HomeMy WebLinkAbout2026 FIRE ALARM INSPECTION BUILDING REPORT2026
Charles White Management
12 Beatrice Lane
West Yarmouth, MA 02673
(508)889-1445
Building Contact:George Deraleau
Title:Contact
Company:Cape Cod Alarm
Contact:Marty Crowell
Title:Installer
Fire Alarm Systems
INSPECTIONCERTIFICATE
Sep 21, 2026Inspection Date:
Tested to NFPA 72 Standards
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed
ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Page of 2 10
Executive Summary
Cape Cod Alarm Download Date: 09/25/2026
EXECUTIVE SUMMARY
Generated by: BuildingReports.com
Building Information
Charles White Management
12 Beatrice Lane
West Yarmouth, MA 02673
United States of America
Contact: George Deraleau
Phone: (508)889-1445
Fax:
Mobile:
Email:
Inspection Performed By
Cape Cod Alarm204 Old Townhouse RoadWest Yarmouth, MA 02673United States of America
Inspector: Marty Crowell
Phone: (508) 398-6316
Fax:
Mobile:
Email: service@capecodalarm.com
System Control Unit
Manufacturer: Silent Knight Inspection Date: 09/21/2026 IDC Style: E
Model Number: SK-4 Install Date: 06/01/2017 SLC Style: N/A
Software Version:Version Date: 05/06/2022 NAC Style: E
Location: 1st Floor Utility Closet Disconnect Location:Disconnect Type:
Current Protection: Breaker
Monitoring
Company: Cape Cod Alarm Phone: (508)398-6316 Account #: S24797
Central Station Signal Verification
Type: Mesh Radio Network Mfg: AES Model #: 7788F
Test Time/Date: 9/21/26 1:01:35 PM Restore Time: 1:07 PM Note:
Type of Signal Signal Confirmed Time Notes
Alarm Signal 1:00 PM
Trouble Signal
Page of 3 10
Executive Summary
Cape Cod Alarm Download Date: 09/25/2026
Building: Charles White Management
Contact: George Deraleau
Company: Cape Cod Alarm
Inspector: Marty Crowell
Type of Signal (continued)Signal Confirmed Time Notes
Supervisory Signal 1:02 PM
Inspection Summary
Category
Total Items Serviced Passed Failed/Other
Qty %Qty %Qty %Qty %
Control 5 41.67%5 100.00%5 100.00%0 0.00%
Indicating 1 8.33%1 100.00%0 0.00%1 100.00%
Initiating 1 8.33%1 100.00%1 100.00%0 0.00%
Monitor 3 25.00%3 100.00%3 100.00%0 0.00%
Supervisory 2 16.67%0 0.00%0 0.00%0 0.00%
Totals 12 100%10 83.33%9 90.00%1 10.00%
Certification
Page of 4 10
Discrepancy Report
Cape Cod Alarm Download Date: 09/25/2026
Control Panel: 1 - Silent Knight SK-4Building: Charles White Management
DISCREPANCY REPORT
Deficiency, Impairment, and Observation
Generated by: BuildingReports.com
The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where
appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a
manufacturer's replacement/upgrade program is included.
This section is now enhanced by BuildingReports AI, which helps refine applicable manufacturer recalls and replacement notices, enabling service providers and facilities to address potential issues more quickly.
Building: Charles White Management
Items listed for Recall or Replacement/Upgrade
Device Type Manufacturer Model Number Date Qty
No recalled items found during this inspection.
Discrepancies
ScanID Location Problem Address Reference
INDICATING
Beacon
76584181 Outside of Unit (Up High)Failed Test 1 NFPA72
14.2.2.2.2
Code References
NFPA72 14.2.2.2.2 System deficiencies shall be corrected.
Page of 5 10
Proposed Solutions Report
Cape Cod Alarm Download Date: 09/25/2026
Control Panel: 1 - Silent Knight SK-4Building: Charles White Management
PROPOSED SOLUTIONS REPORT
Generated by: BuildingReports.com
The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark
where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials
basis.
ScanID Location Solution Model #Cost Fixed Date
INDICATING
Beacon
76584181 Outside of Unit (Up High)Replace T/M
Customer WO/PO #:
(none)
Internal WO/PO #:
(none)
Total: T/M
Page of 6 10
Inspection & Testing
Cape Cod Alarm Download Date: 09/25/2026
Control Panel: 1 - Silent Knight SK-4Building: Charles White Management
INSPECTION & TESTING
Generated by: BuildingReports.com
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other .
Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.
Device Type Location Service Time Date
PASSED
Control
Battery 1st Floor Utility Closet inside AES Tested 1:01:31 PM 09/21/2026
Battery 1st Floor Utility Closet inside FACP Tested 1:01:05 PM 09/21/2026
Battery 1st Floor Utility Closet inside FACP Tested 1:01:06 PM 09/21/2026
Communicator 1st Floor Utility Closet Tested 1:01:35 PM 09/21/2026
Control Panel 1st Floor Utility Closet Tested 1:03:26 PM 09/21/2026
Initiating
Waterflow Switch 1st Floor Utility Closet Tested 1:01:12 PM 09/21/2026
Monitor
Monitoring Alarm Signal Tested 1:01:33 PM 09/21/2026
Monitoring Supervisory Signal Tested 1:01:34 PM 09/21/2026
Monitoring Trouble Signal Tested 1:01:33 PM 09/21/2026
FAILED/OTHER
Indicating
Beacon Outside of Unit (Up High)Tested 1:03:34 PM 09/21/2026
UNTESTED
Supervisory
Tamper Switch 1st Floor Utility Closet
Tamper Switch 1st Floor Utility Closet
Page of 7 10
Service Summary
Cape Cod Alarm Download Date: 09/25/2026
SERVICE SUMMARY
Generated by: BuildingReports.com
The Service Summary section provides an overview of the services performed in this report.
Building: Charles White Management
Device Type Service Quantity
PASSED
Battery, Sealed Lead Acid Tested 3
Communicator, Mesh Radio Network Tested 1
Control Panel, Conventional Tested 1
Monitoring, Alarm Signal Tested 1
Monitoring, Trouble Signal Tested 1
Monitoring, Supervisory Signal Tested 1
Waterflow Switch Tested 1
Total 9
FAILED/OTHER
Beacon Tested 1
Total 1
UNTESTED
Tamper Switch 2
Total 2
Grand Total 12
Page of 8 10
Battery & Power Supply Testing
Cape Cod Alarm Download Date: 09/25/2026
Control Panel: 1 - Silent Knight SK-4Building: Charles White Management
BATTERY & POWER SUPPLY TESTING
Generated by: BuildingReports.com
The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to
provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Battery
Type Location
Rated
Ah
Rated
Volts
Pre
Test
Post
Test
Min
Ah
Teste
d Ah
MFG
Date
PASSED
Sealed Lead Acid 1st Floor Utility Closet inside AES 7 12 100 80 04/16
/2024
Sealed Lead Acid 1st Floor Utility Closet inside FACP 7 12 100 80 04/16
/2024
Sealed Lead Acid 1st Floor Utility Closet inside FACP 7 12 100 90 04/16/2024
Page of 9 10
Inventory & Warranty Report
Cape Cod Alarm Download Date: 09/25/2026
Control Panel: 1 - Silent Knight SK-4Building: Charles White Management
INVENTORY & WARRANTY REPORT
Generated by: BuildingReports.com
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete
inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices
installed for two years or more are grouped together for easy reference.
Building: Charles White Management
Device or Type Category % of Inventory Quantity
Battery Control 25.00%3
Beacon Indicating 8.33%1
Communicator Control 8.33%1
Control Panel Control 8.33%1
Monitoring Monitor 25.00%3
Tamper Switch Supervisory 16.67%2
Waterflow Switch Initiating 8.33%1
Type Qty Model #Description Install Date
IN SERVICE - 2 YEARS TO 3 YEARS
Power Patrol
Battery 3 FAS1075 Sealed Lead Acid 04/16/2024
IN SERVICE - 5 YEARS TO 10 YEARS
AES
Communicator 1 7788F Mesh Radio Network 05/01/2017
Monitoring 1 7788F Alarm Signal 05/01/2017
Monitoring 1 7788F Supervisory Signal 05/01/2017
Monitoring 1 7788F Trouble Signal 05/01/2017
Edwards
Beacon 1 06/01/2017
Page of 10 10
Inventory & Warranty Report
Cape Cod Alarm Download Date: 09/25/2026
Type Qty Model #Description Install Date
IN SERVICE - 5 YEARS TO 10 YEARS (continued)
Landsdale
Tamper Switch 2 06/01/2017
Silent Knight
Control Panel 1 SK-4 Conventional 06/01/2017
System Sensor
Waterflow Switch 1 WFDTH 06/01/2017