527 CMR 4.00 Form 1
Application for Permit, Permit, and Certificate of Completion for the
Installation or Alteration ofFuel Oil Burning Equipment and the Storage ofFuel Oil
.LlarW^ri- /0-27- /b
FP-056
(Rev.04/10)
Elec
0wner/Occupant Name:l(alhL!.4,t b"lr-
lnstallation Address: ) Caf Oc
Permit #'s: FD _FDID#:
- (City or Town)(Date)
FeePaid:$ A-
Tel.#: )a'y'' >t L ' Oo ,t
fl Power Vent
Serviced Floor or Unit #:
0therEffieating Unit
Burner: tr New
E Domestic Water Heater
tr Existing E Location:
Mfg e/,-"1;
Type:C-'urn t= b-./Nozzle size: > {^) O /Z
fl Waste oil
Location:1ra-capaciry: lfgallons No. of Tanks:
Special requirements (or additional safety devices)
tr Fuel Oil
Storage Tank: E New
Type:
E Kerosene
Zd*irting
Co. Name
Address:
Completion Date:
Combustion Test:
Smoke:
-/) r-It4
EF: tryestr no
(water heateo
zip:d24,E o
D OSV valve 216l Line Protected tr Sheet Hock E Sprinkler AFUE: tr yes E no
(fumace and boilers)
rct*f2
City:S. D.b-
Net Stack Temp ls>
Breech Draft:---. o
Efficiency Hating %:
q
0
/a ->?-.//
Gross Stack Tsmp.:
C0, Test:/ >'/.
Overfire Draft - , /-t-'
lhe r whom the inslallation (or alleralion)lyas made
.1. Chapter 148 and 527 CMR 4.00 curlently in etfecl.
condilion and inslructions as to ils use and
Stanp)
.5Da
I, the undersigned certily that lhe installalion ol luel burning equipmenl has been made in accordance wilh M.G
Furthermore,lhis installation has been tosted in accordance with such rsquirements, is now in proper op€rating
maintenance have been lumished to
rnsrarer: J4 mn.1-
Print Name>b U4't,/)orvc.u
ced ol ci
Address City
Once signed by the fire department, this is a PERMIT lor the storage of luel oil and use ol the oil burning equipmont.
/L (l-.L C A QTA lFt Ku c- rC t( z\'te
REFER TO CHECKLIST ON REVERSE SIDE
Form Distribution: White: Fire Dept. (Application) Yellow: lnstallation (Permit to Store) Pink: lnstallel (Permit To lnstall)
Approved by:
oTl"V"r"-**",r*k/rr/e/honlrra"mq"/*r[r,*r 4&* o7" "r;"*
Model # or Size:
B/Kr^..,f-
0ale:
ALL INSTALLATIONS
tr4.03 (1)d All applications musl be on Form 1
tr4.03 (1)e Over 10,000 gallons on site requires License & Perm
from localcommunity
tr4,03 (1)g Certificate ol Competency required, no other license
acceptable, plumbing, electrical, etc.
!4.04 (3)a Verjty emergency shul-ofl is outside bumer room
tr4.04 (4)b Verily separate circuit lor oil burner
tr4.04 (4)e Verify presence ol overhead thermal switch
tr4.04 (4)c Verify presence olservice switch within 3'of burner
!4.04 (3)b Verity presence ol high limit controller
fj4 04 (3)c(1) Primary control has safety timing of 45 secs.(max)
tr4.04 (4)d Stack type primary may be easily removed
!4.04 (3)d Steam boiler equipped with low-water cutotf
tr4.04 (4)l Clear access lo clean out and services panels
tr 4.04 (5)b No oil leaks present at burner
tr4.04 (5)d lnstallation instructions present on site
tr4.04 (5)l Overhead combustible clearances within 5 leel over unil
Gypsum board or sprinkler required unless unit is AFUE
(Furnace or Boile4 rated or EF (water healed
tr4.04 (5)g Combustion test results on Form 1
!4.04 (9)b(12) Three metal screws at each joint in chimney
tr4.04 (9)b(7) Thimble present at chimney connection
tr4.04 (9)d lF PoWER VENTER lS USED: Check air pressure
switch, post purge control and secondary control.
lnstallation insfuclions present.
f]4.04 (9)f Dratt regulator is present unless exempted
D4.04 (5)m Adequate air is present for combustion
tr4.04 (5)o Adequate clearances per manutacturers listing
tr4.04 (2)i Thermalvalves al burner and tanks
tr4.04 (1)b Listed flexible hose may be used.
tr4.04 (1)c No Teflon tape on oil line or on oil line fittings
tr4,04 (1)c No compression fittings are permitted
tr a.04 (1)c Solder ioints made with 500 degree F solder or greater
!4.04 (1)e Alloilsupply and relurn lines must be prolected trom
iniury. All new lines must be continuously sleeved with
non metallic tubing. oil safety valves may be used on
exisling lines not exposed to freezing. Overhead lines
require no sleeve and are permitted
tr4.04 (1)g Oil supply lines and retum lines to tanks exposed to
lreezing temperatures must come olf lhe top ol tanks
Lines for kerosene, and range oil (#1) are exempt -
tr4.04 (1)i No oil leaks present at tank
tr4.04 (1)k Listed oillilter is present
tr4.03 (5)b Tank is UL80 or (DlB+) PV-VI 321 (under 660 gal) or UL
142 (over 600 gal)
tr4.03 (5)e Shutoff valve located at bottom ol tank
tr4.03 (5)l Size ol vent as per Table 4.03A
tr4.03 (5)g Oil tank gauge must be present to determine oil level
tr4.03 (1 1)c lnside tanks have audible fill device (v€nt alarm)
tr4.03 (5)J Outlet cross connection at bottom ol tanks must be 1/2'
pipe or lubing.
tr4.03 (5)l Non-combustible tank supports, tank secure.
UNENCLOSED TANKS
Single tanks shall not be largerthan 660 gallons
Maximum aggregate capacity of unenclosed multiple
lanks is 1320 gallons
Unenclosed tanks shall be at least five leet from an
inlernal or exlemal flame
Unenclosed tanks shall not obslruct service meters,
service panels and shutotl valves
Eottom outlet tanks pitched to the opening
Tanks exposed to vehicles will be prolected by barriers
ENCLOSED TANKS
Over 660 gallon tanks enclosed by two hour tire resistive
assembly
Tank enclosures provided with 6' high tight sills or ramps
Tank is 4' above floor supported by 12'thick masonry
saddles spaced not more lhan eight feet on centers and
15" from top and walls ol enclosure
All oil musl be transferred by pump, and conneclions
must be at the top ol the tank
tr4.03 (6)b
tr4.03 (6)b
tr4 03 (6)d
tr4.03 (6)d
n4.03 (6)e
tr4.03 (6)r
! 4.03 (7)a
!4.03 (7)b
D4.03 (7)d
n4.03 (7)e
ALL TANKS
!4.03 (9)d Two tanks may be cross-connected as shown in Fig.
4.03 1.
44.03 (10)b Return lines must enter the top ol tanks
!4.03 (9)c Vent pipes musl be two leet from building openings
tr4.03 (9)c Vent pipes must terminate 3 ft. above grade min.
n4.03 (9)c Vent pipes must have v{eatherproof caps
!4.03 (10)a Fill pipes must be two feel from building openings
!4.03 (10)a Fill pipes must have tamper proof identilying caps
tr4.04 (9)d rF PoWER VENTER rS USED:
All outside conneclions sealed Vent terminal must be three leet
above all air inlets within 1ofl. Burner air intake is exempted Vent
terminal must be lour feet from doors and windows. Vent must be
one loot above flnished grade. Three foot clearance from inside
corners. Nol above or within three leet of an oil tank. Seven feet
above a public walkway.
lF UNDEB PORCH OB DECK: Heating use only, no hot water.
Four leet below deck AND not enclosed under deck
OUTSIDE TANKS
!4.03 (8)a All UST's and tanks over 660 gallons must be installed
as per cMR 9.00
Tank protected from physical damage
Tanks exterior coated with organic alkyd resin or asphalt
paint
Damaged protective coatings musl be recovered
Tank does not block means of egress
Tank mounted on continuous 4'thick slab that extends
8' beyond tank perimeter
Tank is supported by rigid non-combustible supports
fl4.03 (8)c
!4.03 (8)c
!4.03 (8)c
D4.03 (8)c
!4.03 (8)d
Nole To lnstaller: lnspeclions will be conducted using thischecklisl as a guideline. Current regulations will apply.
!4.03 (8)d