HomeMy WebLinkAbout2026 FIRE ALARM INSPECTION BUILDING REPORT2026
173 Route 6A LLC
173 Main Street
Yarmouthport, MA 02675
(774)994-2149
Building Contact:Greg Bilezikian
Title:Contact
Company:Cape Cod Alarm
Contact:Marty Crowell
Title:Installer
Fire Alarm Systems
INSPECTIONCERTIFICATE
Sep 8, 2026Inspection Date:
Tested to NFPA 72 Standards
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed
ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Page of 2 10
Executive Summary
Cape Cod Alarm Download Date: 09/10/2026
EXECUTIVE SUMMARY
Generated by: BuildingReports.com
Building Information
173 Route 6A LLC
173 Main Street
Yarmouthport, MA 02675
United States of America
Contact: Greg Bilezikian
Phone: (781)987-3647
Fax:
Mobile:
Email:
Inspection Performed By
Cape Cod Alarm204 Old Townhouse RoadWest Yarmouth, MA 02673United States of America
Inspector: Marty Crowell
Phone: (508) 398-6316
Fax:
Mobile:
Email: service@capecodalarm.com
System Control Unit
Manufacturer: Silent Knight Inspection Date: 09/08/2026 IDC Style: E
Model Number: 5208 Install Date: 09/04/2024 SLC Style: N/A
Software Version:Version Date: 09/04/2024 NAC Style: E
Location: Basement at bottom of the Stairs Disconnect Location:Disconnect Type:
Current Protection: Breaker
Monitoring
Company: Cape Cod Alarm Phone: (508)398-6316 Account #: S27519
Central Station Signal Verification
Type: Cellular Mfg: Napco Model #: SLE-LTEV-FIRE
Test Time/Date: 9/8/26 3:12:26 PM Restore Time: 3:52 PM Note:
Type of Signal Signal Confirmed Time Notes
Trouble Signal 3:13 PM
Alarm Signal 3:14 PM
Page of 3 10
Executive Summary
Cape Cod Alarm Download Date: 09/10/2026
Building: 173 Route 6A LLC
Contact: Greg Bilezikian
Company: Cape Cod Alarm
Inspector: Marty Crowell
Inspection Summary
Category
Total Items Serviced Passed Failed/Other
Qty %Qty %Qty %Qty %
Control 6 21.43%6 100.00%6 100.00%0 0.00%
Indicating 7 25.00%7 100.00%7 100.00%0 0.00%
Initiating 13 46.43%13 100.00%13 100.00%0 0.00%
Monitor 2 7.14%2 100.00%2 100.00%0 0.00%
Totals 28 100%28 100.00%28 100.00%0 0.00%
Certification
Page of 4 10
Inspection & Testing
Cape Cod Alarm Download Date: 09/10/2026
Control Panel: 1 - Silent Knight 5208Building: 173 Route 6A LLC
INSPECTION & TESTING
Generated by: BuildingReports.com
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other .
Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.
Device Type Location Service Time Date
PASSED
Control
Battery Basement in Fire Alarm Control Panel Tested 3:12:20 PM 09/08/2026
Battery Basement in Fire Alarm Control Panel Tested 3:12:21 PM 09/08/2026
Battery Basement in Fire Alarm Control Panel (for Power Supply)Tested 3:38:19 PM 09/08/2026
Communicator Basement at bottom of the Stairs Tested 3:12:26 PM 09/08/2026
Control Panel Basement at bottom of the Stairs Tested 3:12:25 PM 09/08/2026
Power Supply Basement in Fire Alarm Control Panel Tested 3:12:33 PM 09/08/2026
Indicating
Horn/Strobe 1st Floor Kitchen Area by Rear Exit Tested 3:17:56 PM 09/08/2026
Horn/Strobe 1st Floor Retail Area Right Side Tested 3:20:14 PM 09/08/2026
Horn/Strobe 1st Floor Sitting Area Left Side Tested 3:22:33 PM 09/08/2026
Horn/Strobe 2nd Floor at top of Front Stairs Tested 3:21:24 PM 09/08/2026
Mini-Horn 2nd Floor Kitchen Tested 3:39:15 PM 09/08/2026
Mini-Horn Basement at bottom of the Stairs Tested 3:39:12 PM 09/08/2026
Strobe 1st Floor Restroom Tested 3:29:00 PM 09/08/2026
Initiating
Heat Detector 1st Floor Kitchen Oven Area(Up High)Tested 3:38:56 PM 09/08/2026
Heat Detector 1st Floor Kitchen Prep Area Tested 3:17:00 PM 09/08/2026
Heat Detector 1st Floor Kitchen Prep Area by Coolers Tested 3:38:53 PM 09/08/2026
Page of 5 10
Inspection & Testing
Cape Cod Alarm Download Date: 09/10/2026
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
Heat Detector 2nd Floor Hallway Tested 3:39:02 PM 09/08/2026
Pull Station 1st Floor Kitchen Area by Rear Exit Door Tested 3:17:58 PM 09/08/2026
Pull Station 1st Floor Retail Area Right Side Tested 3:20:22 PM 09/08/2026
Smoke Detector 1st Floor Retail Area Right Side Tested 3:20:09 PM 09/08/2026
Smoke Detector 1st Floor Sitting Area Left Side Tested 3:22:17 PM 09/08/2026
Smoke Detector 1st Floor at bottom of the Front Stairs Tested 3:21:01 PM 09/08/2026
Smoke Detector 2nd Floor at top of Front Stairs Tested 3:21:26 PM 09/08/2026
Smoke Detector 2nd Floor at top of Rear Stairs Tested 3:19:37 PM 09/08/2026
Smoke Detector Basement Storage Area Tested 3:16:00 PM 09/08/2026
Smoke Detector Basement at bottom of the Stairs Tested 3:12:39 PM 09/08/2026
Monitor
Monitoring Alarm Signal Tested 3:12:26 PM 09/08/2026
Monitoring Trouble Signal Tested 3:12:27 PM 09/08/2026
Page of 6 10
Service Summary
Cape Cod Alarm Download Date: 09/10/2026
SERVICE SUMMARY
Generated by: BuildingReports.com
The Service Summary section provides an overview of the services performed in this report.
Building: 173 Route 6A LLC
Device Type Service Quantity
PASSED
Battery, Sealed Lead Acid Tested 3
Communicator, Cellular Tested 1
Control Panel, Conventional Tested 1
Heat Detector, Combination Tested 3
Heat Detector, Fixed Temperature Tested 1
Horn/Strobe Tested 4
Mini-Horn Tested 2
Monitoring, Trouble Signal Tested 1
Monitoring, Alarm Signal Tested 1
Power Supply Tested 1
Pull Station, Dual Action Tested 2
Smoke Detector Tested 7
Strobe Tested 1
Total 28
Grand Total 28
Page of 7 10
Sound and Visual Testing
Cape Cod Alarm Download Date: 09/10/2026
SOUND AND VISUAL TESTING
Generated by: BuildingReports.com
The Sound and Visual Testing section lists various points throughout your building where audible and visual alarm notification
devices were tested. Any bar-coded audible and visual devices will appear in the Inspection and Testing section of this report.
Items in this section are grouped by Passed or Failed/Other. Where specific decibel readings were recorded, they will appear
under the ambient and alarm columns. The Voice column indicates whether the Sound Test Point passed the Voice Intelligibility
requirements. The STI or Sound Transmission Index is shown if recorded.
Building: 173 Route 6A LLC
Audible/Visual Appliances
Location Comment Ambient Alarm Synched ScanID
PASSED
Horn/Strobe
1st Floor Sitting Area Left Side Passed ☐98926083
1st Floor Retail Area Right Side Passed ☐98926149
1st Floor Kitchen Area by Rear
Exit
Passed ☐98926157
2nd Floor at top of Front Stairs Passed ☐98926159
Strobe
1st Floor Restroom Passed ☐98926079
Page of 8 10
Battery & Power Supply Testing
Cape Cod Alarm Download Date: 09/10/2026
Control Panel: 1 - Silent Knight 5208Building: 173 Route 6A LLC
BATTERY & POWER SUPPLY TESTING
Generated by: BuildingReports.com
The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to
provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Battery
Type Location
Rated
Ah
Rated
Volts
Pre
Test
Post
Test
Min
Ah
Teste
d Ah
MFG
Date
PASSED
Sealed Lead Acid Basement in Fire Alarm Control
Panel
7 12 100 80 09/04
/2024
Sealed Lead Acid Basement in Fire Alarm Control
Panel
7 12 100 80 09/04
/2024
Sealed Lead Acid Basement in Fire Alarm Control Panel (for Power Supply)7 12 100 80 09/04/2024
Page of 9 10
Inventory & Warranty Report
Cape Cod Alarm Download Date: 09/10/2026
Control Panel: 1 - Silent Knight 5208Building: 173 Route 6A LLC
INVENTORY & WARRANTY REPORT
Generated by: BuildingReports.com
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete
inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices
installed for two years or more are grouped together for easy reference.
Building: 173 Route 6A LLC
Device or Type Category % of Inventory Quantity
Battery Control 10.71%3
Communicator Control 3.57%1
Control Panel Control 3.57%1
Heat Detector Initiating 14.29%4
Horn/Strobe Indicating 14.29%4
Mini-Horn Indicating 7.14%2
Monitoring Monitor 7.14%2
Power Supply Control 3.57%1
Pull Station Initiating 7.14%2
Smoke Detector Initiating 25.00%7
Strobe Indicating 3.57%1
Type Qty Model #Description Install Date
IN SERVICE - 2 YEARS TO 3 YEARS
Elk
Power Supply 1 624 09/04/2024
Gentex
Mini-Horn 2 MHW 09/04/2024
Napco
Communicator 1 SLE-LTEV-FIRE Cellular 09/04/2024
Page of 10 10
Inventory & Warranty Report
Cape Cod Alarm Download Date: 09/10/2026
Type Qty Model #Description Install Date
IN SERVICE - 2 YEARS TO 3 YEARS (continued)
Power Patrol
Battery 1 FAS1055 Sealed Lead Acid 09/04/2024
Battery 2 FAS1075 Sealed Lead Acid 09/04/2024
Silent Knight
Control Panel 1 5208 Conventional 09/04/2024
Pull Station 2 PS-DATK Dual Action 09/04/2024
System Sensor
Horn/Strobe 3 P2R 09/04/2024
Horn/Strobe 1 PC2WL 09/04/2024
Smoke Detector 7 2WT-B 09/04/2024
Strobe 1 SR 09/04/2024
(manufacturer not specified)
Monitoring 1 Alarm Signal 09/04/2024
Monitoring 1 Trouble Signal 09/04/2024
IN SERVICE - 5 YEARS TO 10 YEARS
System Sensor
Heat Detector 3 5601P Combination 09/04/2019
Heat Detector 1 5604 Fixed Temperature 09/04/2019