HomeMy WebLinkAbout2026 FIRE ALARM INSPECTION BUILDING REPORT (2)2026
Sunflower Marketplace - Building 1
923 Route 6A
Yarmouthport, MA 02675
(508)362-5439
Building Contact:Nancy Basler
Title:Contact
Company:Cape Cod Alarm
Contact:Chad Benaka
Title:Service Tech
Fire Alarm Systems
INSPECTIONCERTIFICATE
Oct 13, 2026Inspection Date:
Tested to NFPA 72 Standards
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed
ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Page of 2 14
Executive Summary
Cape Cod Alarm Download Date: 10/15/2026
EXECUTIVE SUMMARY
Generated by: BuildingReports.com
Building Information
Sunflower Marketplace - Building 1
923 Route 6A
Yarmouthport, MA 02675
United States of America
Contact: Nancy Basler
Phone: (508)367-6991
Fax:
Mobile:
Email:
Inspection Performed By
Cape Cod Alarm204 Old Townhouse RoadWest Yarmouth, MA 02673United States of America
Inspector: Chad Benaka
Phone: (508) 398-6316
Fax:
Mobile:
Email: service@capecodalarm.com
System Control Unit
Manufacturer: Notifier Inspection Date: 10/13/2026 IDC Style: E
Model Number: SFP-40B Install Date: 11/13/2024 SLC Style: N/A
Software Version:Version Date: 12/31/1969 NAC Style: E
Location: 1st Floor Building 1 Unit D Entry Foyer Disconnect Location:Disconnect Type:
Current Protection: Breaker
Monitoring
Company: Cape Cod Alarm Phone:Account #: S24993
Central Station Signal Verification
Type: Mesh Radio Network Mfg: AES Model #: 7788F
Test Time/Date: 10/13/26 12:58:36 PM Restore Time: 1:52 PM Note:
Type of Signal Signal Confirmed Time Notes
Trouble Signal 12:47 PM
Alarm Signal 1:26 PM
Page of 3 14
Executive Summary
Cape Cod Alarm Download Date: 10/15/2026
Building: Sunflower Marketplace - Building 1
Contact: Nancy Basler
Company: Cape Cod Alarm
Inspector: Chad Benaka
Inspection Summary
Category
Total Items Serviced Passed Failed/Other
Qty %Qty %Qty %Qty %
Control 5 19.23%5 100.00%5 100.00%0 0.00%
Indicating 5 19.23%5 100.00%5 100.00%0 0.00%
Initiating 14 53.85%14 100.00%5 35.71%9 64.29%
Monitor 2 7.69%2 100.00%2 100.00%0 0.00%
Totals 26 100%26 100.00%17 65.38%9 34.62%
Certification
Page of 4 14
Discrepancy Report
Cape Cod Alarm Download Date: 10/15/2026
Control Panel: 1 - Notifier SFP-40BBuilding: Sunflower Marketplace - Building 1
DISCREPANCY REPORT
Deficiency, Impairment, and Observation
Generated by: BuildingReports.com
The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where
appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a
manufacturer's replacement/upgrade program is included.
This section is now enhanced by BuildingReports AI, which helps refine applicable manufacturer recalls and replacement notices, enabling service providers and facilities to address potential issues more quickly.
Building: Sunflower Marketplace - Building 1
Items listed for Recall or Replacement/Upgrade
Device Type Manufacturer Model Number Date Qty
No recalled items found during this inspection.
Discrepancies
ScanID Location Problem Address Reference
INITIATING
Heat Detector
B9520972 1st Floor Building 1 Unit A Back Room Date Expired 1 NFPA72 Table
14.4.3.2 (17)(4)(c)
B9520971 1st Floor Building 1 Unit A Entry Area Date Expired 1 NFPA72 Table 14.4.3.2 (17)(4)(c)
B9520959 1st Floor Building 1 Unit B Entry Area Date Expired 1 NFPA72 Table
14.4.3.2 (17)(4)(c)
B9521063 1st Floor Building 1 Unit C Entry Area Date Expired 1 NFPA72 Table
14.4.3.2 (17)(4)(c)
B9521064 1st Floor Building 1 Unit C Front Left Office Date Expired 1 NFPA72 Table 14.4.3.2 (17)(4)(c)
Page of 5 14
Discrepancy Report
Cape Cod Alarm Download Date: 10/15/2026
ScanID Location Problem Address Reference
INITIATING (continued)
Heat Detector (continued)
B9521062 1st Floor Building 1 Unit C Rear Left Office Date Expired 1 NFPA72 Table 14.4.3.2 (17)(4)(c)
B9520970 1st Floor Building 1 Unit D Entry Area Date Expired 1 NFPA72 Table
14.4.3.2 (17)(4)(c)
B9520967 1st Floor Building 1 Unit D Entry Areaby
Reception
Date Expired 1 NFPA72 Table
14.4.3.2 (17)(4)(c)
B9520974 1st Floor Building 1 Unit D Repair Shop Date Expired 1 NFPA72 Table 14.4.3.2 (17)(4)(c)
Code References
NFPA72 Table 14.4.3.2 (17)(4)(c)After 15 years from initial installation, replace all devices or have 2 detectors per 100 laboratory tested.
Page of 6 14
Proposed Solutions Report
Cape Cod Alarm Download Date: 10/15/2026
Control Panel: 1 - Notifier SFP-40BBuilding: Sunflower Marketplace - Building 1
PROPOSED SOLUTIONS REPORT
Generated by: BuildingReports.com
The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark
where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials
basis.
ScanID Location Solution Model #Cost Fixed Date
INITIATING
Heat Detector
B9520972 1st Floor Building 1 Unit A Back
Room
Replace 281BPL T/M
B9520971 1st Floor Building 1 Unit A Entry Area Replace 281BPL T/M
B9520959 1st Floor Building 1 Unit B Entry Area Replace 281BPL T/M
B9521063 1st Floor Building 1 Unit C Entry
Area
Replace 281BPL T/M
B9521064 1st Floor Building 1 Unit C Front
Left Office
Replace 281BPL T/M
B9521062 1st Floor Building 1 Unit C Rear Left Office Replace 281BPL T/M
B9520970 1st Floor Building 1 Unit D Entry
Area
Replace 281BPL T/M
B9520967 1st Floor Building 1 Unit D Entry
Areaby Reception
Replace 281BPL T/M
B9520974 1st Floor Building 1 Unit D Repair Shop Replace 281BPL T/M
Customer WO/PO #:(none)Internal WO/PO #:(none)Total: T/M
Page of 7 14
Notes & Recommendations
Cape Cod Alarm Download Date: 10/15/2026
NOTES & RECOMMENDATIONS
Generated by: BuildingReports.com
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the
building inspection. Notes are grouped by Category.
General Note
No audible sound in Unit A,
Page of 8 14
Inspection & Testing
Cape Cod Alarm Download Date: 10/15/2026
Control Panel: 1 - Notifier SFP-40BBuilding: Sunflower Marketplace - Building 1
INSPECTION & TESTING
Generated by: BuildingReports.com
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other .
Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.
Device Type Location Service Time Date
PASSED
Control
Battery In AES Trasnmitter Tested 1:00:03 PM 10/13/2026
Battery In Fire Alaem Control Panel Tested 1:40:45 PM 10/13/2026
Battery In Fire Alarm Control Panel Tested 1:40:49 PM 10/13/2026
Communicator Attic above Fire Alarm Control Panel Tested 12:58:36 PM 10/13/2026
Control Panel 1st Floor Building 1 Unit D Entry Foyer Tested 1:06:26 PM 10/13/2026
Indicating
Horn/Strobe 1st Floor Building 1 Unit B Entry Foyer Tested 1:23:20 PM 10/13/2026
Horn/Strobe 1st Floor Building 1 Unit C Entry Foyer Tested 1:32:16 PM 10/13/2026
Horn/Strobe 1st Floor Building 1 Unit D Entry Foyer Tested 1:08:00 PM 10/13/2026
Horn/Strobe 1st Floor Building 1 Unit E Entry Foyer Tested 1:17:57 PM 10/13/2026
Strobe Outside Building 1 Unit D Tested 1:07:26 PM 10/13/2026
Initiating
Heat Detector 1st Floor Building 1 Unit D Entry Area Tested 1:11:10 PM 10/13/2026
Pull Station 1st Floor Building 1 Unit D Entry Foyer Tested 1:09:46 PM 10/13/2026
Smoke Detector 1st Floor Building 1 Unit D Entry Foyer Tested 1:10:42 PM 10/13/2026
Smoke Detector 1st Floor Building 1 Unit D Repair Shop Tested 1:16:01 PM 10/13/2026
Smoke Detector 1st Floor Building 1 Unit D Smoke by door to
Back Room
Tested 1:13:16 PM 10/13/2026
Monitor
Monitoring Alarm Signal Tested 12:59:24 PM 10/13/2026
Page of 9 14
Inspection & Testing
Cape Cod Alarm Download Date: 10/15/2026
Device Type Location Service Time Date
PASSED (continued)
Monitor (continued)
Monitoring Trouble Signal Tested 12:59:50 PM 10/13/2026
FAILED/OTHER
Initiating
Heat Detector 1st Floor Building 1 Unit A Back Room Tested 1:21:11 PM 10/13/2026
Heat Detector 1st Floor Building 1 Unit A Entry Area Tested 1:20:30 PM 10/13/2026
Heat Detector 1st Floor Building 1 Unit B Entry Area Tested 1:23:33 PM 10/13/2026
Heat Detector 1st Floor Building 1 Unit C Entry Area Tested 1:35:05 PM 10/13/2026
Heat Detector 1st Floor Building 1 Unit C Front Left Office Tested 1:34:28 PM 10/13/2026
Heat Detector 1st Floor Building 1 Unit C Rear Left Office Tested 1:35:59 PM 10/13/2026
Heat Detector 1st Floor Building 1 Unit D Entry Area Tested 1:18:32 PM 10/13/2026
Heat Detector 1st Floor Building 1 Unit D Entry Areaby
Reception
Tested 1:12:44 PM 10/13/2026
Heat Detector 1st Floor Building 1 Unit D Repair Shop Tested 1:14:33 PM 10/13/2026
Page of 10 14
Service Summary
Cape Cod Alarm Download Date: 10/15/2026
SERVICE SUMMARY
Generated by: BuildingReports.com
The Service Summary section provides an overview of the services performed in this report.
Building: Sunflower Marketplace - Building 1
Device Type Service Quantity
PASSED
Battery, Sealed Lead Acid Tested 3
Communicator, Mesh Radio Network Tested 1
Control Panel, Conventional Tested 1
Heat Detector, Hardwire - Combination Tested 1
Horn/Strobe Tested 4
Monitoring, Alarm Signal Tested 1
Monitoring, Trouble Signal Tested 1
Pull Station, Dual Action Tested 1
Smoke Detector Tested 3
Strobe Tested 1
Total 17
FAILED/OTHER
Heat Detector, Hardwire - Combination Tested 9
Total 9
Grand Total 26
Page of 11 14
Sound and Visual Testing
Cape Cod Alarm Download Date: 10/15/2026
SOUND AND VISUAL TESTING
Generated by: BuildingReports.com
The Sound and Visual Testing section lists various points throughout your building where audible and visual alarm notification
devices were tested. Any bar-coded audible and visual devices will appear in the Inspection and Testing section of this report.
Items in this section are grouped by Passed or Failed/Other. Where specific decibel readings were recorded, they will appear
under the ambient and alarm columns. The Voice column indicates whether the Sound Test Point passed the Voice Intelligibility
requirements. The STI or Sound Transmission Index is shown if recorded.
Building: Sunflower Marketplace - Building 1
Audible/Visual Appliances
Location Comment Ambient Alarm Synched ScanID
PASSED
Horn/Strobe
1st Floor Building 1 Unit C Entry
Foyer
Passed ☐B9520960
1st Floor Building 1 Unit B Entry Foyer Passed ☐B9520961
1st Floor Building 1 Unit D Entry
Foyer
Passed ☐B9520964
1st Floor Building 1 Unit E Entry
Foyer
Passed ☐B9520973
Strobe
Outside Building 1 Unit D Passed ☐B9520956
Page of 12 14
Battery & Power Supply Testing
Cape Cod Alarm Download Date: 10/15/2026
Control Panel: 1 - Notifier SFP-40BBuilding: Sunflower Marketplace - Building 1
BATTERY & POWER SUPPLY TESTING
Generated by: BuildingReports.com
The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to
provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Battery
Type Location
Rated
Ah
Rated
Volts
Pre
Test
Post
Test
Min
Ah
Teste
d Ah
MFG
Date
PASSED
Sealed Lead Acid In AES Trasnmitter 5 12 100%100%11/13
/2024
Sealed Lead Acid In Fire Alaem Control Panel 7 12 100%100%10/13
/2026
Sealed Lead Acid In Fire Alarm Control Panel 7 12 100%100%10/13/2026
Page of 13 14
Inventory & Warranty Report
Cape Cod Alarm Download Date: 10/15/2026
Control Panel: 1 - Notifier SFP-40BBuilding: Sunflower Marketplace - Building 1
INVENTORY & WARRANTY REPORT
Generated by: BuildingReports.com
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete
inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices
installed for two years or more are grouped together for easy reference.
Building: Sunflower Marketplace - Building 1
Device or Type Category % of Inventory Quantity
Battery Control 11.54%3
Communicator Control 3.85%1
Control Panel Control 3.85%1
Heat Detector Initiating 38.46%10
Horn/Strobe Indicating 15.38%4
Monitoring Monitor 7.69%2
Pull Station Initiating 3.85%1
Smoke Detector Initiating 11.54%3
Strobe Indicating 3.85%1
Type Qty Model #Description Install Date
NEW (UNDER 90 DAYS)
AES
Communicator 1 7788F Mesh Radio Network 10/13/2026
Power Patrol
Battery 2 FAS1075 Sealed Lead Acid 10/13/2026
Silent Knight
Pull Station 1 PS-DA Dual Action 10/13/2026
System Sensor
Heat Detector 1 5601P Hardwire - Combination 10/13/2026
Page of 14 14
Inventory & Warranty Report
Cape Cod Alarm Download Date: 10/15/2026
Type Qty Model #Description Install Date
NEW (UNDER 90 DAYS)(continued)
System Sensor (continued)
Smoke Detector 3 2100 10/13/2026
Wheelock
Horn/Strobe 4 MT-24-LSM 10/13/2026
Strobe 1 10/13/2026
(manufacturer not specified)
Monitoring 1 Alarm Signal 10/13/2026
Monitoring 1 Trouble Signal 10/13/2026
IN SERVICE - 1 YEAR TO 2 YEARS
Notifier
Control Panel 1 SFP-40B Conventional 11/13/2024
Power Patrol
Battery 1 FAS1055 Sealed Lead Acid 11/13/2024
IN SERVICE - 25 YEARS OR OLDER
Edwards
Heat Detector 9 281BPL Hardwire - Combination 10/13/1998