office)Tested 2:25:06 PM 08/18/2026
Heat Detector 1st Floor Garage (far end)Tested 2:25:15 PM 08/18/2026
Heat Detector 1st Floor Garage above Office Tested 2:34:54 PM 08/18/2026
Heat Detector 1st Floor Hallway Restroom Tested 2:35:43 PM 08/18/2026
Page of 10 14
Service Summary
Cape Cod Alarm Download Date: 08/20/2026
SERVICE SUMMARY
Generated by: BuildingReports.com
The Service Summary section provides an overview of the services performed in this report.
Building: Cape Cod Mechanical Systems
Device Type Service Quantity
PASSED
Battery, Sealed Lead Acid Tested 3
Communicator, Mesh Radio Network Tested 1
Control Panel, Conventional Tested 1
Heat Detector, Hardwire - Combination Tested 1
Horn/Strobe Tested 3
Monitoring, Alarm Signal Tested 1
Pull Station, Single Action Tested 2
Smoke Detector Tested 7
Total 19
FAILED/OTHER
Heat Detector, Hardwire - Fixed
Temperature
Tested 4
Heat Detector, Hardwire - Combination Tested 2
Total 6
Grand Total 25
Page of 11 14
Sound and Visual Testing
Cape Cod Alarm Download Date: 08/20/2026
SOUND AND VISUAL TESTING
Generated by: BuildingReports.com
The Sound and Visual Testing section lists various points throughout your building where audible and visual alarm notification
devices were tested. Any bar-coded audible and visual devices will appear in the Inspection and Testing section of this report.
Items in this section are grouped by Passed or Failed/Other. Where specific decibel readings were recorded, they will appear
under the ambient and alarm columns. The Voice column indicates whether the Sound Test Point passed the Voice Intelligibility
requirements. The STI or Sound Transmission Index is shown if recorded.
Building: Cape Cod Mechanical Systems
Audible/Visual Appliances
Location Comment Ambient Alarm Synched ScanID
PASSED
Horn/Strobe
1st Floor Office Entry Passed ☐B9520009
1st Floor Garage Side Door Passed ☐B9520031
1st Floor Garage Restroom Passed ☐B9520042
Page of 12 14
Battery & Power Supply Testing
Cape Cod Alarm Download Date: 08/20/2026
Control Panel: 1 - ESL 1503Building: Cape Cod Mechanical Systems
BATTERY & POWER SUPPLY TESTING
Generated by: BuildingReports.com
The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to
provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Battery
Type Location
Rated
Ah
Rated
Volts
Pre
Test
Post
Test
Min
Ah
Teste
d Ah
MFG
Date
PASSED
Sealed Lead Acid In AES Transmitter 5 12 90%80%01/04
/2024
Sealed Lead Acid In Fire Alarm Control Panel 7 12 100%100%08/18
/2026
Sealed Lead Acid In Fire Alarm Control Panel 7 12 100%100%08/18/2026
Page of 13 14
Inventory & Warranty Report
Cape Cod Alarm Download Date: 08/20/2026
Control Panel: 1 - ESL 1503Building: Cape Cod Mechanical Systems
INVENTORY & WARRANTY REPORT
Generated by: BuildingReports.com
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete
inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices
installed for two years or more are grouped together for easy reference.
Building: Cape Cod Mechanical Systems
Device or Type Category % of Inventory Quantity
Battery Control 12.00%3
Communicator Control 4.00%1
Control Panel Control 4.00%1
Heat Detector Initiating 28.00%7
Horn/Strobe Indicating 12.00%3
Monitoring Monitor 4.00%1
Pull Station Initiating 8.00%2
Smoke Detector Initiating 28.00%7
Type Qty Model #Description Install Date
NEW (UNDER 90 DAYS)
AES
Communicator 1 7058E Mesh Radio Network 08/18/2026
Power Patrol
Battery 2 FAS1075 Sealed Lead Acid 08/18/2026
System Sensor
Smoke Detector 2 2WB 08/18/2026
(manufacturer not specified)
Monitoring 1 Alarm Signal 08/18/2026
IN SERVICE - 2 YEARS TO 3 YEARS
Page of 14 14
Inventory & Warranty Report
Cape Cod Alarm Download Date: 08/20/2026
Type Qty Model #Description Install Date
IN SERVICE - 2 YEARS TO 3 YEARS (continued)
Power Patrol
Battery 1 FAS1055 Sealed Lead Acid 01/04/2024
IN SERVICE - 5 YEARS TO 10 YEARS
System Sensor
Heat Detector 1 5601P Hardwire - Combination 08/18/2020
IN SERVICE - 25 YEARS OR OLDER
ESL
Control Panel 1 1503 Conventional 08/18/2000
Smoke Detector 5 521BXT 08/18/2000
Edwards
Heat Detector 2 281BPL Hardwire - Combination 08/18/2000
Heat Detector 4 284BPL Hardwire - Fixed Temperature 08/18/2000
Pull Station 2 270 Single Action 08/18/2000
Mircom
Horn/Strobe 2 FHS-240R 08/18/2000
Siemens
Horn/Strobe 1 MHU-MCS-RC 08/18/2000