Loading...
HomeMy WebLinkAbout2026 FIRE ALARM INSPECTION BUILDING REPORT2026 Charles White Management 12 Beatrice Lane West Yarmouth, MA 02673 (508)889-1445 Building Contact:George Deraleau Title:Contact Company:Cape Cod Alarm Contact:Marty Crowell Title:Installer Fire Alarm Systems INSPECTIONCERTIFICATE Sep 21, 2026Inspection Date: Tested to NFPA 72 Standards This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval. Page of 2 10 Executive Summary Cape Cod Alarm Download Date: 09/25/2026 EXECUTIVE SUMMARY Generated by: BuildingReports.com Building Information Charles White Management 12 Beatrice Lane West Yarmouth, MA 02673 United States of America Contact: George Deraleau Phone: (508)889-1445 Fax: Mobile: Email: Inspection Performed By Cape Cod Alarm204 Old Townhouse RoadWest Yarmouth, MA 02673United States of America Inspector: Marty Crowell Phone: (508) 398-6316 Fax: Mobile: Email: service@capecodalarm.com System Control Unit Manufacturer: Silent Knight Inspection Date: 09/21/2026 IDC Style: E Model Number: SK-4 Install Date: 06/01/2017 SLC Style: N/A Software Version:Version Date: 05/06/2022 NAC Style: E Location: 1st Floor Utility Closet Disconnect Location:Disconnect Type: Current Protection: Breaker Monitoring Company: Cape Cod Alarm Phone: (508)398-6316 Account #: S24797 Central Station Signal Verification Type: Mesh Radio Network Mfg: AES Model #: 7788F Test Time/Date: 9/21/26 1:01:35 PM Restore Time: 1:07 PM Note: Type of Signal Signal Confirmed Time Notes Alarm Signal 1:00 PM Trouble Signal Page of 3 10 Executive Summary Cape Cod Alarm Download Date: 09/25/2026 Building: Charles White Management Contact: George Deraleau Company: Cape Cod Alarm Inspector: Marty Crowell Type of Signal (continued)Signal Confirmed Time Notes Supervisory Signal 1:02 PM Inspection Summary Category Total Items Serviced Passed Failed/Other Qty %Qty %Qty %Qty % Control 5 41.67%5 100.00%5 100.00%0 0.00% Indicating 1 8.33%1 100.00%0 0.00%1 100.00% Initiating 1 8.33%1 100.00%1 100.00%0 0.00% Monitor 3 25.00%3 100.00%3 100.00%0 0.00% Supervisory 2 16.67%0 0.00%0 0.00%0 0.00% Totals 12 100%10 83.33%9 90.00%1 10.00% Certification Page of 4 10 Discrepancy Report Cape Cod Alarm Download Date: 09/25/2026 Control Panel: 1 - Silent Knight SK-4Building: Charles White Management DISCREPANCY REPORT Deficiency, Impairment, and Observation Generated by: BuildingReports.com The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection. Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included. This section is now enhanced by BuildingReports AI, which helps refine applicable manufacturer recalls and replacement notices, enabling service providers and facilities to address potential issues more quickly. Building: Charles White Management Items listed for Recall or Replacement/Upgrade Device Type Manufacturer Model Number Date Qty No recalled items found during this inspection. Discrepancies ScanID Location Problem Address Reference INDICATING Beacon 76584181 Outside of Unit (Up High)Failed Test 1 NFPA72 14.2.2.2.2 Code References NFPA72 14.2.2.2.2 System deficiencies shall be corrected. Page of 5 10 Proposed Solutions Report Cape Cod Alarm Download Date: 09/25/2026 Control Panel: 1 - Silent Knight SK-4Building: Charles White Management PROPOSED SOLUTIONS REPORT Generated by: BuildingReports.com The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis. ScanID Location Solution Model #Cost Fixed Date INDICATING Beacon 76584181 Outside of Unit (Up High)Replace T/M Customer WO/PO #: (none) Internal WO/PO #: (none) Total: T/M Page of 6 10 Inspection & Testing Cape Cod Alarm Download Date: 09/25/2026 Control Panel: 1 - Silent Knight SK-4Building: Charles White Management INSPECTION & TESTING Generated by: BuildingReports.com The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other . Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred. Device Type Location Service Time Date PASSED Control Battery 1st Floor Utility Closet inside AES Tested 1:01:31 PM 09/21/2026 Battery 1st Floor Utility Closet inside FACP Tested 1:01:05 PM 09/21/2026 Battery 1st Floor Utility Closet inside FACP Tested 1:01:06 PM 09/21/2026 Communicator 1st Floor Utility Closet Tested 1:01:35 PM 09/21/2026 Control Panel 1st Floor Utility Closet Tested 1:03:26 PM 09/21/2026 Initiating Waterflow Switch 1st Floor Utility Closet Tested 1:01:12 PM 09/21/2026 Monitor Monitoring Alarm Signal Tested 1:01:33 PM 09/21/2026 Monitoring Supervisory Signal Tested 1:01:34 PM 09/21/2026 Monitoring Trouble Signal Tested 1:01:33 PM 09/21/2026 FAILED/OTHER Indicating Beacon Outside of Unit (Up High)Tested 1:03:34 PM 09/21/2026 UNTESTED Supervisory Tamper Switch 1st Floor Utility Closet Tamper Switch 1st Floor Utility Closet Page of 7 10 Service Summary Cape Cod Alarm Download Date: 09/25/2026 SERVICE SUMMARY Generated by: BuildingReports.com The Service Summary section provides an overview of the services performed in this report. Building: Charles White Management Device Type Service Quantity PASSED Battery, Sealed Lead Acid Tested 3 Communicator, Mesh Radio Network Tested 1 Control Panel, Conventional Tested 1 Monitoring, Alarm Signal Tested 1 Monitoring, Trouble Signal Tested 1 Monitoring, Supervisory Signal Tested 1 Waterflow Switch Tested 1 Total 9 FAILED/OTHER Beacon Tested 1 Total 1 UNTESTED Tamper Switch 2 Total 2 Grand Total 12 Page of 8 10 Battery & Power Supply Testing Cape Cod Alarm Download Date: 09/25/2026 Control Panel: 1 - Silent Knight SK-4Building: Charles White Management BATTERY & POWER SUPPLY TESTING Generated by: BuildingReports.com The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other. Battery Type Location Rated Ah Rated Volts Pre Test Post Test Min Ah Teste d Ah MFG Date PASSED Sealed Lead Acid 1st Floor Utility Closet inside AES 7 12 100 80 04/16 /2024 Sealed Lead Acid 1st Floor Utility Closet inside FACP 7 12 100 80 04/16 /2024 Sealed Lead Acid 1st Floor Utility Closet inside FACP 7 12 100 90 04/16/2024 Page of 9 10 Inventory & Warranty Report Cape Cod Alarm Download Date: 09/25/2026 Control Panel: 1 - Silent Knight SK-4Building: Charles White Management INVENTORY & WARRANTY REPORT Generated by: BuildingReports.com The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference. Building: Charles White Management Device or Type Category % of Inventory Quantity Battery Control 25.00%3 Beacon Indicating 8.33%1 Communicator Control 8.33%1 Control Panel Control 8.33%1 Monitoring Monitor 25.00%3 Tamper Switch Supervisory 16.67%2 Waterflow Switch Initiating 8.33%1 Type Qty Model #Description Install Date IN SERVICE - 2 YEARS TO 3 YEARS Power Patrol Battery 3 FAS1075 Sealed Lead Acid 04/16/2024 IN SERVICE - 5 YEARS TO 10 YEARS AES Communicator 1 7788F Mesh Radio Network 05/01/2017 Monitoring 1 7788F Alarm Signal 05/01/2017 Monitoring 1 7788F Supervisory Signal 05/01/2017 Monitoring 1 7788F Trouble Signal 05/01/2017 Edwards Beacon 1 06/01/2017 Page of 10 10 Inventory & Warranty Report Cape Cod Alarm Download Date: 09/25/2026 Type Qty Model #Description Install Date IN SERVICE - 5 YEARS TO 10 YEARS (continued) Landsdale Tamper Switch 2 06/01/2017 Silent Knight Control Panel 1 SK-4 Conventional 06/01/2017 System Sensor Waterflow Switch 1 WFDTH 06/01/2017