HomeMy WebLinkAbout2026 FIRE ALARM INSPECTION BUILDING REPORT2026
Lambrose Nikoladis
812 Main Street
South Yarmouth, MA 02664
(774)269-1166
Building Contact:Lambrose Nikoladis
Title:Contact
Company:Cape Cod Alarm
Contact:Chad Benaka
Title:Service Tech
Fire Alarm Systems
INSPECTIONCERTIFICATE
Sep 3, 2026Inspection Date:
Tested to NFPA 72 Standards
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed
ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Page of 2 14
Executive Summary
Cape Cod Alarm Download Date: 09/08/2026
EXECUTIVE SUMMARY
Generated by: BuildingReports.com
Building Information
Lambrose Nikoladis
812 Main Street
South Yarmouth, MA 02664
United States of America
Contact: Lambrose Nikoladis
Phone: (774)269-1166
Fax:
Mobile:
Email:
Inspection Performed By
Cape Cod Alarm204 Old Townhouse RoadWest Yarmouth, MA 02673United States of America
Inspector: Chad Benaka
Phone: (508) 398-6316
Fax:
Mobile:
Email: service@capecodalarm.com
System Control Unit
Manufacturer: DSC Inspection Date: 09/03/2026 IDC Style: E
Model Number: PC 4020CF Install Date: 06/03/2026 SLC Style: N/A
Software Version:Version Date: 12/31/1969 NAC Style: E
Location: Basement at bottom of the Stairs Disconnect Location:Disconnect Type:
Current Protection: Breaker
Monitoring
Company: Cape Cod Alarm Phone:Account #: S27130
Page of 3 14
Executive Summary
Cape Cod Alarm Download Date: 09/08/2026
Building: Lambrose Nikoladis
Contact: Lambrose Nikoladis
Company: Cape Cod Alarm
Inspector: Chad Benaka
Inspection Summary
Category
Total Items Serviced Passed Failed/Other
Qty %Qty %Qty %Qty %
Control 6 13.95%6 100.00%6 100.00%0 0.00%
Indicating 9 20.93%9 100.00%8 88.89%1 11.11%
Initiating 26 60.47%26 100.00%26 100.00%0 0.00%
Supervisory 2 4.65%2 100.00%2 100.00%0 0.00%
Totals 43 100%43 100.00%42 97.67%1 2.33%
Certification
Page of 4 14
Discrepancy Report
Cape Cod Alarm Download Date: 09/08/2026
Control Panel: 1 - DSC PC 4020CFBuilding: Lambrose Nikoladis
DISCREPANCY REPORT
Deficiency, Impairment, and Observation
Generated by: BuildingReports.com
The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where
appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a
manufacturer's replacement/upgrade program is included.
This section is now enhanced by BuildingReports AI, which helps refine applicable manufacturer recalls and replacement notices, enabling service providers and facilities to address potential issues more quickly.
Building: Lambrose Nikoladis
Items listed for Recall or Replacement/Upgrade
Device Type Manufacturer Model Number Date Qty
No recalled items found during this inspection.
Discrepancies
ScanID Location Problem Address Reference
INDICATING
Strobe
B9520302 Outside Main Entry Failed Operation 1 NFPA72
18.5.5.5.2;
18.5.5.6.7
Code References
NFPA72 18.5.5.5.2; 18.5.5.6.7 Rooms: Visual notification appliances shall be installed using one of the following: 1) A single visual notification appliance. 2) Two groups of visual notification appliances, where visual notification appliances of each group are synchronized, in the same room or adjacent space within the field of view. This shall include synchronization of visual appliances operated by separate systems. Corridors: In corridors where more than two visual notification appliances are in any field of view, they shall flash in synchronization.
Page of 5 14
Proposed Solutions Report
Cape Cod Alarm Download Date: 09/08/2026
Control Panel: 1 - DSC PC 4020CFBuilding: Lambrose Nikoladis
PROPOSED SOLUTIONS REPORT
Generated by: BuildingReports.com
The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark
where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials
basis.
ScanID Location Solution Model #Cost Fixed Date
INDICATING
Strobe
B9520302 Outside Main Entry Investigate/Replace SRK T/M
Customer WO/PO #:
(none)
Internal WO/PO #:
(none)
Total: T/M
Page of 6 14
Inspection & Testing
Cape Cod Alarm Download Date: 09/08/2026
Control Panel: 1 - DSC PC 4020CFBuilding: Lambrose Nikoladis
INSPECTION & TESTING
Generated by: BuildingReports.com
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other .
Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.
Device Type Location Service Time Date
PASSED
Control
Annunciator Basement Tested 12:26:47 PM 09/03/2026
Control Panel Basement at bottom of the Stairs Tested 12:19:03 PM 09/03/2026
Power Supply Basement at bottom of the Stairs Tested 12:18:28 PM 09/03/2026
Indicating
Horn/Strobe Basement at bottom of the Stairs Tested 12:18:09 PM 09/03/2026
Horn/Strobe Attic Tested 12:01:56 PM 09/03/2026
Mini-Horn 1st Floor Room 1 Tested 12:38:27 PM 09/03/2026
Mini-Horn 1st Floor Room 2 Tested 12:46:55 PM 09/03/2026
Mini-Horn 2nd Floor Room 3 Tested 1:01:14 PM 09/03/2026
Mini-Horn 2nd Floor Room 4 Tested 12:59:02 PM 09/03/2026
Mini-Horn 2nd Floor Room 5 Tested 12:54:13 PM 09/03/2026
Mini-Horn 2nd Floor Room 6 Tested 12:57:17 PM 09/03/2026
Initiating
CO Detector 1st Floor near Room 2 Tested 12:32:38 PM 09/03/2026
CO Detector 2nd Floor Hallway by Room 3 Tested 1:05:32 PM 09/03/2026
CO Detector 2nd Floor Hallway by Room 5 Tested 1:04:48 PM 09/03/2026
CO Detector Basement above Fire Alarm Control Panel Tested 12:08:48 PM 09/03/2026
CO Detector Attic Tested 12:00:04 PM 09/03/2026
Heat Detector 1st Floor Kitchen Tested 12:52:18 PM 09/03/2026
Page of 7 14
Inspection & Testing
Cape Cod Alarm Download Date: 09/08/2026
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
Pull Station 1st Floor Front Entry Door Tested 12:49:21 PM 09/03/2026
Pull Station 1st Floor Rear Entry Door Tested 12:34:40 PM 09/03/2026
Pull Station 2nd Floor Stairs to Attic Tested 1:03:26 PM 09/03/2026
Pull Station 2nd Floor at top of the Rear Stairs Tested 1:02:40 PM 09/03/2026
Pull Station Basement at bottom of the Stairs Tested 12:17:47 PM 09/03/2026
Pull Station Attic Tested 12:01:36 PM 09/03/2026
Smoke Detector 1st Floor Hallway by Room 2 Tested 12:37:14 PM 09/03/2026
Smoke Detector 1st Floor Hallway by Stairs Tested 12:48:08 PM 09/03/2026
Smoke Detector 1st Floor Room 1 Tested 12:38:00 PM 09/03/2026
Smoke Detector 1st Floor Room 2 Tested 12:46:33 PM 09/03/2026
Smoke Detector 2nd Floor Hallway by Room 5 Tested 1:04:29 PM 09/03/2026
Smoke Detector 2nd Floor Hallway by Stairs to Attic Tested 1:03:57 PM 09/03/2026
Smoke Detector 2nd Floor Room 3 Tested 1:01:02 PM 09/03/2026
Smoke Detector 2nd Floor Room 4 Tested 12:59:17 PM 09/03/2026
Smoke Detector 2nd Floor Room 5 Tested 12:54:31 PM 09/03/2026
Smoke Detector 2nd Floor Room 6 Tested 12:57:01 PM 09/03/2026
Smoke Detector Basement at bottom of the Stairs Tested 12:17:21 PM 09/03/2026
Smoke Detector Attic Side Room Tested 12:03:42 PM 09/03/2026
Smoke Detector Attic near Stairs Tested 12:02:42 PM 09/03/2026
Waterflow Switch Basement Tested 12:24:56 PM 09/03/2026
Supervisory
Tamper Switch Basement Tested 12:24:10 PM 09/03/2026
Tamper Switch Basement Tested 12:24:42 PM 09/03/2026
FAILED/OTHER
Indicating
Page of 8 14
Inspection & Testing
Cape Cod Alarm Download Date: 09/08/2026
Control Panel: 2Building: Lambrose Nikoladis
Device Type Location Service Time Date
FAILED/OTHER (continued)
Indicating (continued)
Strobe Outside Main Entry Tested 1:21:04 PM 09/03/2026
Device Type Location Service Time Date
PASSED
Control
Battery In Fire Alarm Control Panel Tested 12:19:35 PM 09/03/2026
Battery Inside Power Supply Tested 12:20:27 PM 09/03/2026
Battery Inside Power Supply Tested 12:21:04 PM 09/03/2026
Page of 9 14
Service Summary
Cape Cod Alarm Download Date: 09/08/2026
SERVICE SUMMARY
Generated by: BuildingReports.com
The Service Summary section provides an overview of the services performed in this report.
Building: Lambrose Nikoladis
Device Type Service Quantity
PASSED
Annunciator Tested 1
Battery, Sealed Lead Acid Tested 3
CO Detector Tested 5
Control Panel, Conventional Tested 1
Heat Detector, Hardwire - Combination Tested 1
Horn/Strobe Tested 2
Mini-Horn Tested 6
Power Supply Tested 1
Pull Station, Dual Action Tested 6
Smoke Detector Tested 13
Tamper Switch Tested 2
Waterflow Switch Tested 1
Total 42
FAILED/OTHER
Strobe Tested 1
Total 1
Grand Total 43
Page of 10 14
Sound and Visual Testing
Cape Cod Alarm Download Date: 09/08/2026
SOUND AND VISUAL TESTING
Generated by: BuildingReports.com
The Sound and Visual Testing section lists various points throughout your building where audible and visual alarm notification
devices were tested. Any bar-coded audible and visual devices will appear in the Inspection and Testing section of this report.
Items in this section are grouped by Passed or Failed/Other. Where specific decibel readings were recorded, they will appear
under the ambient and alarm columns. The Voice column indicates whether the Sound Test Point passed the Voice Intelligibility
requirements. The STI or Sound Transmission Index is shown if recorded.
Building: Lambrose Nikoladis
Audible/Visual Appliances
Location Comment Ambient Alarm Synched ScanID
PASSED
Horn/Strobe
Basement at bottom of the Stairs Passed ☐B9520263
Attic Passed ☐B9520266
FAILED/OTHER
Strobe
Outside Main Entry Failed Operation ☐B9520302
Page of 11 14
Battery & Power Supply Testing
Cape Cod Alarm Download Date: 09/08/2026
Control Panel: 2Building: Lambrose Nikoladis
BATTERY & POWER SUPPLY TESTING
Generated by: BuildingReports.com
The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to
provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Battery
Type Location
Rated
Ah
Rated
Volts
Pre
Test
Post
Test
Min
Ah
Teste
d Ah
MFG
Date
PASSED
Sealed Lead Acid In Fire Alarm Control Panel 7 12 100%100%09/03
/2026
Sealed Lead Acid Inside Power Supply 7 12 100%80%08/13
/2026
Sealed Lead Acid Inside Power Supply 7 12 100%80%08/13/2026
Page of 12 14
Inventory & Warranty Report
Cape Cod Alarm Download Date: 09/08/2026
Control Panel: 1 - DSC PC 4020CFBuilding: Lambrose Nikoladis
INVENTORY & WARRANTY REPORT
Generated by: BuildingReports.com
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete
inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices
installed for two years or more are grouped together for easy reference.
Building: Lambrose Nikoladis
Device or Type Category % of Inventory Quantity
Annunciator Control 2.33%1
Battery Control 6.98%3
CO Detector Initiating 11.63%5
Control Panel Control 2.33%1
Heat Detector Initiating 2.33%1
Horn/Strobe Indicating 4.65%2
Mini-Horn Indicating 13.95%6
Power Supply Control 2.33%1
Pull Station Initiating 13.95%6
Smoke Detector Initiating 30.23%13
Strobe Indicating 2.33%1
Tamper Switch Supervisory 4.65%2
Waterflow Switch Initiating 2.33%1
Type Qty Model #Description Install Date
NEW (UNDER 90 DAYS)
System Sensor
Strobe 1 SRK 09/03/2026
IN SERVICE - 90 DAYS - 1 YEAR
Page of 13 14
Inventory & Warranty Report
Cape Cod Alarm Download Date: 09/08/2026
Control Panel: 2Building: Lambrose Nikoladis
Type Qty Model #Description Install Date
IN SERVICE - 90 DAYS - 1 YEAR (continued)
DSC
Annunciator 1 06/03/2026
Control Panel 1 PC 4020CF Conventional 06/03/2026
Power Supply 1 PC4070 06/03/2026
Fire-Lite
Pull Station 6 BG-12 Dual Action 06/03/2026
Gentex
Mini-Horn 4 MHR 06/03/2026
Mini-Horn 2 MHW 06/03/2026
Potter
Waterflow Switch 1 VSC 06/03/2026
System Sensor
CO Detector 4 CO1224T 06/03/2026
CO Detector 1 CO1224T 11/03/2025
Horn/Strobe 2 P2R 06/03/2026
Smoke Detector 5 2WTA-B 06/03/2026
Smoke Detector 8 2WTB 06/03/2026
Victaulic
Tamper Switch 2 06/03/2026
IN SERVICE - 5 YEARS TO 10 YEARS
System Sensor
Heat Detector 1 5601P Hardwire - Combination 06/03/2020
Type Qty Model #Description Install Date
NEW (UNDER 90 DAYS)
Power Patrol
Page of 14 14
Inventory & Warranty Report
Cape Cod Alarm Download Date: 09/08/2026
Type Qty Model #Description Install Date
NEW (UNDER 90 DAYS)(continued)
Power Patrol (continued)
Battery 2 FAS1075 Sealed Lead Acid 08/13/2026
IN SERVICE - 90 DAYS - 1 YEAR
Power Patrol
Battery 1 FAS1075 Sealed Lead Acid 06/03/2026