HomeMy WebLinkAbout2026 FIRE ALARM INSPECTION BUILDING REPORT (4)2026
Sunflower Marketplace - Building 3
923 Route 6A
Yarmouthport, MA 02675
(508)362-4100
Building Contact:Nancy Basler
Title:Contact
Company:Cape Cod Alarm
Contact:Chad Benaka
Title:Service Tech
Fire Alarm Systems
INSPECTIONCERTIFICATE
Oct 13, 2026Inspection Date:
Tested to NFPA 72 Standards
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed
ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Page of 2 14
Executive Summary
Cape Cod Alarm Download Date: 10/15/2026
EXECUTIVE SUMMARY
Generated by: BuildingReports.com
Building Information
Sunflower Marketplace - Building 3
923 Route 6A
Yarmouthport, MA 02675
United States of America
Contact: Nancy Basler
Phone: (508)367-6991
Fax:
Mobile:
Email:
Inspection Performed By
Cape Cod Alarm204 Old Townhouse RoadWest Yarmouth, MA 02673United States of America
Inspector: Chad Benaka
Phone: (508) 398-6316
Fax:
Mobile:
Email: service@capecodalarm.com
System Control Unit
Manufacturer: Silent Knight Inspection Date: 10/13/2026 IDC Style: E
Model Number: 5208 Install Date: 10/13/2026 SLC Style: N/A
Software Version:Version Date: 12/31/1969 NAC Style: E
Location: 1st Floor Building 3 Unit K Front Entry Disconnect Location:Disconnect Type:
Current Protection: Breaker
Monitoring
Company: Cape Cod Alarm Phone: (508)398-6316 Account #: S61140
Central Station Signal Verification
Type: Mesh Radio Network Mfg: AES Model #: 7788F
Test Time/Date: 10/13/26 8:59:45 AM Restore Time: 9:49 AM Note:
Type of Signal Signal Confirmed Time Notes
Supervisory Signal 8:45 AM
Trouble Signal 8:27 AM
Page of 3 14
Executive Summary
Cape Cod Alarm Download Date: 10/15/2026
Building: Sunflower Marketplace - Building 3
Contact: Nancy Basler
Company: Cape Cod Alarm
Inspector: Chad Benaka
Type of Signal (continued)Signal Confirmed Time Notes
Alarm Signal 8:39 AM
Inspection Summary
Category
Total Items Serviced Passed Failed/Other
Qty %Qty %Qty %Qty %
Control 5 8.77%5 100.00%5 100.00%0 0.00%
Indicating 24 42.11%24 100.00%24 100.00%0 0.00%
Initiating 25 43.86%25 100.00%25 100.00%0 0.00%
Monitor 3 5.26%3 100.00%3 100.00%0 0.00%
Totals 57 100%57 100.00%57 100.00%0 0.00%
Certification
Page of 4 14
Notes & Recommendations
Cape Cod Alarm Download Date: 10/15/2026
NOTES & RECOMMENDATIONS
Generated by: BuildingReports.com
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the
building inspection. Notes are grouped by Category.
General Note
Unit H which is a dentist office has no system fire alarm devices in it.
Page of 5 14
Inspection & Testing
Cape Cod Alarm Download Date: 10/15/2026
Control Panel: 1 - Silent Knight 5208Building: Sunflower Marketplace - Building 3
INSPECTION & TESTING
Generated by: BuildingReports.com
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other .
Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.
Device Type Location Service Time Date
PASSED
Control
Battery Building 3 in AES Transmitter Tested 9:00:21 AM 10/13/2026
Battery Building 3 in Fire Alarm Control Panel Tested 9:01:47 AM 10/13/2026
Battery Building 3 in Fire Alarm Control Panel Tested 9:02:01 AM 10/13/2026
Communicator 1st Floor Building 3 Unit K Front Entry Tested 8:59:45 AM 10/13/2026
Control Panel 1st Floor Building 3 Unit K Front Entry Tested 8:58:14 AM 10/13/2026
Indicating
Horn/Strobe 1st Floor Building 3 Rear Foyer Tested 9:15:31 AM 10/13/2026
Horn/Strobe 1st Floor Building 3 Unit G Reception Front Entry Tested 9:20:20 AM 10/13/2026
Horn/Strobe 1st Floor Building 3 Unit I Room 104 Front
Entry
Tested 9:08:50 AM 10/13/2026
Horn/Strobe 1st Floor Building 3 Unit I Room 105 Rear
Entry
Tested 9:11:57 AM 10/13/2026
Horn/Strobe 1st Floor Building 3 Unit K Back Storage of Room 103 Tested 8:52:42 AM 10/13/2026
Horn/Strobe 1st Floor Building 3 Unit K Room 103 Front
Entry
Tested 9:03:46 AM 10/13/2026
Horn/Strobe 2nd Floor Building 3 Unit G Conference
Room 112
Tested 9:25:24 AM 10/13/2026
Horn/Strobe 2nd Floor Building 3 Unit G Hallway by Room
113
Tested 9:29:18 AM 10/13/2026
Horn/Strobe 2nd Floor Building 3 Unit G Room 108 Tested 9:37:21 AM 10/13/2026
Page of 6 14
Inspection & Testing
Cape Cod Alarm Download Date: 10/15/2026
Device Type Location Service Time Date
PASSED (continued)
Indicating (continued)
Horn/Strobe 2nd Floor Building 3 Unit G Room 109 Tested 9:39:04 AM 10/13/2026
Horn/Strobe 2nd Floor Building 3 Unit G Room 110 Tested 9:40:34 AM 10/13/2026
Horn/Strobe 2nd Floor Building 3 Unit G Room 110 Tested 9:40:59 AM 10/13/2026
Horn/Strobe 2nd Floor Building 3 Unit G Room 111 Tested 9:26:00 AM 10/13/2026
Strobe 1st Floor Building 3 Unit G Main Reception Restroom Tested 9:21:52 AM 10/13/2026
Strobe 1st Floor Building 3 Unit I Room 104
Restroom
Tested 9:07:30 AM 10/13/2026
Strobe 1st Floor Building 3 Unit I Room 105
Restroom
Tested 9:12:36 AM 10/13/2026
Strobe 1st Floor Building 3 Unit K Room 103 Back Restroom Tested 8:49:03 AM 10/13/2026
Strobe 1st Floor Building 3 Unit K Room 103
Restroom
Tested 8:56:50 AM 10/13/2026
Strobe 2nd Floor Building 3 Unit G Restroom by
Room 114
Tested 9:30:32 AM 10/13/2026
Strobe 2nd Floor Building 3 Unit G Room 108 Restroom Tested 9:38:01 AM 10/13/2026
Strobe 2nd Floor Building 3 Unit G Room 109 Restroom Tested 9:38:28 AM 10/13/2026
Strobe 2nd Floor Building 3 Unit G Room 110
Restroom
Tested 9:41:32 AM 10/13/2026
Strobe 2nd Floor Building 3 Unit G Room 111
Restroom
Tested 9:24:08 AM 10/13/2026
Strobe 2nd Floor Building 3 Unit G Room 112 Restroom Tested 9:26:46 AM 10/13/2026
Initiating
CO Detector 1st Floor Building 3 Unit I Room 105 Tested 9:14:11 AM 10/13/2026
CO Detector 1st Floor Building 3 Unit K Room 103 Tested 8:47:20 AM 10/13/2026
CO Detector 2nd Floor Building 3 Unit G Hallway by Room
109
Tested 9:39:36 AM 10/13/2026
Page of 7 14
Inspection & Testing
Cape Cod Alarm Download Date: 10/15/2026
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
CO Detector 2nd Floor Building 3 Unit G Hallway by Room 112 Tested 9:28:16 AM 10/13/2026
Pull Station 1st Floor Building 3 Rear Foyer Tested 9:16:11 AM 10/13/2026
Pull Station 1st Floor Building 3 Unit G Reception Front
Entry
Tested 9:19:54 AM 10/13/2026
Pull Station 1st Floor Building 3 Unit I Room 104 Front Entry Tested 9:08:32 AM 10/13/2026
Pull Station 1st Floor Building 3 Unit I Room 105 Rear
Entry
Tested 9:11:34 AM 10/13/2026
Pull Station 1st Floor Building 3 Unit K Back Storage of
Room 103
Tested 8:52:48 AM 10/13/2026
Pull Station 1st Floor Building 3 Unit K Room 103 Front
Entry
Tested 9:04:20 AM 10/13/2026
Smoke Detector 1st Floor Building 3 Rear Foyer Tested 9:16:42 AM 10/13/2026
Smoke Detector 1st Floor Building 3 Unit G Reception Front
Entry
Tested 9:21:07 AM 10/13/2026
Smoke Detector 1st Floor Building 3 Unit I Room 104 Tested 9:10:11 AM 10/13/2026
Smoke Detector 1st Floor Building 3 Unit I Room 105 Tested 9:13:09 AM 10/13/2026
Smoke Detector 1st Floor Building 3 Unit K Back Storage of Room 103 Tested 9:05:04 AM 10/13/2026
Smoke Detector 1st Floor Building 3 Unit K Room 103 Tested 8:48:05 AM 10/13/2026
Smoke Detector 1st Floor Building 3 Unit K Room 103 by
Restroom
Tested 9:45:05 AM 10/13/2026
Smoke Detector 2nd Floor Building 3 Unit G Hallway by Room 108 Tested 9:34:33 AM 10/13/2026
Smoke Detector 2nd Floor Building 3 Unit G Hallway by Room
110
Tested 9:40:16 AM 10/13/2026
Smoke Detector 2nd Floor Building 3 Unit G Hallway by Room
113
Tested 9:29:53 AM 10/13/2026
Smoke Detector 2nd Floor Building 3 Unit G Room 108 Tested 9:36:53 AM 10/13/2026
Page of 8 14
Inspection & Testing
Cape Cod Alarm Download Date: 10/15/2026
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
Smoke Detector 2nd Floor Building 3 Unit G Room 109 Tested 9:38:50 AM 10/13/2026
Smoke Detector 2nd Floor Building 3 Unit G Room 110 Tested 9:41:18 AM 10/13/2026
Smoke Detector 2nd Floor Building 3 Unit G Room 111 Tested 9:26:13 AM 10/13/2026
Smoke Detector 2nd Floor Building 3 Unit G Room 112 Tested 9:27:33 AM 10/13/2026
Monitor
Monitoring Alarm Signal Tested 9:02:11 AM 10/13/2026
Monitoring Supervisory Signal Tested 9:03:11 AM 10/13/2026
Monitoring Trouble Signal Tested 9:02:59 AM 10/13/2026
Page of 9 14
Service Summary
Cape Cod Alarm Download Date: 10/15/2026
SERVICE SUMMARY
Generated by: BuildingReports.com
The Service Summary section provides an overview of the services performed in this report.
Building: Sunflower Marketplace - Building 3
Device Type Service Quantity
PASSED
Battery, Sealed Lead Acid Tested 3
CO Detector Tested 4
Communicator, Mesh Radio Network Tested 1
Control Panel, Conventional Tested 1
Horn/Strobe Tested 13
Monitoring, Supervisory Signal Tested 1
Monitoring, Trouble Signal Tested 1
Monitoring, Alarm Signal Tested 1
Pull Station, Dual Action Tested 6
Smoke Detector Tested 15
Strobe Tested 11
Total 57
Grand Total 57
Page of 10 14
Sound and Visual Testing
Cape Cod Alarm Download Date: 10/15/2026
SOUND AND VISUAL TESTING
Generated by: BuildingReports.com
The Sound and Visual Testing section lists various points throughout your building where audible and visual alarm notification
devices were tested. Any bar-coded audible and visual devices will appear in the Inspection and Testing section of this report.
Items in this section are grouped by Passed or Failed/Other. Where specific decibel readings were recorded, they will appear
under the ambient and alarm columns. The Voice column indicates whether the Sound Test Point passed the Voice Intelligibility
requirements. The STI or Sound Transmission Index is shown if recorded.
Building: Sunflower Marketplace - Building 3
Audible/Visual Appliances
Location Comment Ambient Alarm Synched ScanID
PASSED
Horn/Strobe
1st Floor Building 3 Unit K Room
103 Front Entry
Passed ☐B9520841
1st Floor Building 3 Rear Foyer Passed ☐B9520853
1st Floor Building 3 Unit G
Reception Front Entry
Passed ☐B9520860
1st Floor Building 3 Unit I Room
104 Front Entry
Passed ☐B9520864
1st Floor Building 3 Unit I Room 105 Rear Entry Passed ☐B9520869
1st Floor Building 3 Unit K Back Storage of Room 103 Passed ☐B9520871
2nd Floor Building 3 Unit G
Conference Room 112
Passed ☐B9520875
2nd Floor Building 3 Unit G
Hallway by Room 113
Passed ☐B9520878
2nd Floor Building 3 Unit G Room 111 Passed ☐B9520881
2nd Floor Building 3 Unit G Room
110
Passed ☐B9520882
Page of 11 14
Sound and Visual Testing
Cape Cod Alarm Download Date: 10/15/2026
Location Comment Ambient Alarm Synched ScanID
PASSED (continued)
Horn/Strobe (continued)
2nd Floor Building 3 Unit G Room 110 Passed ☐B9520891
2nd Floor Building 3 Unit G Room
109
Passed ☐B9520893
2nd Floor Building 3 Unit G Room
108
Passed ☐B9520897
Strobe
2nd Floor Building 3 Unit G Room
112 Restroom
Passed ☐B9520856
1st Floor Building 3 Unit G Main Reception Restroom Passed ☐B9520858
1st Floor Building 3 Unit K Room
103 Restroom
Passed ☐B9520863
1st Floor Building 3 Unit I Room
105 Restroom
Passed ☐B9520867
1st Floor Building 3 Unit I Room 104 Restroom Passed ☐B9520870
1st Floor Building 3 Unit K Room
103 Back Restroom
Passed ☐B9520873
2nd Floor Building 3 Unit G
Restroom by Room 114
Passed ☐B9520876
2nd Floor Building 3 Unit G Room
111 Restroom
Passed ☐B9520879
2nd Floor Building 3 Unit G Room 109 Restroom Passed ☐B9520894
2nd Floor Building 3 Unit G Room
108 Restroom
Passed ☐B9520895
2nd Floor Building 3 Unit G Room
110 Restroom
Passed ☐B9520908
Page of 12 14
Battery & Power Supply Testing
Cape Cod Alarm Download Date: 10/15/2026
Control Panel: 1 - Silent Knight 5208Building: Sunflower Marketplace - Building 3
BATTERY & POWER SUPPLY TESTING
Generated by: BuildingReports.com
The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to
provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Battery
Type Location
Rated
Ah
Rated
Volts
Pre
Test
Post
Test
Min
Ah
Teste
d Ah
MFG
Date
PASSED
Sealed Lead Acid Building 3 in AES Transmitter 7 12 100%100%09/13
/2025
Sealed Lead Acid Building 3 in Fire Alarm Control
Panel
7 12 100%100%09/13
/2025
Sealed Lead Acid Building 3 in Fire Alarm Control Panel 7 12 100%100%09/13/2025
Page of 13 14
Inventory & Warranty Report
Cape Cod Alarm Download Date: 10/15/2026
Control Panel: 1 - Silent Knight 5208Building: Sunflower Marketplace - Building 3
INVENTORY & WARRANTY REPORT
Generated by: BuildingReports.com
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete
inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices
installed for two years or more are grouped together for easy reference.
Building: Sunflower Marketplace - Building 3
Device or Type Category % of Inventory Quantity
Battery Control 5.26%3
CO Detector Initiating 7.02%4
Communicator Control 1.75%1
Control Panel Control 1.75%1
Horn/Strobe Indicating 22.81%13
Monitoring Monitor 5.26%3
Pull Station Initiating 10.53%6
Smoke Detector Initiating 26.32%15
Strobe Indicating 19.30%11
Type Qty Model #Description Install Date
NEW (UNDER 90 DAYS)
AES
Communicator 1 7788F Mesh Radio Network 10/13/2026
Fire-Lite
Pull Station 6 BG-12 Dual Action 10/13/2026
Silent Knight
Control Panel 1 5208 Conventional 10/13/2026
System Sensor
Horn/Strobe 9 P2RL-LF 10/13/2026
Page of 14 14
Inventory & Warranty Report
Cape Cod Alarm Download Date: 10/15/2026
Type Qty Model #Description Install Date
NEW (UNDER 90 DAYS)(continued)
System Sensor (continued)
Smoke Detector 12 2151 10/13/2026
Smoke Detector 3 2WBT 10/13/2026
Strobe 1 SR 10/13/2026
Strobe 10 SRL 10/13/2026
Wheelock
Horn/Strobe 4 ZRS-MCW-FR 10/13/2026
(manufacturer not specified)
Monitoring 1 Alarm Signal 10/13/2026
Monitoring 1 Supervisory Signal 10/13/2026
Monitoring 1 Trouble Signal 10/13/2026
IN SERVICE - 1 YEAR TO 2 YEARS
Power Patrol
Battery 3 FAS1075 Sealed Lead Acid 09/13/2025
IN SERVICE - 5 YEARS TO 10 YEARS
System Sensor
CO Detector 2 CO1224T 11/13/2019
CO Detector 2 CO1224T 10/13/2017