Gerardi's Café
902 Main Street (Route 28)
South Yarmouth, MA 02664
(508)394-3111
Building Contact:Sasha Gerardi
Title:Contact
Company:Cape Cod Alarm
Contact:Marty Crowell
Title:Installer
Fire Alarm Systems
INSPECTIONCERTIFICATE
Sep 24, 2026Inspection Date:
Tested to NFPA 72 Standards
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed
ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Page of 2 10
Executive Summary
Cape Cod Alarm Download Date: 09/29/2026
EXECUTIVE SUMMARY
Generated by: BuildingReports.com
Building Information
Gerardi's Café
902 Main Street (Route 28)
South Yarmouth, MA 02664
United States of America
Contact: Sasha Gerardi
Phone: (508)394-3111
Fax:
Mobile:
Email:
Inspection Performed By
Cape Cod Alarm204 Old Townhouse RoadWest Yarmouth, MA 02673United States of America
Inspector: Marty Crowell
Phone: (508) 398-6316
Fax:
Mobile:
Email: service@capecodalarm.com
System Control Unit
Manufacturer: Mircom Inspection Date: 09/24/2026 IDC Style: E
Model Number: FA 300 Install Date: 09/05/2018 SLC Style: N/A
Software Version:Version Date: 09/05/2018 NAC Style: E
Location: 1st Floor Electric/Boiler Room Disconnect Location:Disconnect Type:
Current Protection: Breaker
Monitoring
Company: Cape Cod Alarm Phone: (508)398-6316 Account #: S60145
Central Station Signal Verification
Type: Digital Communicator Mfg: Mircom Model #: FA 300
Test Time/Date: 9/24/26 9:51:18 AM Restore Time: 10:03 AM Note:
Type of Signal Signal Confirmed Time Notes
Trouble Signal 9:57 AM
Alarm Signal 9:55 AM
Page of 3 10
Executive Summary
Cape Cod Alarm Download Date: 09/29/2026
Building: Gerardi's Café
Contact: Sasha Gerardi
Company: Cape Cod Alarm
Inspector: Marty Crowell
Inspection Summary
Category
Total Items Serviced Passed Failed/Other
Qty %Qty %Qty %Qty %
Alarm 1 4.76%1 100.00%1 100.00%0 0.00%
Control 6 28.57%6 100.00%6 100.00%0 0.00%
Indicating 5 23.81%5 100.00%5 100.00%0 0.00%
Initiating 7 33.33%7 100.00%7 100.00%0 0.00%
Monitor 2 9.52%2 100.00%2 100.00%0 0.00%
Totals 21 100%21 100.00%21 100.00%0 0.00%
Certification
Page of 4 10
Inspection & Testing
Cape Cod Alarm Download Date: 09/29/2026
Control Panel: 1 - Mircom FA 300Building: Gerardi's Café
INSPECTION & TESTING
Generated by: BuildingReports.com
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other .
Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.
Device Type Location Service Time Date
PASSED
Alarm
Kitchen Hood 1st Floor Kitchen Tested 10:02:45 AM 09/24/2026
Control
Battery 1st Floor in Fire Alarm Control Panel Tested 9:51:13 AM 09/24/2026
Battery 1st Floor in Fire Alarm Control Panel Tested 9:51:15 AM 09/24/2026
Communicator 1st Floor Electric/Boiler Room Tested 9:51:18 AM 09/24/2026
Control Panel 1st Floor Electric/Boiler Room Tested 9:51:16 AM 09/24/2026
Phone Jack 1st Floor in Fire Alarm Control Panel Tested 9:59:46 AM 09/24/2026
Phone Jack 1st Floor in Fire Alarm Control Panel Tested 9:59:50 AM 09/24/2026
Indicating
Horn/Strobe 1st Floor Back Kitchen Door Tested 9:58:35 AM 09/24/2026
Horn/Strobe 1st Floor Front Door Tested 9:57:41 AM 09/24/2026
Horn/Strobe 1st Floor Side Door Tested 9:56:00 AM 09/24/2026
Strobe 1st Floor Men’s Room Tested 9:51:49 AM 09/24/2026
Strobe 1st Floor Women’s Room Tested 9:52:02 AM 09/24/2026
Initiating
Heat Detector 1st Floor Kitchen Tested 10:02:41 AM 09/24/2026
Heat Detector 1st Floor outside Walk In Refrigerator Tested 10:02:37 AM 09/24/2026
Pull Station 1st Floor Back Kitchen Door Tested 9:58:33 AM 09/24/2026
Pull Station 1st Floor Front Door Tested 9:57:42 AM 09/24/2026
Page of 5 10
Inspection & Testing
Cape Cod Alarm Download Date: 09/29/2026
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
Pull Station 1st Floor Side Door Tested 9:55:55 AM 09/24/2026
Smoke Detector 1st Floor Dining Room Side Exit Tested 9:52:44 AM 09/24/2026
Smoke Detector 1st Floor Hallway to Kitchen Tested 9:52:32 AM 09/24/2026
Monitor
Monitoring Alarm Signal Tested 9:51:19 AM 09/24/2026
Monitoring Trouble Signal Tested 9:51:17 AM 09/24/2026
Page of 6 10
Service Summary
Cape Cod Alarm Download Date: 09/29/2026
SERVICE SUMMARY
Generated by: BuildingReports.com
The Service Summary section provides an overview of the services performed in this report.
Building: Gerardi's Café
Device Type Service Quantity
PASSED
Battery, Sealed Lead Acid Tested 2
Communicator, Digital Communicator Tested 1
Control Panel Tested 1
Heat Detector, Fixed Temperature Tested 2
Horn/Strobe Tested 3
Kitchen Hood Tested 1
Monitoring, Trouble Signal Tested 1
Monitoring, Alarm Signal Tested 1
Phone Jack Tested 2
Pull Station, Dual Action Tested 3
Smoke Detector Tested 2
Strobe Tested 2
Total 21
Grand Total 21
Page of 7 10
Sound and Visual Testing
Cape Cod Alarm Download Date: 09/29/2026
SOUND AND VISUAL TESTING
Generated by: BuildingReports.com
The Sound and Visual Testing section lists various points throughout your building where audible and visual alarm notification
devices were tested. Any bar-coded audible and visual devices will appear in the Inspection and Testing section of this report.
Items in this section are grouped by Passed or Failed/Other. Where specific decibel readings were recorded, they will appear
under the ambient and alarm columns. The Voice column indicates whether the Sound Test Point passed the Voice Intelligibility
requirements. The STI or Sound Transmission Index is shown if recorded.
Building: Gerardi's Café
Audible/Visual Appliances
Location Comment Ambient Alarm Synched ScanID
PASSED
Horn/Strobe
1st Floor Front Door Passed ☐48947355
1st Floor Back Kitchen Door Passed ☐48947359
1st Floor Side Door Passed ☐98926504
Strobe
1st Floor Women’s Room Passed ☐48947364
1st Floor Men’s Room Passed ☐48947365
Page of 8 10
Battery & Power Supply Testing
Cape Cod Alarm Download Date: 09/29/2026
Control Panel: 1 - Mircom FA 300Building: Gerardi's Café
BATTERY & POWER SUPPLY TESTING
Generated by: BuildingReports.com
The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to
provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Battery
Type Location
Rated
Ah
Rated
Volts
Pre
Test
Post
Test
Min
Ah
Teste
d Ah
MFG
Date
PASSED
Sealed Lead Acid 1st Floor in Fire Alarm Control
Panel
7 12 100 80 09/19
/2024
Sealed Lead Acid 1st Floor in Fire Alarm Control
Panel
7 12 100 80 09/19
/2024
Page of 9 10
Inventory & Warranty Report
Cape Cod Alarm Download Date: 09/29/2026
Control Panel: 1 - Mircom FA 300Building: Gerardi's Café
INVENTORY & WARRANTY REPORT
Generated by: BuildingReports.com
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete
inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices
installed for two years or more are grouped together for easy reference.
Building: Gerardi's Café
Device or Type Category % of Inventory Quantity
Battery Control 9.52%2
Communicator Control 4.76%1
Control Panel Control 4.76%1
Heat Detector Initiating 9.52%2
Horn/Strobe Indicating 14.29%3
Kitchen Hood Alarm 4.76%1
Monitoring Monitor 9.52%2
Phone Jack Control 9.52%2
Pull Station Initiating 14.29%3
Smoke Detector Initiating 9.52%2
Strobe Indicating 9.52%2
Type Qty Model #Description Install Date
IN SERVICE - 2 YEARS TO 3 YEARS
Power Patrol
Battery 2 FAS1075 Sealed Lead Acid 09/19/2024
System Sensor
Heat Detector 1 5604 Fixed Temperature 09/19/2024
Horn/Strobe 1 P2RL-LF 09/19/2024
Page of 10 10
Inventory & Warranty Report
Cape Cod Alarm Download Date: 09/29/2026
Type Qty Model #Description Install Date
IN SERVICE - 5 YEARS TO 10 YEARS
Badger
Kitchen Hood 1 Ansul Trip 09/05/2018
Fire-Lite
Pull Station 1 BG-12 Dual Action 09/05/2018
Firelite
Pull Station 2 BG-12 Dual Action 09/05/2018
Mircom
Communicator 1 FA 300 Digital Communicator 09/05/2018
Control Panel 1 FA 300 09/05/2018
System Sensor
Heat Detector 1 5604 Fixed Temperature 09/05/2017
Smoke Detector 2 2WTB 09/05/2018
Wheelock
Horn/Strobe 2 NS-121575W-FW 09/05/2018
Strobe 2 RSS-121575W-FW 09/05/2018
(manufacturer not specified)
Monitoring 1 Alarm Signal 09/05/2018
Monitoring 1 Trouble Signal 09/05/2018
Phone Jack 2 09/05/2018