Loading...
HomeMy WebLinkAbout2013 Dec 03 - 2014 Jul 11 - Emails with Sullivan Engineering Inc.i : vonHone, Amy From: vonHone, Amy Sent: Friday, July 11, 2014 2:17 PM To: 'chuck@sullivanengin.com';john(a�sullivanengin.com Subject: RE: 47 Harbor Road Chuck- Bruce has reviewed the paperwork and has the following comments: 1. Proposed 1st Floor Plan -the entryway into the proposed family room must be flush with the hallway wall. It looks like there is a small bump out on both sides of the entryway that may encourage the installation of a door which would not be allowed. 2. Septic Plan - Provide the proposed Gallons Per Day the system is designed for. Show the distance between the leaching and the groundwater/bottom of test hole. Provide the test hole results from the original plan. Please call or email with questions. Thanks, Amy Amy L. von Hone, R.S., C.H.O. ' Assistant Health Director Yarmouth Health Department ', -----Original Message----- ' From: Chuck Rowland [mailto:chuck@sullivanengin.com] Sent: Thursday, July 10, 2014 1:44 PM To: vonHone, Amy; john@sullivanengin.com Subject: RE: 47 Harbor Road j Amy, There was a revision to the plans, so please find attached the floor plans for the existing and the proposed I addition. The third floor tower was eliminated. �i Thanks Chuck Rowland, EIT Sullivan Engineering Inc. 7 Parker Road/ P.O. Box 659 Osterville, MA 02655 508-428-3344 508-428-9617 (fax) ' -----Original Message----- � From: vonHone, Amy [mailto:AVonHone@yarmouth.ma.us] Sent: Tuesday, July 08, 2014 12:02 PM To: 'john@sullivanengin.com' ' Cc: chuck@sullivanengin.com ' i vonHone, Amy Prom: Chuck Rowland <chuck@sullivanengin.com> Sent: Thursday, July 10, 2014 1:44 PM To: vonHone, Amy;john@sullivanengin.com Subject: RE: 47 Harbor Road Attachments: Plans-ZBA set 5.15.2014.pdf Amy, There was a revision to the plans, so please find attached the floor plans for the existing and the proposed ' addition. The third floor tower was eliminated. Thanks Chuck Rowland, EIT I Sullivan Engineering Inc. ' 7 Parker Road/ P.O. Box 659 ' Osterville, MA 02655 508-428-3344 508-428-9617 (fax) ----Original Message---- , From: vonHone, Amy fmailto:AVonHoneCcDvarmouth.ma.usl Sent: Tuesday, July 08, 2014 12:02 PM To: 'john@sullivanengin.com' , Cc: chuckC�Dsullivanenain.com ' Subject: RE: 47 Harbor Road Hi John & Chuck- ' Could you scan me a revised set of floor plans that label the rest of the rooms and I will review them with the � director to confirm his approval. ( Also, is there a page for the third floor tower? � Also, septic plan will be fine if you can add an outline of the proposed leach showing the perimeter dimensions, and on the plan view, show the new lines from the d-box into the leach chambers. I will consult with Bruce once I get the floor plans. Thanks, Amy , Amy L. von Hone, R.S., C.H.0. Assistant Health Director Yarmouth Health Department ----Original Message---- From: John O'Dea fmailto:iohnCcDsullivanenpin.coml Sent: Monday, June 30, 2014 12:33 PM To: vonHone, Amy Cc: chuckC�sullivanenqin.com i Subject: RE: 47 Harbor Road Would end of day work? 4:15? John O'Dea, PE Sullivan Engineering Inc. 7 Parker Road/ P.O. Box 659 Osterville, MA 02655 508-428-3344 508-428-9617 (fax) ---Original Message--- From: vonHone, Amy fmailto:AVonHone(a�varmouth.ma.usl Sent: Monday, June 30, 2014 11:07 AM To: 'john@sullivanengin.com' Subject: RE: 47 Harbor Road I am swamped with plan reviews but your office is certainly welcome to drop off a plan and explain the highlights to me for an eventual formal review. i should be in the office this afternoon if you want to give me a timeframe. Thanks, Amy ' Amy L. von Hone, R.S., C.H.O. ' Assistant Health Director ' Yarmouth Health Department --Original Message--- ' From: John O'Dea (mailto:iohnCtDsullivanenqin.coml Sent: Monday, June 30, 2014 10:59 AM , To: vonHone, Amy ' Ca chuckla�sullivanenqin.com � Subject: RE: 47 Harbor Road Amy We have been to Conservation for this project, and I believe it has or will be reviewed by Zoning shortly. Would it be possible for Chuck Rowland from our office to stop by to review our plan. I think we should be very close to having all the information needed for a permit- but want to dot all the I's and cross all the Ys. Chuck lives in Yarmouth, so beginning or end of day would be preferable. John O'Dea, PE Sullivan Engineering Inc. 7 Parker Road/ P.O. Box 659 Osterville, MA 02655 508-428-3344 ' 508�28-9617 (fax) ' z -----Original Message----- From: vonHone, Amy fmailto:AVonHonena.varmouth.ma.usl Sent: Thursday, December 05, 2013 9:01 AM To: 'john@sullivanengin.com' Subject: RE: 47 Harbor Road No additional test hole needed -good sand and no groundwater and original test hole was done under the new code Amy L. von Hone, R.S., C.H.O. Assistant Health Director Yarmouth Health Department ----Original Message----- From: John O'Dea fmailto:iohn(casullivanenain.coml Sent: Thursday, December 05, 2013 8:57 AM To: vonHone, Amy Subject: RE: 47 Harbor Road Amy, Thank you. The goal will be to do this variance free, but I will get back to you once we are further into a real design. The other question I have is - is an additional perc test required? I have attached the plan for the existing ' system. ' John O'Dea, PE Sullivan Engineering Inc. 7 Parker Road/ P.O. Box 659 Osterville, MA 02655 508-428-3344 � 508-428-9617 (fax) ; -----Original Message----- From: vonHone, Amy fmailto:AVonHoneCcDvarmouth.ma.usl Sent: Wednesday, December 04, 2013 9:13 AM To: 'john@sullivanengin.com' i Subject: RE: 47 Harbor Road Yes -the leach can be extended at an angle and still get credit for the sidewall. Just let us know if you think it will need variances for the leach expansion -that may require full BOH review. Amy Amy L. von Hone, R.S., C.H.O. ', Assistant Health Director Yarmouth Health Department � 3 i - ---Original Message--- From: John O'Dea fmailto:iohn(c�sullivanenain.coml Sent: Tuesday, December 03, 2013 1:49 PM To: vonHone, Amy ' Subject: 47 Harbor Road Amy, j We are working on a proposed addition /expansion plan for a house located at 47 Harbor Road. i The septic system was upgraded for 3 bedrooms in 2008. We are trying to determine if there is room to expand the system. On the attached Addition Sketch I have showed the approximate location of the leaching field in the drive. Because of the property line and building setbacks it is not possible to extend the rectangle linearly. Could we put an angle in the field for an additional chamber and still get credit for sidewall? John O'Dea, PE Sullivan Engineering Inc. 7 Parker Road/ P.O. Box 659 Osterville, MA 02655 508-428-3344 508-428-9617 (fax) � i I I I 4 I