HomeMy WebLinkAbout2026 FIRE ALARM INSPECTION BUILDING REPORT2026
Sunflower Marketplace - Building 2
923 Route 6A
Yarmouthport, MA 02675
(508)362-5439
Building Contact:Nancy Basler
Title:Contact
Company:Cape Cod Alarm
Contact:Chad Benaka
Title:Service Tech
Fire Alarm Systems
INSPECTIONCERTIFICATE
Oct 13, 2026Inspection Date:
Tested to NFPA 72 Standards
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed
ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Page of 2 11
Executive Summary
Cape Cod Alarm Download Date: 10/15/2026
EXECUTIVE SUMMARY
Generated by: BuildingReports.com
Building Information
Sunflower Marketplace - Building 2
923 Route 6A
Yarmouthport, MA 02675
United States of America
Contact: Nancy Basler
Phone: (508)367-6991
Fax:
Mobile:
Email:
Inspection Performed By
Cape Cod Alarm204 Old Townhouse RoadWest Yarmouth, MA 02673United States of America
Inspector: Chad Benaka
Phone: (508) 398-6316
Fax:
Mobile:
Email: service@capecodalarm.com
System Control Unit
Manufacturer: Silent Knight Inspection Date: 10/13/2026 IDC Style: E
Model Number: 5208 Install Date: 10/13/2026 SLC Style: N/A
Software Version:Version Date: 12/31/1969 NAC Style: E
Location: 1st Floor Building 2 Main Entry Disconnect Location:Disconnect Type:
Current Protection: Breaker
Monitoring
Company: Cape Cod Alarm Phone: (508)398-6316 Account #: S61392
Central Station Signal Verification
Type: Mesh Radio Network Mfg: AES Model #: 7788F
Test Time/Date: 10/13/26 10:06:05 AM Restore Time: 10:30 AM Note:
Type of Signal Signal Confirmed Time Notes
Trouble Signal 10:02 AM
Alarm Signal 10:10 AM
Page of 3 11
Executive Summary
Cape Cod Alarm Download Date: 10/15/2026
Building: Sunflower Marketplace - Building 2
Contact: Nancy Basler
Company: Cape Cod Alarm
Inspector: Chad Benaka
Inspection Summary
Category
Total Items Serviced Passed Failed/Other
Qty %Qty %Qty %Qty %
Control 5 29.41%5 100.00%5 100.00%0 0.00%
Indicating 3 17.65%3 100.00%3 100.00%0 0.00%
Initiating 7 41.18%7 100.00%7 100.00%0 0.00%
Monitor 2 11.76%2 100.00%2 100.00%0 0.00%
Totals 17 100%17 100.00%17 100.00%0 0.00%
Certification
Page of 4 11
Notes & Recommendations
Cape Cod Alarm Download Date: 10/15/2026
NOTES & RECOMMENDATIONS
Generated by: BuildingReports.com
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the
building inspection. Notes are grouped by Category.
General Note
Local smoke in room 107 is expired Local CO/Smoke in 107 will expire next year.
Page of 5 11
Inspection & Testing
Cape Cod Alarm Download Date: 10/15/2026
Control Panel: 1 - Silent Knight 5208Building: Sunflower Marketplace - Building 2
INSPECTION & TESTING
Generated by: BuildingReports.com
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other .
Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.
Device Type Location Service Time Date
PASSED
Control
Battery In AES Transmitter Tested 10:05:00 AM 10/13/2026
Battery In Fire Aalarm Control Panel Tested 10:02:26 AM 10/13/2026
Battery In Fire Alarm Control Panel Tested 10:03:31 AM 10/13/2026
Communicator Attic Building 2 Main Entry above Fire Alarm
Control Panel
Tested 10:06:05 AM 10/13/2026
Control Panel 1st Floor Building 2 Main Entry Tested 10:01:27 AM 10/13/2026
Indicating
Horn/Strobe 1st Floor Room 106 Side Door Tested 10:16:56 AM 10/13/2026
Horn/Strobe 1st Floor Room 107 Tested 10:09:34 AM 10/13/2026
Horn/Strobe 1st Floor Room 107 Side Door Tested 10:12:38 AM 10/13/2026
Initiating
Heat Detector 1st Floor Room 107 Left Restroom Tested 10:26:03 AM 10/13/2026
Heat Detector 1st Floor Room 107 Right Restroom Tested 10:24:07 AM 10/13/2026
Pull Station 1st Floor Room 106 Side Door Tested 10:16:45 AM 10/13/2026
Pull Station 1st Floor Room 107 Tested 10:10:58 AM 10/13/2026
Pull Station 1st Floor Room 107 Side Door Tested 10:12:52 AM 10/13/2026
Smoke Detector 1st Floor Room 107 Tested 10:12:04 AM 10/13/2026
Smoke Detector 1st Floor Room 107 Tested 10:17:13 AM 10/13/2026
Monitor
Monitoring Alarm Signal Tested 10:06:51 AM 10/13/2026
Page of 6 11
Inspection & Testing
Cape Cod Alarm Download Date: 10/15/2026
Device Type Location Service Time Date
PASSED (continued)
Monitor (continued)
Monitoring Trouble Signal Tested 10:07:19 AM 10/13/2026
Page of 7 11
Service Summary
Cape Cod Alarm Download Date: 10/15/2026
SERVICE SUMMARY
Generated by: BuildingReports.com
The Service Summary section provides an overview of the services performed in this report.
Building: Sunflower Marketplace - Building 2
Device Type Service Quantity
PASSED
Battery, Sealed Lead Acid Tested 3
Communicator, Mesh Radio Network Tested 1
Control Panel, Conventional Tested 1
Heat Detector, Hardwire - Combination Tested 2
Horn/Strobe Tested 3
Monitoring, Alarm Signal Tested 1
Monitoring, Trouble Signal Tested 1
Pull Station, Dual Action Tested 3
Smoke Detector Tested 2
Total 17
Grand Total 17
Page of 8 11
Sound and Visual Testing
Cape Cod Alarm Download Date: 10/15/2026
SOUND AND VISUAL TESTING
Generated by: BuildingReports.com
The Sound and Visual Testing section lists various points throughout your building where audible and visual alarm notification
devices were tested. Any bar-coded audible and visual devices will appear in the Inspection and Testing section of this report.
Items in this section are grouped by Passed or Failed/Other. Where specific decibel readings were recorded, they will appear
under the ambient and alarm columns. The Voice column indicates whether the Sound Test Point passed the Voice Intelligibility
requirements. The STI or Sound Transmission Index is shown if recorded.
Building: Sunflower Marketplace - Building 2
Audible/Visual Appliances
Location Comment Ambient Alarm Synched ScanID
PASSED
Horn/Strobe
1st Floor Room 107 Passed ☐B9520887
1st Floor Room 106 Side Door Passed ☐B9520898
1st Floor Room 107 Side Door Passed ☐B9520900
Page of 9 11
Battery & Power Supply Testing
Cape Cod Alarm Download Date: 10/15/2026
Control Panel: 1 - Silent Knight 5208Building: Sunflower Marketplace - Building 2
BATTERY & POWER SUPPLY TESTING
Generated by: BuildingReports.com
The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to
provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Battery
Type Location
Rated
Ah
Rated
Volts
Pre
Test
Post
Test
Min
Ah
Teste
d Ah
MFG
Date
PASSED
Sealed Lead Acid In AES Transmitter 7 12 100%100%03/13
/2025
Sealed Lead Acid In Fire Aalarm Control Panel 7 12 100%100%02/13
/2025
Sealed Lead Acid In Fire Alarm Control Panel 7 12 100%100%02/13/2025
Page of 10 11
Inventory & Warranty Report
Cape Cod Alarm Download Date: 10/15/2026
Control Panel: 1 - Silent Knight 5208Building: Sunflower Marketplace - Building 2
INVENTORY & WARRANTY REPORT
Generated by: BuildingReports.com
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete
inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices
installed for two years or more are grouped together for easy reference.
Building: Sunflower Marketplace - Building 2
Device or Type Category % of Inventory Quantity
Battery Control 17.65%3
Communicator Control 5.88%1
Control Panel Control 5.88%1
Heat Detector Initiating 11.76%2
Horn/Strobe Indicating 17.65%3
Monitoring Monitor 11.76%2
Pull Station Initiating 17.65%3
Smoke Detector Initiating 11.76%2
Type Qty Model #Description Install Date
NEW (UNDER 90 DAYS)
AES
Communicator 1 7788F Mesh Radio Network 10/13/2026
Fire-Lite
Pull Station 3 BG-12L Dual Action 10/13/2026
Silent Knight
Control Panel 1 5208 Conventional 10/13/2026
System Sensor
Heat Detector 2 5601P Hardwire - Combination 10/13/2026
Smoke Detector 1 2100 10/13/2026
Page of 11 11
Inventory & Warranty Report
Cape Cod Alarm Download Date: 10/15/2026
Type Qty Model #Description Install Date
NEW (UNDER 90 DAYS)(continued)
System Sensor (continued)
Smoke Detector 1 2WBT 10/13/2026
Wheelock
Horn/Strobe 3 NS-24MCW 10/13/2026
IN SERVICE - 1 YEAR TO 2 YEARS
Power Patrol
Battery 3 FAS1075 Sealed Lead Acid 02/13/2025
(manufacturer not specified)
Monitoring 1 Alarm Signal 02/13/2025
Monitoring 1 Trouble Signal 02/13/2025