Loading...
HomeMy WebLinkAbout2026 FIRE ALARM INSPECTION BUILDING REPORT2026 Sunflower Marketplace - Building 2 923 Route 6A Yarmouthport, MA 02675 (508)362-5439 Building Contact:Nancy Basler Title:Contact Company:Cape Cod Alarm Contact:Chad Benaka Title:Service Tech Fire Alarm Systems INSPECTIONCERTIFICATE Oct 13, 2026Inspection Date: Tested to NFPA 72 Standards This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval. Page of 2 11 Executive Summary Cape Cod Alarm Download Date: 10/15/2026 EXECUTIVE SUMMARY Generated by: BuildingReports.com Building Information Sunflower Marketplace - Building 2 923 Route 6A Yarmouthport, MA 02675 United States of America Contact: Nancy Basler Phone: (508)367-6991 Fax: Mobile: Email: Inspection Performed By Cape Cod Alarm204 Old Townhouse RoadWest Yarmouth, MA 02673United States of America Inspector: Chad Benaka Phone: (508) 398-6316 Fax: Mobile: Email: service@capecodalarm.com System Control Unit Manufacturer: Silent Knight Inspection Date: 10/13/2026 IDC Style: E Model Number: 5208 Install Date: 10/13/2026 SLC Style: N/A Software Version:Version Date: 12/31/1969 NAC Style: E Location: 1st Floor Building 2 Main Entry Disconnect Location:Disconnect Type: Current Protection: Breaker Monitoring Company: Cape Cod Alarm Phone: (508)398-6316 Account #: S61392 Central Station Signal Verification Type: Mesh Radio Network Mfg: AES Model #: 7788F Test Time/Date: 10/13/26 10:06:05 AM Restore Time: 10:30 AM Note: Type of Signal Signal Confirmed Time Notes Trouble Signal 10:02 AM Alarm Signal 10:10 AM Page of 3 11 Executive Summary Cape Cod Alarm Download Date: 10/15/2026 Building: Sunflower Marketplace - Building 2 Contact: Nancy Basler Company: Cape Cod Alarm Inspector: Chad Benaka Inspection Summary Category Total Items Serviced Passed Failed/Other Qty %Qty %Qty %Qty % Control 5 29.41%5 100.00%5 100.00%0 0.00% Indicating 3 17.65%3 100.00%3 100.00%0 0.00% Initiating 7 41.18%7 100.00%7 100.00%0 0.00% Monitor 2 11.76%2 100.00%2 100.00%0 0.00% Totals 17 100%17 100.00%17 100.00%0 0.00% Certification Page of 4 11 Notes & Recommendations Cape Cod Alarm Download Date: 10/15/2026 NOTES & RECOMMENDATIONS Generated by: BuildingReports.com The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category. General Note Local smoke in room 107 is expired Local CO/Smoke in 107 will expire next year. Page of 5 11 Inspection & Testing Cape Cod Alarm Download Date: 10/15/2026 Control Panel: 1 - Silent Knight 5208Building: Sunflower Marketplace - Building 2 INSPECTION & TESTING Generated by: BuildingReports.com The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other . Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred. Device Type Location Service Time Date PASSED Control Battery In AES Transmitter Tested 10:05:00 AM 10/13/2026 Battery In Fire Aalarm Control Panel Tested 10:02:26 AM 10/13/2026 Battery In Fire Alarm Control Panel Tested 10:03:31 AM 10/13/2026 Communicator Attic Building 2 Main Entry above Fire Alarm Control Panel Tested 10:06:05 AM 10/13/2026 Control Panel 1st Floor Building 2 Main Entry Tested 10:01:27 AM 10/13/2026 Indicating Horn/Strobe 1st Floor Room 106 Side Door Tested 10:16:56 AM 10/13/2026 Horn/Strobe 1st Floor Room 107 Tested 10:09:34 AM 10/13/2026 Horn/Strobe 1st Floor Room 107 Side Door Tested 10:12:38 AM 10/13/2026 Initiating Heat Detector 1st Floor Room 107 Left Restroom Tested 10:26:03 AM 10/13/2026 Heat Detector 1st Floor Room 107 Right Restroom Tested 10:24:07 AM 10/13/2026 Pull Station 1st Floor Room 106 Side Door Tested 10:16:45 AM 10/13/2026 Pull Station 1st Floor Room 107 Tested 10:10:58 AM 10/13/2026 Pull Station 1st Floor Room 107 Side Door Tested 10:12:52 AM 10/13/2026 Smoke Detector 1st Floor Room 107 Tested 10:12:04 AM 10/13/2026 Smoke Detector 1st Floor Room 107 Tested 10:17:13 AM 10/13/2026 Monitor Monitoring Alarm Signal Tested 10:06:51 AM 10/13/2026 Page of 6 11 Inspection & Testing Cape Cod Alarm Download Date: 10/15/2026 Device Type Location Service Time Date PASSED (continued) Monitor (continued) Monitoring Trouble Signal Tested 10:07:19 AM 10/13/2026 Page of 7 11 Service Summary Cape Cod Alarm Download Date: 10/15/2026 SERVICE SUMMARY Generated by: BuildingReports.com The Service Summary section provides an overview of the services performed in this report. Building: Sunflower Marketplace - Building 2 Device Type Service Quantity PASSED Battery, Sealed Lead Acid Tested 3 Communicator, Mesh Radio Network Tested 1 Control Panel, Conventional Tested 1 Heat Detector, Hardwire - Combination Tested 2 Horn/Strobe Tested 3 Monitoring, Alarm Signal Tested 1 Monitoring, Trouble Signal Tested 1 Pull Station, Dual Action Tested 3 Smoke Detector Tested 2 Total 17 Grand Total 17 Page of 8 11 Sound and Visual Testing Cape Cod Alarm Download Date: 10/15/2026 SOUND AND VISUAL TESTING Generated by: BuildingReports.com The Sound and Visual Testing section lists various points throughout your building where audible and visual alarm notification devices were tested. Any bar-coded audible and visual devices will appear in the Inspection and Testing section of this report. Items in this section are grouped by Passed or Failed/Other. Where specific decibel readings were recorded, they will appear under the ambient and alarm columns. The Voice column indicates whether the Sound Test Point passed the Voice Intelligibility requirements. The STI or Sound Transmission Index is shown if recorded. Building: Sunflower Marketplace - Building 2 Audible/Visual Appliances Location Comment Ambient Alarm Synched ScanID PASSED Horn/Strobe 1st Floor Room 107 Passed ☐B9520887 1st Floor Room 106 Side Door Passed ☐B9520898 1st Floor Room 107 Side Door Passed ☐B9520900 Page of 9 11 Battery & Power Supply Testing Cape Cod Alarm Download Date: 10/15/2026 Control Panel: 1 - Silent Knight 5208Building: Sunflower Marketplace - Building 2 BATTERY & POWER SUPPLY TESTING Generated by: BuildingReports.com The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other. Battery Type Location Rated Ah Rated Volts Pre Test Post Test Min Ah Teste d Ah MFG Date PASSED Sealed Lead Acid In AES Transmitter 7 12 100%100%03/13 /2025 Sealed Lead Acid In Fire Aalarm Control Panel 7 12 100%100%02/13 /2025 Sealed Lead Acid In Fire Alarm Control Panel 7 12 100%100%02/13/2025 Page of 10 11 Inventory & Warranty Report Cape Cod Alarm Download Date: 10/15/2026 Control Panel: 1 - Silent Knight 5208Building: Sunflower Marketplace - Building 2 INVENTORY & WARRANTY REPORT Generated by: BuildingReports.com The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference. Building: Sunflower Marketplace - Building 2 Device or Type Category % of Inventory Quantity Battery Control 17.65%3 Communicator Control 5.88%1 Control Panel Control 5.88%1 Heat Detector Initiating 11.76%2 Horn/Strobe Indicating 17.65%3 Monitoring Monitor 11.76%2 Pull Station Initiating 17.65%3 Smoke Detector Initiating 11.76%2 Type Qty Model #Description Install Date NEW (UNDER 90 DAYS) AES Communicator 1 7788F Mesh Radio Network 10/13/2026 Fire-Lite Pull Station 3 BG-12L Dual Action 10/13/2026 Silent Knight Control Panel 1 5208 Conventional 10/13/2026 System Sensor Heat Detector 2 5601P Hardwire - Combination 10/13/2026 Smoke Detector 1 2100 10/13/2026 Page of 11 11 Inventory & Warranty Report Cape Cod Alarm Download Date: 10/15/2026 Type Qty Model #Description Install Date NEW (UNDER 90 DAYS)(continued) System Sensor (continued) Smoke Detector 1 2WBT 10/13/2026 Wheelock Horn/Strobe 3 NS-24MCW 10/13/2026 IN SERVICE - 1 YEAR TO 2 YEARS Power Patrol Battery 3 FAS1075 Sealed Lead Acid 02/13/2025 (manufacturer not specified) Monitoring 1 Alarm Signal 02/13/2025 Monitoring 1 Trouble Signal 02/13/2025