HomeMy WebLinkAbout2026 FIRE ALARM INSPECTION BUILDING REPORT (4)2026 Sunflower Marketplace - Building 3 923 Route 6A Yarmouthport, MA 02675 (508)362-4100 Building Contact:Nancy Basler Title:Contact Company:Cape Cod Alarm Contact:Chad Benaka Title:Service Tech Fire Alarm Systems INSPECTIONCERTIFICATE Oct 13, 2026Inspection Date: Tested to NFPA 72 Standards This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval. Page of 2 14 Executive Summary Cape Cod Alarm Download Date: 10/15/2026 EXECUTIVE SUMMARY Generated by: BuildingReports.com Building Information Sunflower Marketplace - Building 3 923 Route 6A Yarmouthport, MA 02675 United States of America Contact: Nancy Basler Phone: (508)367-6991 Fax: Mobile: Email: Inspection Performed By Cape Cod Alarm204 Old Townhouse RoadWest Yarmouth, MA 02673United States of America Inspector: Chad Benaka Phone: (508) 398-6316 Fax: Mobile: Email: service@capecodalarm.com System Control Unit Manufacturer: Silent Knight Inspection Date: 10/13/2026 IDC Style: E Model Number: 5208 Install Date: 10/13/2026 SLC Style: N/A Software Version:Version Date: 12/31/1969 NAC Style: E Location: 1st Floor Building 3 Unit K Front Entry Disconnect Location:Disconnect Type: Current Protection: Breaker Monitoring Company: Cape Cod Alarm Phone: (508)398-6316 Account #: S61140 Central Station Signal Verification Type: Mesh Radio Network Mfg: AES Model #: 7788F Test Time/Date: 10/13/26 8:59:45 AM Restore Time: 9:49 AM Note: Type of Signal Signal Confirmed Time Notes Supervisory Signal 8:45 AM Trouble Signal 8:27 AM Page of 3 14 Executive Summary Cape Cod Alarm Download Date: 10/15/2026 Building: Sunflower Marketplace - Building 3 Contact: Nancy Basler Company: Cape Cod Alarm Inspector: Chad Benaka Type of Signal (continued)Signal Confirmed Time Notes Alarm Signal 8:39 AM Inspection Summary Category Total Items Serviced Passed Failed/Other Qty %Qty %Qty %Qty % Control 5 8.77%5 100.00%5 100.00%0 0.00% Indicating 24 42.11%24 100.00%24 100.00%0 0.00% Initiating 25 43.86%25 100.00%25 100.00%0 0.00% Monitor 3 5.26%3 100.00%3 100.00%0 0.00% Totals 57 100%57 100.00%57 100.00%0 0.00% Certification Page of 4 14 Notes & Recommendations Cape Cod Alarm Download Date: 10/15/2026 NOTES & RECOMMENDATIONS Generated by: BuildingReports.com The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category. General Note Unit H which is a dentist office has no system fire alarm devices in it. Page of 5 14 Inspection & Testing Cape Cod Alarm Download Date: 10/15/2026 Control Panel: 1 - Silent Knight 5208Building: Sunflower Marketplace - Building 3 INSPECTION & TESTING Generated by: BuildingReports.com The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other . Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred. Device Type Location Service Time Date PASSED Control Battery Building 3 in AES Transmitter Tested 9:00:21 AM 10/13/2026 Battery Building 3 in Fire Alarm Control Panel Tested 9:01:47 AM 10/13/2026 Battery Building 3 in Fire Alarm Control Panel Tested 9:02:01 AM 10/13/2026 Communicator 1st Floor Building 3 Unit K Front Entry Tested 8:59:45 AM 10/13/2026 Control Panel 1st Floor Building 3 Unit K Front Entry Tested 8:58:14 AM 10/13/2026 Indicating Horn/Strobe 1st Floor Building 3 Rear Foyer Tested 9:15:31 AM 10/13/2026 Horn/Strobe 1st Floor Building 3 Unit G Reception Front Entry Tested 9:20:20 AM 10/13/2026 Horn/Strobe 1st Floor Building 3 Unit I Room 104 Front Entry Tested 9:08:50 AM 10/13/2026 Horn/Strobe 1st Floor Building 3 Unit I Room 105 Rear Entry Tested 9:11:57 AM 10/13/2026 Horn/Strobe 1st Floor Building 3 Unit K Back Storage of Room 103 Tested 8:52:42 AM 10/13/2026 Horn/Strobe 1st Floor Building 3 Unit K Room 103 Front Entry Tested 9:03:46 AM 10/13/2026 Horn/Strobe 2nd Floor Building 3 Unit G Conference Room 112 Tested 9:25:24 AM 10/13/2026 Horn/Strobe 2nd Floor Building 3 Unit G Hallway by Room 113 Tested 9:29:18 AM 10/13/2026 Horn/Strobe 2nd Floor Building 3 Unit G Room 108 Tested 9:37:21 AM 10/13/2026 Page of 6 14 Inspection & Testing Cape Cod Alarm Download Date: 10/15/2026 Device Type Location Service Time Date PASSED (continued) Indicating (continued) Horn/Strobe 2nd Floor Building 3 Unit G Room 109 Tested 9:39:04 AM 10/13/2026 Horn/Strobe 2nd Floor Building 3 Unit G Room 110 Tested 9:40:34 AM 10/13/2026 Horn/Strobe 2nd Floor Building 3 Unit G Room 110 Tested 9:40:59 AM 10/13/2026 Horn/Strobe 2nd Floor Building 3 Unit G Room 111 Tested 9:26:00 AM 10/13/2026 Strobe 1st Floor Building 3 Unit G Main Reception Restroom Tested 9:21:52 AM 10/13/2026 Strobe 1st Floor Building 3 Unit I Room 104 Restroom Tested 9:07:30 AM 10/13/2026 Strobe 1st Floor Building 3 Unit I Room 105 Restroom Tested 9:12:36 AM 10/13/2026 Strobe 1st Floor Building 3 Unit K Room 103 Back Restroom Tested 8:49:03 AM 10/13/2026 Strobe 1st Floor Building 3 Unit K Room 103 Restroom Tested 8:56:50 AM 10/13/2026 Strobe 2nd Floor Building 3 Unit G Restroom by Room 114 Tested 9:30:32 AM 10/13/2026 Strobe 2nd Floor Building 3 Unit G Room 108 Restroom Tested 9:38:01 AM 10/13/2026 Strobe 2nd Floor Building 3 Unit G Room 109 Restroom Tested 9:38:28 AM 10/13/2026 Strobe 2nd Floor Building 3 Unit G Room 110 Restroom Tested 9:41:32 AM 10/13/2026 Strobe 2nd Floor Building 3 Unit G Room 111 Restroom Tested 9:24:08 AM 10/13/2026 Strobe 2nd Floor Building 3 Unit G Room 112 Restroom Tested 9:26:46 AM 10/13/2026 Initiating CO Detector 1st Floor Building 3 Unit I Room 105 Tested 9:14:11 AM 10/13/2026 CO Detector 1st Floor Building 3 Unit K Room 103 Tested 8:47:20 AM 10/13/2026 CO Detector 2nd Floor Building 3 Unit G Hallway by Room 109 Tested 9:39:36 AM 10/13/2026 Page of 7 14 Inspection & Testing Cape Cod Alarm Download Date: 10/15/2026 Device Type Location Service Time Date PASSED (continued) Initiating (continued) CO Detector 2nd Floor Building 3 Unit G Hallway by Room 112 Tested 9:28:16 AM 10/13/2026 Pull Station 1st Floor Building 3 Rear Foyer Tested 9:16:11 AM 10/13/2026 Pull Station 1st Floor Building 3 Unit G Reception Front Entry Tested 9:19:54 AM 10/13/2026 Pull Station 1st Floor Building 3 Unit I Room 104 Front Entry Tested 9:08:32 AM 10/13/2026 Pull Station 1st Floor Building 3 Unit I Room 105 Rear Entry Tested 9:11:34 AM 10/13/2026 Pull Station 1st Floor Building 3 Unit K Back Storage of Room 103 Tested 8:52:48 AM 10/13/2026 Pull Station 1st Floor Building 3 Unit K Room 103 Front Entry Tested 9:04:20 AM 10/13/2026 Smoke Detector 1st Floor Building 3 Rear Foyer Tested 9:16:42 AM 10/13/2026 Smoke Detector 1st Floor Building 3 Unit G Reception Front Entry Tested 9:21:07 AM 10/13/2026 Smoke Detector 1st Floor Building 3 Unit I Room 104 Tested 9:10:11 AM 10/13/2026 Smoke Detector 1st Floor Building 3 Unit I Room 105 Tested 9:13:09 AM 10/13/2026 Smoke Detector 1st Floor Building 3 Unit K Back Storage of Room 103 Tested 9:05:04 AM 10/13/2026 Smoke Detector 1st Floor Building 3 Unit K Room 103 Tested 8:48:05 AM 10/13/2026 Smoke Detector 1st Floor Building 3 Unit K Room 103 by Restroom Tested 9:45:05 AM 10/13/2026 Smoke Detector 2nd Floor Building 3 Unit G Hallway by Room 108 Tested 9:34:33 AM 10/13/2026 Smoke Detector 2nd Floor Building 3 Unit G Hallway by Room 110 Tested 9:40:16 AM 10/13/2026 Smoke Detector 2nd Floor Building 3 Unit G Hallway by Room 113 Tested 9:29:53 AM 10/13/2026 Smoke Detector 2nd Floor Building 3 Unit G Room 108 Tested 9:36:53 AM 10/13/2026 Page of 8 14 Inspection & Testing Cape Cod Alarm Download Date: 10/15/2026 Device Type Location Service Time Date PASSED (continued) Initiating (continued) Smoke Detector 2nd Floor Building 3 Unit G Room 109 Tested 9:38:50 AM 10/13/2026 Smoke Detector 2nd Floor Building 3 Unit G Room 110 Tested 9:41:18 AM 10/13/2026 Smoke Detector 2nd Floor Building 3 Unit G Room 111 Tested 9:26:13 AM 10/13/2026 Smoke Detector 2nd Floor Building 3 Unit G Room 112 Tested 9:27:33 AM 10/13/2026 Monitor Monitoring Alarm Signal Tested 9:02:11 AM 10/13/2026 Monitoring Supervisory Signal Tested 9:03:11 AM 10/13/2026 Monitoring Trouble Signal Tested 9:02:59 AM 10/13/2026 Page of 9 14 Service Summary Cape Cod Alarm Download Date: 10/15/2026 SERVICE SUMMARY Generated by: BuildingReports.com The Service Summary section provides an overview of the services performed in this report. Building: Sunflower Marketplace - Building 3 Device Type Service Quantity PASSED Battery, Sealed Lead Acid Tested 3 CO Detector Tested 4 Communicator, Mesh Radio Network Tested 1 Control Panel, Conventional Tested 1 Horn/Strobe Tested 13 Monitoring, Supervisory Signal Tested 1 Monitoring, Trouble Signal Tested 1 Monitoring, Alarm Signal Tested 1 Pull Station, Dual Action Tested 6 Smoke Detector Tested 15 Strobe Tested 11 Total 57 Grand Total 57 Page of 10 14 Sound and Visual Testing Cape Cod Alarm Download Date: 10/15/2026 SOUND AND VISUAL TESTING Generated by: BuildingReports.com The Sound and Visual Testing section lists various points throughout your building where audible and visual alarm notification devices were tested. Any bar-coded audible and visual devices will appear in the Inspection and Testing section of this report. Items in this section are grouped by Passed or Failed/Other. Where specific decibel readings were recorded, they will appear under the ambient and alarm columns. The Voice column indicates whether the Sound Test Point passed the Voice Intelligibility requirements. The STI or Sound Transmission Index is shown if recorded. Building: Sunflower Marketplace - Building 3 Audible/Visual Appliances Location Comment Ambient Alarm Synched ScanID PASSED Horn/Strobe 1st Floor Building 3 Unit K Room 103 Front Entry Passed ☐B9520841 1st Floor Building 3 Rear Foyer Passed ☐B9520853 1st Floor Building 3 Unit G Reception Front Entry Passed ☐B9520860 1st Floor Building 3 Unit I Room 104 Front Entry Passed ☐B9520864 1st Floor Building 3 Unit I Room 105 Rear Entry Passed ☐B9520869 1st Floor Building 3 Unit K Back Storage of Room 103 Passed ☐B9520871 2nd Floor Building 3 Unit G Conference Room 112 Passed ☐B9520875 2nd Floor Building 3 Unit G Hallway by Room 113 Passed ☐B9520878 2nd Floor Building 3 Unit G Room 111 Passed ☐B9520881 2nd Floor Building 3 Unit G Room 110 Passed ☐B9520882 Page of 11 14 Sound and Visual Testing Cape Cod Alarm Download Date: 10/15/2026 Location Comment Ambient Alarm Synched ScanID PASSED (continued) Horn/Strobe (continued) 2nd Floor Building 3 Unit G Room 110 Passed ☐B9520891 2nd Floor Building 3 Unit G Room 109 Passed ☐B9520893 2nd Floor Building 3 Unit G Room 108 Passed ☐B9520897 Strobe 2nd Floor Building 3 Unit G Room 112 Restroom Passed ☐B9520856 1st Floor Building 3 Unit G Main Reception Restroom Passed ☐B9520858 1st Floor Building 3 Unit K Room 103 Restroom Passed ☐B9520863 1st Floor Building 3 Unit I Room 105 Restroom Passed ☐B9520867 1st Floor Building 3 Unit I Room 104 Restroom Passed ☐B9520870 1st Floor Building 3 Unit K Room 103 Back Restroom Passed ☐B9520873 2nd Floor Building 3 Unit G Restroom by Room 114 Passed ☐B9520876 2nd Floor Building 3 Unit G Room 111 Restroom Passed ☐B9520879 2nd Floor Building 3 Unit G Room 109 Restroom Passed ☐B9520894 2nd Floor Building 3 Unit G Room 108 Restroom Passed ☐B9520895 2nd Floor Building 3 Unit G Room 110 Restroom Passed ☐B9520908 Page of 12 14 Battery & Power Supply Testing Cape Cod Alarm Download Date: 10/15/2026 Control Panel: 1 - Silent Knight 5208Building: Sunflower Marketplace - Building 3 BATTERY & POWER SUPPLY TESTING Generated by: BuildingReports.com The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other. Battery Type Location Rated Ah Rated Volts Pre Test Post Test Min Ah Teste d Ah MFG Date PASSED Sealed Lead Acid Building 3 in AES Transmitter 7 12 100%100%09/13 /2025 Sealed Lead Acid Building 3 in Fire Alarm Control Panel 7 12 100%100%09/13 /2025 Sealed Lead Acid Building 3 in Fire Alarm Control Panel 7 12 100%100%09/13/2025 Page of 13 14 Inventory & Warranty Report Cape Cod Alarm Download Date: 10/15/2026 Control Panel: 1 - Silent Knight 5208Building: Sunflower Marketplace - Building 3 INVENTORY & WARRANTY REPORT Generated by: BuildingReports.com The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference. Building: Sunflower Marketplace - Building 3 Device or Type Category % of Inventory Quantity Battery Control 5.26%3 CO Detector Initiating 7.02%4 Communicator Control 1.75%1 Control Panel Control 1.75%1 Horn/Strobe Indicating 22.81%13 Monitoring Monitor 5.26%3 Pull Station Initiating 10.53%6 Smoke Detector Initiating 26.32%15 Strobe Indicating 19.30%11 Type Qty Model #Description Install Date NEW (UNDER 90 DAYS) AES Communicator 1 7788F Mesh Radio Network 10/13/2026 Fire-Lite Pull Station 6 BG-12 Dual Action 10/13/2026 Silent Knight Control Panel 1 5208 Conventional 10/13/2026 System Sensor Horn/Strobe 9 P2RL-LF 10/13/2026 Page of 14 14 Inventory & Warranty Report Cape Cod Alarm Download Date: 10/15/2026 Type Qty Model #Description Install Date NEW (UNDER 90 DAYS)(continued) System Sensor (continued) Smoke Detector 12 2151 10/13/2026 Smoke Detector 3 2WBT 10/13/2026 Strobe 1 SR 10/13/2026 Strobe 10 SRL 10/13/2026 Wheelock Horn/Strobe 4 ZRS-MCW-FR 10/13/2026 (manufacturer not specified) Monitoring 1 Alarm Signal 10/13/2026 Monitoring 1 Supervisory Signal 10/13/2026 Monitoring 1 Trouble Signal 10/13/2026 IN SERVICE - 1 YEAR TO 2 YEARS Power Patrol Battery 3 FAS1075 Sealed Lead Acid 09/13/2025 IN SERVICE - 5 YEARS TO 10 YEARS System Sensor CO Detector 2 CO1224T 11/13/2019 CO Detector 2 CO1224T 10/13/2017