HomeMy WebLinkAbout2026 FIRE ALARM INSPECTION BUILDING REPORT (3)2026
Sunflower Marketplace - Building 4
923 Route 6A
Yarmouthport, MA 02675
(508)362-5439
Building Contact:Nancy Basler
Title:Contact
Company:Cape Cod Alarm
Contact:Chad Benaka
Title:Service Tech
Fire Alarm Systems
INSPECTIONCERTIFICATE
Oct 13, 2026Inspection Date:
Tested to NFPA 72 Standards
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed
ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Page of 2 14
Executive Summary
Cape Cod Alarm Download Date: 10/15/2026
EXECUTIVE SUMMARY
Generated by: BuildingReports.com
Building Information
Sunflower Marketplace - Building 4
923 Route 6A
Yarmouthport, MA 02675
United States of America
Contact: Nancy Basler
Phone: (508)367-6991
Fax:
Mobile:
Email:
Inspection Performed By
Cape Cod Alarm204 Old Townhouse RoadWest Yarmouth, MA 02673United States of America
Inspector: Chad Benaka
Phone: (508) 398-6316
Fax:
Mobile:
Email: service@capecodalarm.com
System Control Unit
Manufacturer: Silent Knight Inspection Date: 10/13/2026 IDC Style: E
Model Number: 5207 Install Date: 10/13/2026 SLC Style: N/A
Software Version:Version Date: 12/31/1969 NAC Style: E
Location: 1st Floor Building 4 Main Entry Foyer Disconnect Location:Disconnect Type:
Current Protection: Breaker
Monitoring
Company: Cape Cod Alarm Phone: (508)398-6316 Account #: S0210085
Central Station Signal Verification
Type: Mesh Radio Network Mfg: AES Model #: 7050-E
Test Time/Date: 10/13/26 11:46:01 AM Restore Time: 12:00 PM Note:
Type of Signal Signal Confirmed Time Notes
Trouble Signal 11:47 AM
Alarm Signal 11:48 AM
Page of 3 14
Executive Summary
Cape Cod Alarm Download Date: 10/15/2026
Building: Sunflower Marketplace - Building 4
Contact: Nancy Basler
Company: Cape Cod Alarm
Inspector: Chad Benaka
Inspection Summary
Category
Total Items Serviced Passed Failed/Other
Qty %Qty %Qty %Qty %
Control 5 16.67%5 100.00%5 100.00%0 0.00%
Indicating 4 13.33%4 100.00%4 100.00%0 0.00%
Initiating 19 63.33%19 100.00%13 68.42%6 31.58%
Monitor 2 6.67%2 100.00%2 100.00%0 0.00%
Totals 30 100%30 100.00%24 80.00%6 20.00%
Certification
Page of 4 14
Discrepancy Report
Cape Cod Alarm Download Date: 10/15/2026
Control Panel: 1 - Silent Knight 5207Building: Sunflower Marketplace - Building 4
DISCREPANCY REPORT
Deficiency, Impairment, and Observation
Generated by: BuildingReports.com
The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where
appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a
manufacturer's replacement/upgrade program is included.
This section is now enhanced by BuildingReports AI, which helps refine applicable manufacturer recalls and replacement notices, enabling service providers and facilities to address potential issues more quickly.
Building: Sunflower Marketplace - Building 4
Items listed for Recall or Replacement/Upgrade
Device Type Manufacturer Model Number Date Qty
No recalled items found during this inspection.
Discrepancies
ScanID Location Problem Address Reference
INITIATING
Heat Detector
B9520931 1st Floor Building 4 Unit N Hallway Date Expired 1 NFPA72 Table
14.4.3.2 (17)(4)(c)
B9520798 1st Floor Building 4 Unit O Hallway Date Expired 1 NFPA72 Table 14.4.3.2 (17)(4)(c)
B9520930 1st Floor Building 4 Unit O Hallway Rear Date Expired 1 NFPA72 Table
14.4.3.2 (17)(4)(c)
B9520829 1st Floor Building 4 Unit S Right Side Back
Room
Date Expired 1 NFPA72 Table
14.4.3.2 (17)(4)(c)
B9520830 2nd Floor Building 4 Unit P Date Expired 1 NFPA72 Table 14.4.3.2 (17)(4)(c)
Page of 5 14
Discrepancy Report
Cape Cod Alarm Download Date: 10/15/2026
ScanID Location Problem Address Reference
INITIATING (continued)
Heat Detector (continued)
B9520888 2nd Floor Building 4 Unit Q Date Expired 1 NFPA72 Table 14.4.3.2 (17)(4)(c)
Code References
NFPA72 Table 14.4.3.2 (17)
(4)(c)
After 15 years from initial installation, replace all devices or have 2 detectors per 100
laboratory tested.
Page of 6 14
Proposed Solutions Report
Cape Cod Alarm Download Date: 10/15/2026
Control Panel: 1 - Silent Knight 5207Building: Sunflower Marketplace - Building 4
PROPOSED SOLUTIONS REPORT
Generated by: BuildingReports.com
The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark
where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials
basis.
ScanID Location Solution Model #Cost Fixed Date
INITIATING
Heat Detector
B9520931 1st Floor Building 4 Unit N
Hallway
Replace 281A T/M
B9520798 1st Floor Building 4 Unit O Hallway Replace 281A T/M
B9520930 1st Floor Building 4 Unit O Hallway Rear Replace 281A T/M
B9520829 1st Floor Building 4 Unit S Right
Side Back Room
Replace 281A T/M
B9520830 2nd Floor Building 4 Unit P Replace 281A T/M
B9520888 2nd Floor Building 4 Unit Q Replace 281A T/M
Customer WO/PO #:(none)Internal WO/PO #:(none)Total: T/M
Page of 7 14
Notes & Recommendations
Cape Cod Alarm Download Date: 10/15/2026
NOTES & RECOMMENDATIONS
Generated by: BuildingReports.com
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the
building inspection. Notes are grouped by Category.
General Note
Unit S ( Salon) has no audible devices inside this shop.
No access to Unit M
AES radio needs to be replaced to a red fire radio and we need to get rid of the power situation inside the fire panel and put in a transformer for the radio power.
Page of 8 14
Inspection & Testing
Cape Cod Alarm Download Date: 10/15/2026
Control Panel: 1 - Silent Knight 5207Building: Sunflower Marketplace - Building 4
INSPECTION & TESTING
Generated by: BuildingReports.com
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other .
Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.
Device Type Location Service Time Date
PASSED
Control
Battery In Fire Alarm Control Panel Tested 11:49:32 AM 10/13/2026
Battery In Fire Alarm Control Panel Tested 11:49:45 AM 10/13/2026
Battery in AES Transmitter Tested 11:48:08 AM 10/13/2026
Communicator 1st Floor Building 4 Main Entry Foyer Tested 11:46:01 AM 10/13/2026
Control Panel 1st Floor Building 4 Main Entry Foyer Tested 11:45:22 AM 10/13/2026
Indicating
Horn 1st Floor Building 4 Unit L Front Entry Tested 11:53:41 AM 10/13/2026
Horn 2nd Floor Building 4 Main Entry Foyer Tested 11:40:36 AM 10/13/2026
Horn 2nd Floor Building 4 at top of stairs Tested 11:30:10 AM 10/13/2026
Strobe Outside Main Entry Foyer Tested 11:50:25 AM 10/13/2026
Initiating
Heat Detector 1st Floor Building 4 Unit L Hallway Rear Tested 11:55:40 AM 10/13/2026
Heat Detector 1st Floor Building 4 Unit S Right Side Tested 11:18:57 AM 10/13/2026
Pull Station 1st Floor Building 4 Unit L Front Entry Tested 11:52:36 AM 10/13/2026
Pull Station 1st Floor Building 4 Unit S Front Entry Tested 11:17:52 AM 10/13/2026
Pull Station 2nd Floor Building 4 at top of stairs Tested 11:28:20 AM 10/13/2026
Smoke Detector 1st Floor Building 4 Unit L Hallway Front Tested 11:53:15 AM 10/13/2026
Smoke Detector 1st Floor Building 4 Unit L Hallway Rear Tested 11:55:09 AM 10/13/2026
Smoke Detector 1st Floor Building 4 Unit L Room 101 Tested 11:54:47 AM 10/13/2026
Page of 9 14
Inspection & Testing
Cape Cod Alarm Download Date: 10/15/2026
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
Smoke Detector 1st Floor Building 4 Unit L Room 102 Tested 11:56:28 AM 10/13/2026
Smoke Detector 1st Floor Building 4 Unit L Staff Room Tested 11:54:14 AM 10/13/2026
Smoke Detector 1st Floor Building 4 Unit S Right Side Tested 11:19:38 AM 10/13/2026
Smoke Detector 2nd Floor Building 4 Main Entry Foyer Tested 11:40:14 AM 10/13/2026
Smoke Detector 2nd Floor Building 4 at top of stairs Tested 11:31:23 AM 10/13/2026
Monitor
Monitoring Alarm Signal Tested 11:47:30 AM 10/13/2026
Monitoring Trouble Signal Tested 11:47:08 AM 10/13/2026
FAILED/OTHER
Initiating
Heat Detector 1st Floor Building 4 Unit N Hallway Tested 11:33:13 AM 10/13/2026
Heat Detector 1st Floor Building 4 Unit O Hallway Tested 11:38:04 AM 10/13/2026
Heat Detector 1st Floor Building 4 Unit O Hallway Rear Tested 11:38:38 AM 10/13/2026
Heat Detector 1st Floor Building 4 Unit S Right Side Back
Room
Tested 11:20:51 AM 10/13/2026
Heat Detector 2nd Floor Building 4 Unit P Tested 11:24:27 AM 10/13/2026
Heat Detector 2nd Floor Building 4 Unit Q Tested 11:25:26 AM 10/13/2026
Page of 10 14
Service Summary
Cape Cod Alarm Download Date: 10/15/2026
SERVICE SUMMARY
Generated by: BuildingReports.com
The Service Summary section provides an overview of the services performed in this report.
Building: Sunflower Marketplace - Building 4
Device Type Service Quantity
PASSED
Battery, Sealed Lead Acid Tested 3
Communicator, Mesh Radio Network Tested 1
Control Panel, Conventional Tested 1
Heat Detector, Hardwire - Combination Tested 2
Horn Tested 3
Monitoring, Trouble Signal Tested 1
Monitoring, Alarm Signal Tested 1
Pull Station, Dual Action Tested 2
Pull Station, Single Action Tested 1
Smoke Detector Tested 8
Strobe Tested 1
Total 24
FAILED/OTHER
Heat Detector, Hardwire - Combination Tested 6
Total 6
Grand Total 30
Page of 11 14
Sound and Visual Testing
Cape Cod Alarm Download Date: 10/15/2026
SOUND AND VISUAL TESTING
Generated by: BuildingReports.com
The Sound and Visual Testing section lists various points throughout your building where audible and visual alarm notification
devices were tested. Any bar-coded audible and visual devices will appear in the Inspection and Testing section of this report.
Items in this section are grouped by Passed or Failed/Other. Where specific decibel readings were recorded, they will appear
under the ambient and alarm columns. The Voice column indicates whether the Sound Test Point passed the Voice Intelligibility
requirements. The STI or Sound Transmission Index is shown if recorded.
Building: Sunflower Marketplace - Building 4
Audible/Visual Appliances
Location Comment Ambient Alarm Synched ScanID
PASSED
Strobe
Outside Main Entry Foyer Passed ☐B9520944
Page of 12 14
Battery & Power Supply Testing
Cape Cod Alarm Download Date: 10/15/2026
Control Panel: 1 - Silent Knight 5207Building: Sunflower Marketplace - Building 4
BATTERY & POWER SUPPLY TESTING
Generated by: BuildingReports.com
The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to
provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Battery
Type Location
Rated
Ah
Rated
Volts
Pre
Test
Post
Test
Min
Ah
Teste
d Ah
MFG
Date
PASSED
Sealed Lead Acid In Fire Alarm Control Panel 7 12 100%100%10/13
/2026
Sealed Lead Acid In Fire Alarm Control Panel 7 12 100%100%10/13
/2026
Sealed Lead Acid in AES Transmitter 7 12 100%100%10/13/2026
Page of 13 14
Inventory & Warranty Report
Cape Cod Alarm Download Date: 10/15/2026
Control Panel: 1 - Silent Knight 5207Building: Sunflower Marketplace - Building 4
INVENTORY & WARRANTY REPORT
Generated by: BuildingReports.com
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete
inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices
installed for two years or more are grouped together for easy reference.
Building: Sunflower Marketplace - Building 4
Device or Type Category % of Inventory Quantity
Battery Control 10.00%3
Communicator Control 3.33%1
Control Panel Control 3.33%1
Heat Detector Initiating 26.67%8
Horn Indicating 10.00%3
Monitoring Monitor 6.67%2
Pull Station Initiating 10.00%3
Smoke Detector Initiating 26.67%8
Strobe Indicating 3.33%1
Type Qty Model #Description Install Date
NEW (UNDER 90 DAYS)
AES
Communicator 1 7050-E Mesh Radio Network 10/13/2026
Fire-Lite
Pull Station 1 BG-12 Dual Action 10/13/2026
Notifier
Pull Station 1 NBG-12L Dual Action 10/13/2026
Power Patrol
Battery 3 FAS1075 Sealed Lead Acid 10/13/2026
Page of 14 14
Inventory & Warranty Report
Cape Cod Alarm Download Date: 10/15/2026
Type Qty Model #Description Install Date
NEW (UNDER 90 DAYS)(continued)
Silent Knight
Control Panel 1 5207 Conventional 10/13/2026
System Sensor
Heat Detector 2 5601P Hardwire - Combination 10/13/2026
Smoke Detector 5 2100 10/13/2026
Smoke Detector 1 2WBT 10/13/2026
Wheelock
Strobe 1 10/13/2026
(manufacturer not specified)
Monitoring 1 Alarm Signal 10/13/2026
Monitoring 1 Trouble Signal 10/13/2026
IN SERVICE - 25 YEARS OR OLDER
Chemtron
Heat Detector 6 281A Hardwire - Combination 10/13/1986
Edwards
Horn 3 31T-115-R 10/13/1986
Pull Station 1 270 Single Action 10/13/1986
System Sensor
Smoke Detector 2 SD-800 10/13/1986