HomeMy WebLinkAbout2026 FIRE ALARM INSPECTION BUILDING REPORT2026
Hearth N' Kettle
1196 Route 28
South Yarmouth, MA 02664
(508)394-2252
Building Contact:Fabio Lima
Title:Contact
Company:Cape Cod Alarm
Contact:Marty Crowell
Title:Installer
Fire Alarm Systems
INSPECTIONCERTIFICATE
Oct 15, 2026Inspection Date:
Tested to NFPA 72 Standards
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed
ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Page of 2 12
Executive Summary
Cape Cod Alarm Download Date: 10/16/2026
EXECUTIVE SUMMARY
Generated by: BuildingReports.com
Building Information
Hearth N' Kettle
1196 Route 28
South Yarmouth, MA 02664
United States of America
Contact: Fabio Lima
Phone: (508)394-2252
Fax:
Mobile:
Email:
Inspection Performed By
Cape Cod Alarm204 Old Townhouse RoadWest Yarmouth, MA 02673United States of America
Inspector: Marty Crowell
Phone: (508) 398-6316
Fax:
Mobile:
Email: service@capecodalarm.com
System Control Unit
Manufacturer: Fire-Lite Inspection Date: 10/15/2026 IDC Style: E
Model Number: MS-10UD Install Date: 10/15/2026 SLC Style: N/A
Software Version:Version Date: 10/15/2026 NAC Style: E
Location: Kitchen Area Rear Door Disconnect Location:Disconnect Type:
Current Protection: Breaker
Monitoring
Company: Cape Cod Alarm Phone:Account #: S29192
Central Station Signal Verification
Type: Mesh Radio Network Mfg: AES Model #: 7788F
Test Time/Date: 10/15/26 3:28:35 PM Restore Time: 4:13 PM Note:
Type of Signal Signal Confirmed Time Notes
Alarm Signal 3:36 PM
Trouble Signal 3:37 PM
Page of 3 12
Executive Summary
Cape Cod Alarm Download Date: 10/16/2026
Building: Hearth N' Kettle
Contact: Fabio Lima
Company: Cape Cod Alarm
Inspector: Marty Crowell
Inspection Summary
Category
Total Items Serviced Passed Failed/Other
Qty %Qty %Qty %Qty %
Alarm 1 3.45%1 100.00%1 100.00%0 0.00%
Control 6 20.69%6 100.00%6 100.00%0 0.00%
Indicating 8 27.59%8 100.00%8 100.00%0 0.00%
Initiating 12 41.38%12 100.00%8 66.67%4 33.33%
Monitor 2 6.90%2 100.00%2 100.00%0 0.00%
Totals 29 100%29 100.00%25 86.21%4 13.79%
Certification
Page of 4 12
Discrepancy Report
Cape Cod Alarm Download Date: 10/16/2026
Control Panel: 1 - Fire-Lite MS-10UDBuilding: Hearth N' Kettle
DISCREPANCY REPORT
Deficiency, Impairment, and Observation
Generated by: BuildingReports.com
The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where
appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a
manufacturer's replacement/upgrade program is included.
This section is now enhanced by BuildingReports AI, which helps refine applicable manufacturer recalls and replacement notices, enabling service providers and facilities to address potential issues more quickly.
Building: Hearth N' Kettle
Items listed for Recall or Replacement/Upgrade
Device Type Manufacturer Model Number Date Qty
No recalled items found during this inspection.
Discrepancies
ScanID Location Problem Address Reference
INITIATING
Heat Detector
A9019345 Basement Prep Room Date Expired 1 NFPA72 Table
14.4.3.2 (17)(4)(c)
A9019344 Basement Stairs Date Expired 1 NFPA72 Table 14.4.3.2 (17)(4)(c)
A9019330 Attic above Kitchen (East)Date Expired 1 NFPA72 Table
14.4.3.2 (17)(4)(c)
A9019331 Attic above Kitchen (South)Date Expired 1 NFPA72 Table
14.4.3.2 (17)(4)(c)
Code References
NFPA72 Table 14.4.3.2 (17)
(4)(c)
After 15 years from initial installation, replace all devices or have 2 detectors per 100
laboratory tested.
Page of 5 12
Proposed Solutions Report
Cape Cod Alarm Download Date: 10/16/2026
Control Panel: 1 - Fire-Lite MS-10UDBuilding: Hearth N' Kettle
PROPOSED SOLUTIONS REPORT
Generated by: BuildingReports.com
The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark
where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials
basis.
ScanID Location Solution Model #Cost Fixed Date
INITIATING
Heat Detector
A9019345 Basement Prep Room Replace Twist out T/M
A9019344 Basement Stairs Replace Twist out T/M
A9019330 Attic above Kitchen (East)Replace Twist out T/M
A9019331 Attic above Kitchen (South)Replace Twist out T/M
Customer WO/PO #:
(none)
Internal WO/PO #:
(none)
Total: T/M
Page of 6 12
Inspection & Testing
Cape Cod Alarm Download Date: 10/16/2026
Control Panel: 1 - Fire-Lite MS-10UDBuilding: Hearth N' Kettle
INSPECTION & TESTING
Generated by: BuildingReports.com
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other .
Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.
Device Type Location Service Time Date
PASSED
Alarm
Kitchen Hood Kitchen Area Tested 3:25:35 PM 10/15/2026
Control
Annunciator Lobby South Entry Tested 3:42:07 PM 10/15/2026
Battery Kitchen Area in AES Transmitter Tested 3:28:02 PM 10/15/2026
Battery Kitchen Area in Fire Alarm Control Panel Tested 3:26:20 PM 10/15/2026
Battery Kitchen Area in Fire Alarm Control Panel Tested 3:27:32 PM 10/15/2026
Communicator Kitchen Area Tested 3:28:35 PM 10/15/2026
Control Panel Kitchen Area Rear Door Tested 3:24:31 PM 10/15/2026
Indicating
Horn/Strobe East Dining Area Entry Tested 3:46:46 PM 10/15/2026
Horn/Strobe Kitchen Rear Tested 3:37:21 PM 10/15/2026
Horn/Strobe South Dining Area Tested 3:39:47 PM 10/15/2026
Horn/Strobe South Dining Area Entry Tested 3:45:05 PM 10/15/2026
Horn/Strobe East Dining Area Exit Farrington Room Tested 3:49:15 PM 10/15/2026
Horn/Strobe Basement by door Tested 3:55:13 PM 10/15/2026
Strobe Ladies' Room Tested 3:41:04 PM 10/15/2026
Strobe Men's Room Tested 3:40:31 PM 10/15/2026
Initiating
Pull Station Kitchen Rear Tested 3:35:35 PM 10/15/2026
Page of 7 12
Inspection & Testing
Cape Cod Alarm Download Date: 10/16/2026
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
Pull Station South Entry Tested 3:45:51 PM 10/15/2026
Pull Station South Exit (Farrington Room)Tested 3:50:21 PM 10/15/2026
Pull Station Basement by door Tested 3:56:18 PM 10/15/2026
Smoke Detector Dining Area East Tested 3:47:32 PM 10/15/2026
Smoke Detector above Bar Tested 3:43:22 PM 10/15/2026
Smoke Detector Dining Area East Farrington Room Tested 3:48:13 PM 10/15/2026
Smoke Detector Basement Utility Arrea Tested 3:57:06 PM 10/15/2026
Monitor
Monitoring Alarm Signal Tested 3:29:05 PM 10/15/2026
Monitoring Trouble Signal Tested 3:29:15 PM 10/15/2026
FAILED/OTHER
Initiating
Heat Detector Basement Prep Room Tested 3:55:00 PM 10/15/2026
Heat Detector Basement Stairs Tested 3:53:58 PM 10/15/2026
Heat Detector Attic above Kitchen (East)Tested 3:34:28 PM 10/15/2026
Heat Detector Attic above Kitchen (South)Tested 3:34:14 PM 10/15/2026
Page of 8 12
Service Summary
Cape Cod Alarm Download Date: 10/16/2026
SERVICE SUMMARY
Generated by: BuildingReports.com
The Service Summary section provides an overview of the services performed in this report.
Building: Hearth N' Kettle
Device Type Service Quantity
PASSED
Annunciator Tested 1
Battery, Sealed Lead Acid Tested 3
Communicator, Mesh Radio Network Tested 1
Control Panel, Conventional Tested 1
Horn/Strobe Tested 6
Kitchen Hood, Dry Tested 1
Monitoring, Alarm Signal Tested 1
Monitoring, Trouble Signal Tested 1
Pull Station, Dual Action Tested 4
Smoke Detector Tested 4
Strobe Tested 2
Total 25
FAILED/OTHER
Heat Detector, Hardwire - Fixed Temperature Tested 4
Total 4
Grand Total 29
Page of 9 12
Sound and Visual Testing
Cape Cod Alarm Download Date: 10/16/2026
SOUND AND VISUAL TESTING
Generated by: BuildingReports.com
The Sound and Visual Testing section lists various points throughout your building where audible and visual alarm notification
devices were tested. Any bar-coded audible and visual devices will appear in the Inspection and Testing section of this report.
Items in this section are grouped by Passed or Failed/Other. Where specific decibel readings were recorded, they will appear
under the ambient and alarm columns. The Voice column indicates whether the Sound Test Point passed the Voice Intelligibility
requirements. The STI or Sound Transmission Index is shown if recorded.
Building: Hearth N' Kettle
Audible/Visual Appliances
Location Comment Ambient Alarm Synched ScanID
PASSED
Horn/Strobe
Kitchen Rear Passed ☐A9019323
South Dining Area Passed ☐A9019332
South Dining Area Entry Passed ☐A9019337
East Dining Area Entry Passed ☐A9019339
East Dining Area Exit Farrington
Room
Passed ☐A9019343
Basement by door Passed ☐A9019347
Strobe
Men's Room Passed ☐A9019333
Ladies' Room Passed ☐A9019334
Page of 10 12
Battery & Power Supply Testing
Cape Cod Alarm Download Date: 10/16/2026
Control Panel: 1 - Fire-Lite MS-10UDBuilding: Hearth N' Kettle
BATTERY & POWER SUPPLY TESTING
Generated by: BuildingReports.com
The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to
provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Battery
Type Location
Rated
Ah
Rated
Volts
Pre
Test
Post
Test
Min
Ah
Teste
d Ah
MFG
Date
PASSED
Sealed Lead Acid Kitchen Area in AES Transmitter 7AH 12V 100 80 11/15
/2024
Sealed Lead Acid Kitchen Area in Fire Alarm Control
Panel
7AH 12V 100 80 11/15
/2024
Sealed Lead Acid Kitchen Area in Fire Alarm Control Panel 7AH 12V 100 80 11/15/2024
Page of 11 12
Inventory & Warranty Report
Cape Cod Alarm Download Date: 10/16/2026
Control Panel: 1 - Fire-Lite MS-10UDBuilding: Hearth N' Kettle
INVENTORY & WARRANTY REPORT
Generated by: BuildingReports.com
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete
inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices
installed for two years or more are grouped together for easy reference.
Building: Hearth N' Kettle
Device or Type Category % of Inventory Quantity
Annunciator Control 3.45%1
Battery Control 10.34%3
Communicator Control 3.45%1
Control Panel Control 3.45%1
Heat Detector Initiating 13.79%4
Horn/Strobe Indicating 20.69%6
Kitchen Hood Alarm 3.45%1
Monitoring Monitor 6.90%2
Pull Station Initiating 13.79%4
Smoke Detector Initiating 13.79%4
Strobe Indicating 6.90%2
Type Qty Model #Description Install Date
NEW (UNDER 90 DAYS)
Ansul
Kitchen Hood 1 Ansul Dry 10/15/2026
Fire-Lite
Control Panel 1 MS-10UD Conventional 10/15/2026
IN SERVICE - 1 YEAR TO 2 YEARS
AES
Page of 12 12
Inventory & Warranty Report
Cape Cod Alarm Download Date: 10/16/2026
Type Qty Model #Description Install Date
IN SERVICE - 1 YEAR TO 2 YEARS (continued)
AES (continued)
Communicator 1 7788F Mesh Radio Network 11/15/2024
Monitoring 1 7788F Alarm Signal 11/15/2024
Monitoring 1 7788F Trouble Signal 11/15/2024
Power Patrol
Battery 3 FAS-1075 Sealed Lead Acid 11/15/2024
IN SERVICE - 25 YEARS OR OLDER
Ademco
Pull Station 1 MS-2 Dual Action 10/15/1998
ESL
Pull Station 1 Cat 45 key Dual Action 10/15/1998
FCI-Gamewell
Pull Station 1 MS-2 Dual Action 10/15/1998
Silent Knight
Pull Station 1 1347 key Dual Action 10/15/1998
System Sensor
Annunciator 1 Ann 80 10/15/1998
Horn/Strobe 6 P2R (replacement)10/15/1998
Smoke Detector 4 2W-TB 10/15/1998
Strobe 1 SRL (replacement)10/15/1998
Strobe 1 SRL(replacement)10/15/1998
Twist out style
Heat Detector 4 Twist out Hardwire - Fixed Temperature 11/15/1998