HomeMy WebLinkAbout2026 FIRE ALARM INSPECTION BUILDING REPORT2026
Kennedy Donovan Center
30 Ansel Hallet Road
West Yarmouth, MA 02673
(508)385-6019
Building Contact:Sondra Marquis
Title:Contact
Company:Cape Cod Alarm
Contact:Chad Benaka
Title:Service Tech
Fire Alarm Systems
INSPECTIONCERTIFICATE
Aug 19, 2026Inspection Date:
Tested to NFPA 72 Standards
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed
ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Page of 2 12
Executive Summary
Cape Cod Alarm Download Date: 08/20/2026
EXECUTIVE SUMMARY
Generated by: BuildingReports.com
Building Information
Kennedy Donovan Center
30 Ansel Hallet Road
West Yarmouth, MA 02673
United States of America
Contact: Sondra Marquis
Phone: (508)385-6019
Fax:
Mobile:
Email:
Inspection Performed By
Cape Cod Alarm204 Old Townhouse RoadWest Yarmouth, MA 02673United States of America
Inspector: Chad Benaka
Phone: (508) 398-6316
Fax:
Mobile:
Email: service@capecodalarm.com
System Control Unit
Manufacturer: Fire-Lite Inspection Date: 08/19/2026 IDC Style: E
Model Number: MS-10UD Install Date: 11/16/2023 SLC Style: N/A
Software Version:Version Date: 09/01/2021 NAC Style: E
Location: 1st Floor Right Entry Foyer Disconnect Location:Disconnect Type:
Current Protection: Breaker
Monitoring
Company: Cape Cod Alarm Phone: (508)398-6316 Account #: S11398
Central Station Signal Verification
Type: Mesh Radio Network Mfg: AES Model #: 7788F
Test Time/Date: 8/19/26 2:31:35 PM Restore Time: 3:20 PM Note:
Type of Signal Signal Confirmed Time Notes
Trouble Signal 2:32 PM
Alarm Signal 2:54 PM
Page of 3 12
Executive Summary
Cape Cod Alarm Download Date: 08/20/2026
Building: Kennedy Donovan Center
Contact: Sondra Marquis
Company: Cape Cod Alarm
Inspector: Chad Benaka
Inspection Summary
Category
Total Items Serviced Passed Failed/Other
Qty %Qty %Qty %Qty %
Control 5 10.42%5 100.00%5 100.00%0 0.00%
Indicating 12 25.00%12 100.00%12 100.00%0 0.00%
Initiating 29 60.42%29 100.00%29 100.00%0 0.00%
Monitor 2 4.17%2 100.00%2 100.00%0 0.00%
Totals 48 100%48 100.00%48 100.00%0 0.00%
Certification
Page of 4 12
Inspection & Testing
Cape Cod Alarm Download Date: 08/20/2026
Control Panel: 1 - Fire-Lite MS-10UDBuilding: Kennedy Donovan Center
INSPECTION & TESTING
Generated by: BuildingReports.com
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other .
Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.
Device Type Location Service Time Date
PASSED
Control
Battery 1st Floor in AES Transmitter Tested 2:51:51 PM 08/19/2026
Battery 1st Floor in Fire Alarm Control Panel Tested 2:34:16 PM 08/19/2026
Battery 1st Floor in Fire Alarm Control Panel Tested 2:34:18 PM 08/19/2026
Communicator 1st Floor Right Entry Foyer (above Fire
Alarm Control Panel)
Tested 2:31:35 PM 08/19/2026
Control Panel 1st Floor Right Entry Foyer Tested 2:34:45 PM 08/19/2026
Indicating
Horn/Strobe 1st Floor Left Entry Foyer Tested 2:51:24 PM 08/19/2026
Horn/Strobe 1st Floor Left Side Classroom Tested 2:47:04 PM 08/19/2026
Horn/Strobe 1st Floor Left Side Conference Room Tested 2:48:59 PM 08/19/2026
Horn/Strobe 1st Floor Right Entry Foyer Tested 2:31:48 PM 08/19/2026
Horn/Strobe 1st Floor Right Side Large Room Tested 2:51:28 PM 08/19/2026
Horn/Strobe 1st Floor Left Side Hallway by Therapy Room Tested 2:51:33 PM 08/19/2026
Horn/Strobe 1st Floor Right Side Rear Exit by Electrical
Room
Tested 2:39:31 PM 08/19/2026
Strobe 1st Floor Left Side Left Restroom Tested 2:50:07 PM 08/19/2026
Strobe 1st Floor Left Side Left Side Children’s Restroom Tested 2:46:52 PM 08/19/2026
Strobe 1st Floor Left Side Right Restroom Tested 2:49:56 PM 08/19/2026
Strobe 1st Floor Right Side Rear Exit Right
Restroom
Tested 2:39:22 PM 08/19/2026
Page of 5 12
Inspection & Testing
Cape Cod Alarm Download Date: 08/20/2026
Device Type Location Service Time Date
PASSED (continued)
Indicating (continued)
Strobe 1st Floor Right Side Rear Exit Right Restroom Tested 2:39:28 PM 08/19/2026
Initiating
Duct Detector Duct Smoke A Tested 2:34:47 PM 08/19/2026
Duct Detector Duct Smoke B Tested 2:34:50 PM 08/19/2026
Heat Detector Attic Left Side (East)Tested 2:56:25 PM 08/19/2026
Heat Detector Attic Left Side (East)Tested 2:56:29 PM 08/19/2026
Heat Detector Attic Left Side (East)Tested 2:56:33 PM 08/19/2026
Pull Station 1st Floor Left Entry Foyer Tested 2:51:17 PM 08/19/2026
Pull Station 1st Floor Left Side Classroom Tested 2:47:08 PM 08/19/2026
Pull Station 1st Floor Left Side Conference Room Tested 2:48:56 PM 08/19/2026
Pull Station 1st Floor Right Entry Foyer Tested 2:31:47 PM 08/19/2026
Pull Station 1st Floor Right Side Rear Exit by Electrical
Room
Tested 2:39:30 PM 08/19/2026
Remote Test Switch 1st Floor Right Entry Foyer Tested 2:34:52 PM 08/19/2026
Remote Test Switch 1st Floor Right Entry Foyer Tested 2:34:54 PM 08/19/2026
Smoke Detector 1st Floor Left Side Conference Room Tested 2:49:06 PM 08/19/2026
Smoke Detector 1st Floor Right Area Large Room Tested 2:42:35 PM 08/19/2026
Smoke Detector 1st Floor Right Entry Foyer Tested 2:44:10 PM 08/19/2026
Smoke Detector 1st Floor Right Foyer Left Office Tested 2:44:18 PM 08/19/2026
Smoke Detector 1st Floor Right Foyer Right Office Tested 2:42:22 PM 08/19/2026
Smoke Detector 1st Floor Right Side Breakroom Tested 2:37:38 PM 08/19/2026
Smoke Detector 1st Floor Right Side Electrical Room Tested 2:40:42 PM 08/19/2026
Smoke Detector 1st Floor Right Side File Room Tested 2:40:55 PM 08/19/2026
Smoke Detector 1st Floor Right Side Server Room Tested 2:55:27 PM 08/19/2026
Smoke Detector 1st Floor Left Side Hallway by Classroom Tested 2:45:33 PM 08/19/2026
Page of 6 12
Inspection & Testing
Cape Cod Alarm Download Date: 08/20/2026
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
Smoke Detector 1st Floor Left Side Hallway by Restrooms Tested 2:45:40 PM 08/19/2026
Smoke Detector 1st Floor Left Side Hallway by Therapy Room Tested 2:45:29 PM 08/19/2026
Smoke Detector 1st Floor Left Side Reception Area Front Tested 2:51:43 PM 08/19/2026
Smoke Detector 1st Floor Left Side Reception Area Rear Tested 2:51:39 PM 08/19/2026
Smoke Detector 1st Floor Right Side Conference Room by Breakroom Tested 2:37:41 PM 08/19/2026
Smoke Detector 1st Floor Right Side Hallway by Breakroom Tested 2:37:31 PM 08/19/2026
Smoke Detector 1st Floor Right Side Office by Conference
Room
Tested 2:42:28 PM 08/19/2026
Monitor
Monitoring Alarm Signal Tested 2:31:37 PM 08/19/2026
Monitoring Trouble Signal Tested 2:31:40 PM 08/19/2026
Page of 7 12
Service Summary
Cape Cod Alarm Download Date: 08/20/2026
SERVICE SUMMARY
Generated by: BuildingReports.com
The Service Summary section provides an overview of the services performed in this report.
Building: Kennedy Donovan Center
Device Type Service Quantity
PASSED
Battery, Sealed Lead Acid Tested 3
Communicator, Mesh Radio Network Tested 1
Control Panel, Conventional Tested 1
Duct Detector Tested 2
Heat Detector, Fixed Temperature Tested 3
Horn/Strobe Tested 7
Monitoring, Trouble Signal Tested 1
Monitoring, Alarm Signal Tested 1
Pull Station, Dual Action Tested 5
Remote Test Switch Tested 2
Smoke Detector Tested 17
Strobe Tested 5
Total 48
Grand Total 48
Page of 8 12
Sound and Visual Testing
Cape Cod Alarm Download Date: 08/20/2026
SOUND AND VISUAL TESTING
Generated by: BuildingReports.com
The Sound and Visual Testing section lists various points throughout your building where audible and visual alarm notification
devices were tested. Any bar-coded audible and visual devices will appear in the Inspection and Testing section of this report.
Items in this section are grouped by Passed or Failed/Other. Where specific decibel readings were recorded, they will appear
under the ambient and alarm columns. The Voice column indicates whether the Sound Test Point passed the Voice Intelligibility
requirements. The STI or Sound Transmission Index is shown if recorded.
Building: Kennedy Donovan Center
Audible/Visual Appliances
Location Comment Ambient Alarm Synched ScanID
PASSED
Horn/Strobe
1st Floor Left Side Conference
Room
Passed ☐71252035
1st Floor Right Side Rear Exit by Electrical Room Passed ☐71252037
1st Floor Left Entry Foyer Passed ☐71252194
1st Floor Right Side Large Room Passed ☐71252215
1st Floor Left Side Hallway by
Therapy Room
Passed ☐71252220
1st Floor Left Side Classroom Passed ☐71252224
1st Floor Right Entry Foyer Passed ☐71252237
Strobe
1st Floor Left Side Left Side
Children’s Restroom
Passed ☐71252218
1st Floor Left Side Right Restroom Passed ☐71252221
1st Floor Left Side Left Restroom Passed ☐71252222
1st Floor Right Side Rear Exit
Right Restroom
Passed ☐71252235
Page of 9 12
Sound and Visual Testing
Cape Cod Alarm Download Date: 08/20/2026
Location Comment Ambient Alarm Synched ScanID
PASSED (continued)
Strobe (continued)
1st Floor Right Side Rear Exit Right Restroom Passed ☐84692040
Page of 10 12
Battery & Power Supply Testing
Cape Cod Alarm Download Date: 08/20/2026
Control Panel: 1 - Fire-Lite MS-10UDBuilding: Kennedy Donovan Center
BATTERY & POWER SUPPLY TESTING
Generated by: BuildingReports.com
The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to
provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Battery
Type Location
Rated
Ah
Rated
Volts
Pre
Test
Post
Test
Min
Ah
Teste
d Ah
MFG
Date
PASSED
Sealed Lead Acid 1st Floor in AES Transmitter 7 12 100%100%09/03
/2025
Sealed Lead Acid 1st Floor in Fire Alarm Control
Panel
7 12 100%90%11/16
/2023
Sealed Lead Acid 1st Floor in Fire Alarm Control Panel 7 12 100%100%11/16/2023
Page of 11 12
Inventory & Warranty Report
Cape Cod Alarm Download Date: 08/20/2026
Control Panel: 1 - Fire-Lite MS-10UDBuilding: Kennedy Donovan Center
INVENTORY & WARRANTY REPORT
Generated by: BuildingReports.com
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete
inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices
installed for two years or more are grouped together for easy reference.
Building: Kennedy Donovan Center
Device or Type Category % of Inventory Quantity
Battery Control 6.25%3
Communicator Control 2.08%1
Control Panel Control 2.08%1
Duct Detector Initiating 4.17%2
Heat Detector Initiating 6.25%3
Horn/Strobe Indicating 14.58%7
Monitoring Monitor 4.17%2
Pull Station Initiating 10.42%5
Remote Test Switch Initiating 4.17%2
Smoke Detector Initiating 35.42%17
Strobe Indicating 10.42%5
Type Qty Model #Description Install Date
IN SERVICE - 90 DAYS - 1 YEAR
Power Patrol
Battery 1 FAS1075 Sealed Lead Acid 09/03/2025
IN SERVICE - 2 YEARS TO 3 YEARS
Fire-Lite
Control Panel 1 MS-10UD Conventional 11/16/2023
System Sensor
Page of 12 12
Inventory & Warranty Report
Cape Cod Alarm Download Date: 08/20/2026
Type Qty Model #Description Install Date
IN SERVICE - 2 YEARS TO 3 YEARS (continued)
System Sensor (continued)
Heat Detector 3 5604 Fixed Temperature 11/01/2023
Universal Battery
Battery 2 UB1270 Sealed Lead Acid 11/16/2023
IN SERVICE - 3 YEARS TO 5 YEARS
System Sensor
Strobe 1 SRL 01/01/2023
IN SERVICE - 5 YEARS TO 10 YEARS
AES
Communicator 1 7788F Mesh Radio Network 09/01/2016
System Sensor
Duct Detector 2 09/01/2016
(manufacturer not specified)
Monitoring 1 Alarm Signal 09/01/2016
Monitoring 1 Trouble Signal 09/01/2016
IN SERVICE - 10 YEARS TO 15 YEARS
Audible Signal Appli
Horn/Strobe 7 AS-24MCW 01/01/2016
Fire-Lite
Pull Station 2 BG-12 Dual Action 01/01/2016
Notifier
Pull Station 3 NBG-12L Dual Action 01/01/2016
System Sensor
Remote Test Switch 2 RTS451KEY 01/01/2016
Smoke Detector 17 2151 01/01/2016
Strobe 1 SRL 01/01/2016
Wheelock
Strobe 3 RSS-24100C 01/01/2016