Loading...
HomeMy WebLinkAbout792-792-20658 Norfolk Ave, Easton, MA 02375 • Tel 508 822 6934 • www.swcole.com Report of Concrete Compressive Strength ASTM C31, ASTM C39, ASTM C1231 Project Name:Yarmouth MA - Town of Yarmouth Water Resource Recovery Facility - Concrete Testing Services Client:Wright-Pierce Project #:25-0468 Report Date:9/22/2026 Concrete Supplier:Cape Cod Ready Mix PLACEMENT INFORMATION Date Cast: 9/15/2026 Time Cast: 7:00 AM Date Received: 9/16/2026 Placement Location:STAIRCASE & BEAM & WALKWAYS & EXTERIOR WALL Placement Method:Pump Cylinders Made By:Henry Among Material Type:Concrete Cylinders Placement Vol. (yd ): Aggregate Size (in):3/4 Cylinder Size:4" x 8" INITIAL CURING CONDITION DELIVERY INFORMATION Temperatures Minimum (°F):Maximum (°F): Admixtures: TEST RESULTS Slump (in) (C-143):5 Air Content (%) (C-231):3 Air Temp (°F):72 Conc. Temp (°F) (C-1064):70 Load Number:1 Mixer Num.:83 Ticket Num.:193504 Cubic Yards:10 Design (psi):4500 Batch 5:19 AM Arrive Depart Cylinder Designation Defect (Y/N) Cylinder Weight (lbs) Cylinder Diameter (in) Cross Sectional Area (in ) Date Of Test Cure Type Cap Type Age (Days) Fracture Type Load (kips) Strength (psi) 792-206A N 8.65 3.98 12.41 9/22/2026 Lab Unbonded 7 5 72.56 5830 792-206B 8.6 9/29/2026 Lab 14 792-206C 8.6 10/13/2026 Lab 28 792-206D 8.65 10/13/2026 Lab 28 792-206E 8.6 10/13/2026 Lab 28 792-206F 8.65 HOLD Lab 3 2 Remarks:Kaylie O'Sullivan Reviewed By